The
is a digital display and configuration interface, compatible with
FG-HMI 4.3
RCK-862
plus
, version 2 or higher. It provides convenient and safe remote access to the settings of the
RCK-862
plus
electronic controller.
Whit the
users can remotely access controller information quickly and easily through
FG-HMI 4.3
the color display and touchscreen interface. The interface is designed to be highly intuitive allowing
the user to access the controller's resources in a complete and simplified way. It also allows the
visualization and configuration of settings and sending commands to the controller.
The
communicates with the electronic controller via an RS-485 connection. The touch
FG-HMI 4.3
display has 4.3 inches, and settings can be adjusted for brightness and economy mode.
8. FIXATION PROCEDURE
7. WIRING DIAGRAM
5. STRUCTURE
DIGITAL DISPLAY AND CONFIGURATION INTERFACE COMPATIBLE WITH
THE
ELECTRONIC CONTROLLER
RCK-862
plus
3. APPLICATIONS
- Graphical interface for
RCK-862
plus
controller.
4. TECHNICAL SPECIFICATIONS
Consumption
Controller operating temperature
Protection degree
Operating humidity
RS-485 communication interface
RS-485 Isolated
Pollution degree
USB Interface
Cutout dimensions (mm)
Product Dimensions (WxHxD)
II
Compatible with USB 2.0 Full-SpeedModule (USBFS)
Standard Data Format for Thumbdrives: FAT32
Maximum Thumbdrive Size: 32GB
138 x 86 mm (5,43" x 3,38")
93,6 x 145,6 x 36,6 mm (3,68" x 5,73" x 1,44")
2. ELECTRICAL PRECAUTIONS
BEFORE INSTALLING THE CONTROLLER, WE RECOMMEND THAT YOU READ THE
ENTIRE INSTRUCTION MANUAL IN ORDER TO AVOID POSSIBLE DAMAGE TO THE
PRODUCT.
CAUTION WHEN INSTALLING THE PRODUCT:
-Before performing any procedure on this instrument, disconnect it from the power supply;
-Ensure that the instrument has proper ventilation, avoiding installing it on panels that contain
other devices that can cause it to operate outside the specified temperature limits;
-Install the product away from sources that may generate electromagnetic disturbances, such
as: motors, contactor, relays, electrovalves etc.
AUTHORIZED SERVICE:
-The installation or maintenance of the product must only be carried out by qualified
professionals.
ACCESSORIES:
-Use only original Full Gauge Controls accessories;
-If in doubt, contact technical support.
AS IT IS CONSTANTLY EVOLVING, FULL GAUGE CONTROLS RESERVES THE RIGHT TO
CHANGE THE INFORMATION CONTAINED IN THE MANUAL AT ANY TIME WITHOUT PRIOR
NOTICE.
32 to 122°F
10 to 90% RH (without condensation)
Have this manual in the palm of your
hand through the FG Finder app.
1. DESCRIPTION
To perform the
installation follow the instructions below:
FG-HMI 4.3
1.
Cut out the panel plate
(1)
where the digital interface will be fixed, with dimensions 138 x 86 mm
(5,43" x 3,38").
2.
Position the
in the panel opening together with the seal
(2)
.
FG-HMI 4.3
3.
Locate the side openings
(3)
for securing the clamps at the rear of the part.
4.
Insert the clamping clips
(4)
into the side openings. Lightly tighten the screws to secure the
interface to the panel.
5.
Cross-tighten the screws
(5)
, according to the sequence indicated, so that the set is securely
fastened to the panel. This tightening must be done manually, the use of tools to tighten the
screws is not indicated.
USB
RS
485
Touch
screen
Economy
mode
Alarm
sound
Alarms
Color
display
colors
3
4
5
5
1
2
138 mm
Cutout dimensions to
fix the instrument
5,43"
86 mm
3,38"
93,6 mm
3,68"
145,6 mm
5,73"
84,7 mm
3,33"
2,5 mm
0,1"
136,7 mm
5,38"
34 mm
1,34"
Type 1 connector:
For Type 1 (5.0mm) connectors use a #1 Phillips screwdriver or 3.0mm
Screwdriver. Do not exceed the maximum torque of 0.5 Nm.
Type 2 connector:
For Type 2 (3.5mm) connectors use #0 Phillips screwdriver or 2.4mm Slit. Do not
exceed the maximum torque of 0.2 Nm.
Cable:
The maximum cable length is 1000 meters. The minimum specification of the cable should be
24AWG braided, in order to protect the communication line from outside interference.
RS-485
Type 2 connector
Type 1 connector
Power input
4 5
Communication
connector
The following components are included in the scope of delivery of
:
FG-HMI 4.3
Ÿ
digital interface;
FG-HMI 4.3
Ÿ
Clamps and fastening screws;
Ÿ
Instruction manual;
Ÿ
Full Gauge adhesive;
Ÿ
Connectors.
6. COMPONENTS
Power
24Vac 50/60Hz ou 24Vdc ± 10%
6 VA
IP65
1
2
3
3
1
3
4
2
Correct clamp mounting position
Serial
communication
Group 1
Suction 1 On
Suction 2 On
Discharge 1 On
93,6 mm
3,68"
145,6 mm
5,73"
84,7 mm
3,33"
2,6 mm
0,1"
136,7 mm
5,38"
36,6 mm
1,44"
18898 - MANUAL
FG-HMI4.3RCK862V01-01T
V
er
.01
FG-HMI 4.3
RCK-862
plus