Executing the fan test via ServerView Operations Manager
▶
Open the ServerView Operations Manager and log in.
▶
Under
Administration
select
Server Configuration
.
▶
In the hierarchy tree of the
Server list
tab, select the server to be
configured.
▶
In the right-hand side of the window, specify the details on the selected
server and confirm your entries by clicking
GO...
.
In the left-hand section of the window, the
Configuration
tab is being
activated.
▶
In the navigation area of the
Configuration
tab, select
Other Settings
.
▶
Under
Daily Fan Test
, set the daily fan test time to a few minutes from the
current time. (Ensure to note down your previous setting.)
▶
Click
Save Page
.
The fan test will be started at the specified time.
▶
After the fan test is complete, restore the time setting to its initial value and
click
Save Page
.
In case of maintenance done by Fujitsu engineers in Japan:
Executing the fan test via Chassis ID Prom Tool
Please follow the instructions provided separately.
5.3.20 Updating the golden image
5.3.20.1
Updating the golden image for iRMC S5 firmware
The golden image is part of the PFR (Platform Firmware Resiliency)
feature.
The PFR feature provides protection of firmware, detection of tampered
firmware and automatic recovery of firmware.
Basic software procedures
RX4770 M6
Upgrade and Maintenance Manual
115
Summary of Contents for PRIMERGY RX4770 M6
Page 80: ...Basic hardware procedures 80 Upgrade and Maintenance Manual RX4770 M6 ...
Page 166: ...Hard disk drive HDD solid state disk SSD 166 Upgrade and Maintenance Manual RX4770 M6 ...
Page 298: ...Liquid cooling LC 298 Upgrade and Maintenance Manual RX4770 M6 ...
Page 314: ...Accessible drives 314 Upgrade and Maintenance Manual RX4770 M6 ...