Main memory
9.2.3
Identifying a fault on the CPUMEMR
CPUMEMRs provide PRIMERGY Diagnostics indicators to indicate faulty
CPUMEMRs, CPUs, or DIMM memory modules see
figure 111
.
Figure 111: Indicators on the CPUMEMR
Ê
Press the CSS button that is located on the PCI Riser to identify a faulty
CPUMEMR or a faulty unit on the CPUMEMR, see
"Locate the faulty
component by PRIMERGY diagnostics indicators" on page 39
.
Ê
Take a note on the faulty component indicated by the indicator:
–
Number of the CPUMEMR
–
Faulty component
–
For DIMM memory modules: Identifier of the slot
1
CSS indicator for the CPUMEMR
(orange)
3
8x CSS indicators for each DIMM
memory module pair (orange)
2
CSS indicator for the CPU
(orange)
/
0
1