TEMPERATURE AND HUMIDITY

DIGITAL CONTROLLER WITH

SERIAL COMMUNICATION

4.2 - Parameters configuration

- Access the function F01 pressing simultaneously the keys

and

for 2 seconds until appearing

, releasing after that. Soon it will appear

, and then press

(short touch).

- Use the keys

and

to enter acess code (123) and, when ready press

to confirm.

- Use the keys

and

to access the desired function.

-After selecting the function, press

(short touch) to visualize the value configured for that function.

- Use the keys

and

to change the value, and when ready, press

to memorize the configured

value and return to the menu of functions.
- To leave the menu of functions and return to normal operation, press

until appear

.

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

4. CONFIGURATIONS

4.1 - Temperature and humidity adjust (SETPOINTS):

- Press

for 2 seconds until

appears, then release it. The indication

and the adjusted

temperature for THERM output will appear.
- Use the keys

and

to change the value and then press

to record it.

- Now

and adjusted humidity for HUMID output will appear.

- Use the keys

and

to change the value and then press

again.

-Then, if the AUX output is set to control (F14 = 0, 1, 2 or 3)it may appear

or

.

- Use the keys

and

to change the value for theAUX output and then press

to record it.

SET

SET

SET

SET

4.4 - Parameters description

MT-530 %uper

1. DESCRIPTION

MT-530 %uper

is an instrument that indicates and controls the environment temperature and

humidity, indicated for low and average relative air humidity (from 20 to 85%, without condensation) and
temperature of -10 to 70ºC. Its sensors of temperature and humidity are joined in an only bulb, that
reduces the space in wiring of the installation.

The instrument has serial communication for connection with the

via Internet.

Product complies with UL Inc. (United States and Canada).

®

SITRAD

2. APPLICATION

3. TECHNICAL SPECIFICATIONS

• Humidificators/dehumidificators
• Grains drying
• Laboratories
• Surgical rooms
• Climatized cellars
• Information technology centers

MT-530 Super - 115 or 230 Vac ±10%(50/60 Hz)
MT-530L Super - 12 or 24 Vac/dc

-10 to 70.0 ºC ±1.5°C (with resolution of 0.1°C)
14 to 158 ºF ±3°F (with resolution of 1°F)

20 to 85%RH ±5%RH (with resolution of 0.1%RH)

5(3)A/250Vac 1/8HP (each output)

71 x 28 x 71 mm

0 to 50°C

32 to 122°F

10 to 90% RH (without condensation)

- Power Supply:

- Control Temperature:

- Control Humidity:
- Load current:
- Dimensions:
- Operation temperature:

- Operation humidity:

Description

Fun

Access code: 123 (one hundred and twenty-three)

hermostat operation mode (THERM output)

Minimum setpoint allowed to the user (thermostat)

Maximum setpoint allowed to the user (thermostat)

Control differential (hysteresis) of the thermostat

Minimum delay to turn the thermostat output on

Humidistat operation mode (HUMID output)

Minimum setpoint allowed to the user (humidistat)

Maximum setpoint allowed to the user (humidistat)

Control differential (hysteresis) of the humidistat

Minimum delay to turn the humidistat output on

Humidity output (time on)

Humidity output (time off)

Auxiliary output operation mode (AUX)

Minimum setpoint allowed to the user (AUX output)

T

CELSIUS

FAHRENHEIT

Min.

-99

0 - refrig.

-10.0

-10.0

0

0

0 - dehum.

0

0

0

0

0

0

0

0

Max.

999

1 - heat

70.0

70.0

20.0

999

1 - hum.

100

100

20.0

999

999

999

10

100

Unit

-

-

°C

°C

°C

seg.

-

%RH

%RH

%RH

sec.

sec.

sec.

-

-

Standard

-

-10.0

70.0

1.5

0

0 - refrig.

1 - hum.

0

100

5

0

5

5

5

0

Min.

-99

0 - refrig.

14

14

0

0

0 - dehum.

0

0

0

0

0

0

0

0

Max.

999

1 - heat

158

158

36

999

1 - umid.

100

100

20.0

999

999

999

10

100

Unit

-

-

°F

°F

°F

seg.

-

%RH

%RH

%RH

sec.

sec.

sec.

-

-

Standard

-

0 - refrig.

14

158

3

0

1 - hum.

0

100

5

0

5

5

5

0

Maximum setpoint allowed to the user AUX output

Control differential (hysteresis) of the AUX output

Minimum delay to turn the AUX output on

Time base of AUX output timer

AUX output (time on)

AUX output (time off)

Minimum delay to turn the AUX output on (alarm mode)

Acting point of Buzzer by low temperature

Acting point of Buzzer by high temperature

Acting point of Buzzer by low

Acting point of Buzzer by high

Maximum time of the activated THERM output to activate the alarm

Maximum time of the activated HUMID output to activate the alarm

(

)

Buzzer operation mode

humidity

humidity

Low room temperature alarm

High room temperature alarm

Low room humidity alarm

High room humidity alarm

0

0

0

0

0

0

-10.0

-10.0

0

0

0

0

-10.0

-10.0

0

0

0

0

100

20.0

999

999

999

999

70.0

70.0

100

100

999

1

70.0

70.0

100

100

999

999

-

-

sec.

-

sec.

sec.

°C

°C

%RH

%RH

min.

-

°C

°C

%RH

%RH

min.

min.

100

5

0

0

5

5

-10.0

70.0

0

100

0

1

-10.0

70.0

0

100

0

0

0

0

0

0

0

0

14

14

0

0

0

0

14

14

0

0

0

0

100

20.0

999

999

999

999

158

158

100

100

999

1

158

158

100

100

999

999

100

5

0

0

5

5

14

158

0

100

0

1

14

158

0

100

0

0

-

-

sec.

-

sec.

sec.

°F

°F

%RH

%RH

min.

-

°F

°F

%RH

%RH

min.

min.

Maximum time of the activated AUX output to activate the alarm

Buzzer time on

Buzzer time off

Inhibition time of Buzzer during electrical supply

Display mode

Temperature display offset

Humidity display offset

Network equipment address RS-485

0

0

0

0

0

-5.0

-20.0

0

999

999

999

999

2

5.0

20.0

247

sec.

min.

-

°C

%RH

-

min.

sec.

0

1

1

0

0

0

0

1

0

0

0

0

-9

-20.0

0

0

999

999

999

2

9

20.0

247

999

1

1

0

0

0

0

1

0

sec.

min.

-

°F

%RH

-

min.

sec.

E251415

Ver.02

MT530SP02-01T

-12400

THERM HUMID

M

T-530

Super

AUX

BUZZ