PID TYPE DIGITAL TEMPERATURE 

CONTROLLER

Ver.02

AutoPID

 plus

4.  CONFIGURATION

4.1 - Setpoint adjustment

Press        for 2 seconds until it displays           and then release the key. The operation temperature you 
set is displayed. Use       and       keys to change this value and press        to configure the new value 
when ready.

4.2 - Accessing the function menu

Press      and      keys simultaneously for 2 seconds until it displays         and then release the keys. 
When          is displayed, press        (shortly) and enter the code (123) by using the       and       keys. 
Press        to confirm. You can use       and       keys to access other functions. Use the same procedure 
to adjust other functions.
To exit the menu and return to the normal operation, hold the        key pressed for a while to display          .

4.3 - Advanced functions

SET

SET

SET

SET

SET

4.4 - Function description

Access code (123)

The access code is needed when you want to change the configuration settings. If you just want to view 
the parameters you don't need to input the access code.

Static gain (K)

This gain actuates in the system error (proportional control) and is related to stabilization time and 
control circuit speed. The static gain can be calculated automatically by the autotuning.

Integral time (Ti)

The integrative control is responsible for canceling an error when the system is in a steady condition and 
is also responsible for the system stabilization time. This parameter can be calculated automatically by 
the autotuning.

Derivative time (Td)

This is responsible for stabilizing the system in the setpoint and canceling the overshoot. It can be 
calculated automatically by autotuning, just as the other parameters.

Proportional output anti-saturation system time (Tt)

This  is  responsible  for  preventing  the  proportional  control  output  from  becoming  saturated  due  to 
integral control action (windup). The value recommended for this function is:

The value for this parameter is calculated automatically at the end of autotuning by using Ti and Td 
parameters according to the formula above.

Setpoint influence in the static gain

This is the setpoint gain when calculating the system error. It is used to reduce the effect of an eventual 
noise from the temperature sensor. When you reduce this parameter value, you increase the immunity 
to noise.

Control type

Indicates the process type that the controller will operate. 

Cooling
Heating

Output amplitude for autotuning

Initial amplitude of the signal to be applied in the proportional output during the autotuning stage.
This value is recalculated automatically by the controller during the autotuning and it must be chosen so 
that the system can distinguish the temperature oscillation around the setpoint and the hysteresis.

Temperature hysteresis for autotuning

This hysteresis is used together with the setpoint to control the temperature oscillation in the autotuning.

Steady temperature validation time

This is the time used by the controller to make sure that system temperature is steady and stabilized.

Autotuning starting type

This function defines the mode in which the autotuning must be started.

Only manual start;
Performs autotuning when automatic control is activated;

Performs autotuning if the temperature does not stabilize inside the period of time configured
in F12;
Performs autotuning when automatic control is activated or if the temperature does not
stabilize inside the period of time configured in F12.

Max. time for system stabilization

Maximum time for temperature stabilization before executing autotuning (if configured).

Low temperature alarm

Temperature for activating the low temperature alarm.

Hysteresis for resetting the low temperature alarm

Hysteresis for resetting the low temperature alarm.

High temperature alarm

Temperature for activating the high temperature alarm.

Hysteresis for resetting the high temperature alarm

Hysteresis for resetting the high temperature alarm.

ON-OFF cycle time for alarm output

Cycle time in which the alarm output is turned ON and OFF. If the alarm output is intended to remain 
always ON, this parameter must be set to “0”.

PWM output period

Total time the PWM output remains in the ON and OFF state. The time for each state depends on the 
proportional output value.

Output value in the manual mode

PWM and proportional output value when the controller is in the manual mode.

Output value when a sensor error occurs

PWM and proportional output value when an error occurs in the temperature readings.

Minimum setpoint allowed to the final user

Lower limit to avoid that extremely low temperatures be configured by mistake.

Maximum setpoint allowed to the final user

Upper limit to avoid that extremely high temperatures be configured by mistake.

1. DESCRIPTION

The 

AutoPID

 

plus

 is a digital controller for heating and cooling processes. It uses a PID (proportional, 

integral, and derivative) type controller, which enables to control the temperature with minimal fluctuation.
Product complies with UL Inc. (United States and Canada).

2. APPLICATION

• Freezing and heating chambers
• Refrigeration plants
• Set of compressors etc.

3. TECHNICAL SPECIFICATIONS

- Power Supply: 

90 to 264Vac (50/60 Hz)

- Controlled Temperature: 

-50 to 100°C (with resolution of  0.1°C)

- Indication Accuracy:

0.1°C between -10 and 100°C
and 1°C for the rest of the scale

- Controlling Accuracy: 

0.1°C for the whole scale

- Proportional Outputs:

Voltage output: 0~10Vdc 5mA
PWM: Adjustable period  5mA

- Alarm Output: 

5(3)A 250Vac 1/8HP

- Dimensions: 

71 x 28 x 71mm 

- Operation temperature: 

0 to 50°C

- Operation humidity: 

10 to 90% RH (without condensation)

E251415

Description

Min

Max

Default

Fun

Access code (123)

Static gain

Integral time

Derivative time

Anti-windup time

-99

0.0

0

0

0

999

99.9

999

999

999

0

1.0

12

3

4

Unit

-

-

x 10 sec.

x 10 sec.

x 10 sec.

Setpoint gain in the proportional control 

Control type (0 = cooling, 1 = heating)

Output amplitude for autotuning

Temperature hysteresis for autotuning

Steady temperature validation time

Autotuning starting method

Max. amount of time for stabilizing the temperature before autotuning activation

Low temperature alarm

Hysteresis for resetting the low temperature alarm

High temperature alarm

Hysteresis for resetting the high temperature alarm

ON-OFF cycle time for alarm output

PWM output period

Output value in the manual mode

Output value when error occurs

Minimum setpoint allowed to the final user

Maximum setpoint allowed to the final user

Indication offset

RS-485 network address

0.0

0

10

0.1

1

0

1

-50.0

1.0

-50.0

1.0

0

1

0

0

-50.0

-50.0

-5.0

1

-

-

%

°C

x 10 sec.

-

mim.

°C

°C

°C

°C

sec.

x 10 ms.

%

%

°C

°C

°C

-

1.0

1

100

20.0

999

3

999

100.0

10.0

100.0

10.0

210

999

100

100

100.0

100.0

5.0

247

1.0

0

40

5.0

6

0

999

-50.0

1.0

100.0

1.0

0

1

0

50

-50.0

100.0

0.0

1

AUT

OPID2-08T

-1

1757

MANU

AUTO

TUNE

ALRM