background image

The 

 is a digital display and configuration interface, compatible with 

  

FG-HMI 4.3

RCK-862

plus

   

,  version  2  or  higher.  It  provides  convenient  and  safe  remote  access  to  the  settings  of  the 

RCK-862

plus

  

 electronic controller.

Whit the 

 users can remotely access controller information quickly and easily through 

FG-HMI 4.3

the color display and touchscreen interface. The interface is designed to be highly intuitive allowing 
the user to access the controller's resources in a complete and simplified way. It also allows the 
visualization and configuration of settings and sending commands to the controller.
The 

 

communicates with the electronic controller via an RS-485 connection. The touch 

FG-HMI 4.3

display has 4.3 inches, and settings can be adjusted for brightness and economy mode.

 8. FIXATION PROCEDURE

7. WIRING DIAGRAM

5. STRUCTURE

DIGITAL DISPLAY AND CONFIGURATION INTERFACE COMPATIBLE WITH 

THE 

 ELECTRONIC CONTROLLER 

RCK-862

 

plus

 3. APPLICATIONS

- Graphical interface for 

RCK-862

 

plus

 controller.

 

 4. TECHNICAL SPECIFICATIONS

Consumption

Controller operating temperature

Protection degree

Operating humidity

RS-485 communication interface

RS-485 Isolated

Pollution degree

USB Interface

Cutout dimensions (mm)

Product Dimensions (WxHxD)

II

Compatible with USB 2.0 Full-SpeedModule (USBFS)

 Standard Data Format for Thumbdrives: FAT32 

 Maximum Thumbdrive Size: 32GB

138 x 86 mm (5,43" x 3,38")

93,6 x 145,6 x 36,6 mm (3,68" x 5,73" x 1,44") 

2. ELECTRICAL PRECAUTIONS

BEFORE INSTALLING THE CONTROLLER, WE RECOMMEND THAT YOU READ THE 
ENTIRE INSTRUCTION MANUAL IN ORDER TO AVOID POSSIBLE DAMAGE TO THE 
PRODUCT.

CAUTION WHEN INSTALLING THE PRODUCT:

-Before performing any procedure on this instrument, disconnect it from the power supply;

-Ensure that the instrument has proper ventilation, avoiding installing it on panels that contain 
other devices that can cause it to operate outside the specified temperature limits;

-Install the product away from sources that may generate electromagnetic disturbances, such 
as: motors, contactor, relays, electrovalves etc.

AUTHORIZED SERVICE:

-The  installation  or  maintenance  of  the  product  must  only  be  carried  out  by  qualified 
professionals.

ACCESSORIES:

-Use only original Full Gauge Controls accessories;
-If in doubt, contact technical support.

AS IT IS CONSTANTLY EVOLVING, FULL GAUGE CONTROLS RESERVES THE RIGHT TO 
CHANGE THE INFORMATION CONTAINED IN THE MANUAL AT ANY TIME WITHOUT PRIOR 
NOTICE.

 32 to 122°F

10 to 90% RH (without condensation)

Have this manual in the palm of your 
hand through the FG Finder app.

1. DESCRIPTION

To perform the 

 installation follow the instructions below:

FG-HMI 4.3

1.

Cut out the panel plate 

(1)

 where the digital interface will be fixed, with dimensions 138 x 86 mm 

(5,43" x 3,38").

2.

Position the 

 in the panel opening together with the seal 

(2)

.

FG-HMI 4.3

3.

Locate the side openings 

(3)

 for securing the clamps at the rear of the part.

4.

Insert the clamping clips 

(4)

 into the side openings. Lightly tighten the screws to secure the 

interface to the panel. 

5.

Cross-tighten the screws 

(5)

, according to the sequence indicated, so that the set is securely 

fastened to the panel. This tightening must be done manually, the use of tools to tighten the 
screws is not indicated.

USB

RS

485

Touch 

screen

Economy

mode

Alarm
sound

Alarms

Color

display

colors

3

4

5

5

1

2

138 mm

Cutout dimensions to

 fix the instrument

5,43"

86 mm

3,38" 

93,6 mm
    3,68"

145,6 mm
     5,73"

 84,7 mm
    3,33"

 2,5 mm
    0,1"

136,7 mm
     5,38"

    34 mm
     1,34"

Type  1  connector: 

For  Type  1  (5.0mm)  connectors  use  a  #1  Phillips  screwdriver  or  3.0mm 

Screwdriver. Do not exceed the maximum torque of 0.5 Nm.

Type 2 connector: 

For Type 2 (3.5mm) connectors use #0 Phillips screwdriver or 2.4mm Slit. Do not 

exceed the maximum torque of 0.2 Nm.

Cable: 

The maximum cable length is 1000 meters. The minimum specification of the cable should be 

24AWG braided, in order to protect the communication line from outside interference.

RS-485

Type 2 connector

Type 1 connector

Power input

 

4    5

Communication

 connector

The following components are included in the scope of delivery of 

:

FG-HMI 4.3

Ÿ

 digital interface;

FG-HMI 4.3

Ÿ

Clamps and fastening screws;

Ÿ

Instruction manual;

Ÿ

Full Gauge adhesive;

Ÿ

Connectors.

6. COMPONENTS

Power

24Vac 50/60Hz ou 24Vdc ± 10%

6 VA

IP65

1

2

3

3

1

3

4

2

Correct clamp mounting position

Serial 

communication

Group 1

Suction 1 On

Suction 2 On

Discharge 1 On

93,6 mm
    3,68"

145,6 mm
     5,73"

 84,7 mm
    3,33"

 2,6 mm
    0,1"

136,7 mm
     5,38"

    36,6 mm
     1,44"

18898 - MANUAL

 FG-HMI4.3RCK862V01-01T

V

er

.01

FG-HMI 4.3 

RCK-862

  

plus

Reviews: