Installation manual UTY-XDZX 

 

This product is intended for controlling Fujitsu General Limited split-type outdoor units for use in conjunction with heat 
exchangers of AHU from other manufacturers. 

Conformity of  regulations and laws must be conformed on the whole system (including outdoor unit) by your side. 

Fujitsu General Limited does NOT take any responsibility on the system design at field or the failure caused by the system 

design at the field including our outdoor unit.

 

Please check our technical manual and this installation manual when designing the local system. 

R32 is flammable refrigerant. Please make sure to read the original IEC 60335 and IEC 60335 2-40 (Edition 6.0). The fire 

safety warranty for the whole system (including outdoor unit) must be done by your side when using R32 refrigerant.  

When using R32 refrigerant please check the following items. 

Requirements for charge limits and ventilation (IEC 60335 2-40 Annex GG) shall be satisfied.

 

Requirements for marking (e.g. flame symbol) and information in the manual shall be satisfied.  
Requirements for constructions (e.g. location of the refrigerant detection sensor) shall be satisfied. 

Please make sure to check technical manual, this installation manual and outdoor unit installation manual for correct use 
and installation. Also, for safety, make sure to read the installation manual for the outdoor unit, especially when using R32 
refrigerant. 

 

  Contents

_

   

 

1. Safety precautions 
2. About this product 

2.1 Precaution for using this product 
2.2 Package Content 
2.3 Field supplied material (This is mandatory.) 

3. Product selection 

3.1 Product lineup 

4. Installation work 

4.1 Selecting an installation location 
4.2 Installing the unit 

5. Installation of temperature sensor 

5.1 Placement of temperature sensor 

 

 

6. Electrical wiring 

6.1 Electrical requirement 
6.2 Connection to outdoor unit 
6.3 Connection of wiring 

6.3.1 External inputs 
6.3.2 External outputs 

6.4 Circuit diagram 

7. LED indicators 
8. Switch operations 
9. Startup and Test Run 
10. Check List (Example) 
11. Error codes 
12. Specification

 

_

1. Safety precautions

_

   

Be sure to read this Manual thoroughly before installation. 

The warnings and precautions indicated in this Manual contain important information pertaining to your safety. Be sure to 

observe them. 

Hand this Manual, to the customer. Request the customer to keep them on hand for future use, such as for relocation or 

repairing the unit. 

For installation of the air handling unit (heat exchanger), refer to the installation manual for the air handling unit. 

WARNING 

This mark indicates procedures which, if improperly performed, might lead to the death or 
serious injury of the user. 

Request your dealer or a professional installer to install this product in accordance with this Installation Manual. An 
improperly installed unit can cause serious accidents such as water leakage, electric shock, or fire. If this product is 

installed in disregard of the instructions in the Installation Manual, it will void the manufacturer’s warranty.

 

Do not turn ON the power until all work has been completed. Turning ON the power before the work is completed can 
cause serious accidents such as electric shock or fire. Do not touch this product after turning ON the power.  
When service, maintenance and cleaning around the unit, make sure to do turn off the power supply. 
If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant comes in contact with a flame, it 
produces a toxic gas. 
Installation work must be performed in accordance with national wiring standards by authorized personnel only. Please do 
not work with wet hands. 

Except for EMERGENCY, never turn off main breaker of this products during operation. It will cause compressor failure as 
well as water leakage. First, stop this product by operating the any control unit. Then cut the breaker. 

Summary of Contents for UTY-XDZX

Page 1: ...nt 6 2 Connection to outdoor unit 6 3 Connection of wiring 6 3 1 External inputs 6 3 2 External outputs 6 4 Circuit diagram 7 LED indicators 8 Switch operations 9 Startup and Test Run 10 Check List Example 11 Error codes 12 Specification _1 Safety precautions_ Be sure to read this Manual thoroughly before installation The warnings and precautions indicated in this Manual contain important informat...

Page 2: ...d installation of the unit _2 About this product_ The module has optional cloud connectivity for remote control and diagnostics For setup of cloud connection go to https ecosmart cloud and follow the instructions there 2 1 Precaution for using this product When operating the unit from other source than IO a new command must be received by the device every 5 min to keep the unit operating If no com...

Page 3: ...leak contains suspended carbon fibers or flammable dust or volatile inflammables such as paint thinner or gasoline If gas leaks and settles around the unit it can cause a fire Area where animals may urinate on the unit or ammonia may be generated Select a place where insects and small animals do not invade Area where insects and small animals do not invade W LAN and Radio Wave Usage CAUTION W LAN ...

Page 4: ...nsulation or exceeding the allowable current can cause electric shock or fire For wiring use the prescribed type of cables connect them securely making sure that there are directly no external forces of the cables applied to the terminal connections Improperly connected or secured cables can cause serious accidents such as overheating the terminals electric shock or fire Always fasten the outside ...

Page 5: ...code Maximum wire length Set a length so that the voltage drop is less than 2 Increase the wire diameter when the wire length is long 6 2 Connection to outdoor unit Use suitable cable as specified for the outdoor unit 3 1 5mm 2 GND is recommended 3 2 5mm 2 GND is maximum Use confirmed cable with type 60245 IEC57 is recommended Make sure to terminate ground properly 6 3 Connection of wiring Use sui...

Page 6: ...f cooling This product and outdoor unit mismatch 1Hz blinking Communication error 5Hz blink This error condition is if this product can t receive the communication protocol over the 120 seconds LED 3 is general system state indication For detailed description of LED3 go to https ecosmart cloud LED 3 Meaning Breathing cyan When it is breathing cyan your device is happily connected to the internet R...

Page 7: ...cosmart cloud If you want to know system status please check 3 LED s Reference Contents 7 CAUTION If it makes mistake to choose the outdoor unit and refrigerant type it causes the damage and trouble for the outdoor unit Please make sure to check the connecting outdoor unit model and choose the proper outdoor unit type on website Operation environment Personal computer environment Items Contents CP...

Page 8: ...Error codes_ When an error appears please check on LED or web browser https ecosmart cloud And please check the error code then please check the installation manual or technical manual or service manual of installed outdoor unit _12 Specifications Items Value Input voltage 230V 50Hz Power consumption Max 2 0W Current value Less than 0 01A Dry bulb temperature of installed environmental 20 46 degre...