7.5.7
Replacing a 2.5-inch PCIe SSD module
Customer Replaceable
Unit (CRU)
Hardware: 5 minutes
Tools:
– Installation frame included: tool-less
– Installation frame excluded: Phillips PH1 / (+) No. 1 screw driver
This procedure is valid, if the PCIe SSD module is controlled by an
onboard controller and the VMD function is enabled in the BIOS. For
more information, see the "Intel Virtual RAID on CPU (Intel VROC) User
Guide".
If the PCIe SSD module is controlled by a RAID controller of the PRAID
EP5xxi/CP5xxi/EP6xxi family, the PCIe SSD module can be installed
during operation (hot-plug), see
.
CAUTION
All HDD/SSD modules (drives) must be uniquely identified so that they
can be reinstalled in their original bays later. If this is not done, existing
data can be lost.
Preliminary steps
▶
"Locating the defective server" on page 49
.
▶
If applicable,
"Removing the front cover with lock" on page 52
▶
Identify the physical location of the PCIe SSD module, see
▶
Prepare the removing of the PCIe SSD module.
▶
Depending on your configuration and OS:
.
Hard disk drive (HDD) / solid state disk (SSD)
178
Upgrade and Maintenance Manual
RX2540 M6
Summary of Contents for PRIMERGY RX2540 M6
Page 8: ...Upgrade and Maintenance Manual RX2540 M6 ...
Page 34: ...Before you start 34 Upgrade and Maintenance Manual RX2540 M6 ...
Page 86: ...Basic hardware procedures 86 Upgrade and Maintenance Manual RX2540 M6 ...
Page 120: ...Basic software procedures 120 Upgrade and Maintenance Manual RX2540 M6 ...
Page 232: ...Fans 232 Upgrade and Maintenance Manual RX2540 M6 ...
Page 328: ...Expansion cards and backup units 328 Upgrade and Maintenance Manual RX2540 M6 ...
Page 366: ...Processor CPU 366 Upgrade and Maintenance Manual RX2540 M6 ...
Page 462: ...Front panel 462 Upgrade and Maintenance Manual RX2540 M6 ...
Page 570: ...Appendix A 570 Upgrade and Maintenance Manual RX2540 M6 ...
Page 672: ...List of all used screws for PRIMERGY Servers Assembled in WCZ and FIT June 2021 ...