56
Upgrade and Maintenance Manual
RX2520
M4
Basic hardware procedures
4.5.2
Installing the server in the rack
V
CAUTION!
At least two people are needed to position the server on the rack rails.
(For Japan, please refer to "
安全上のご注意
".)
Additionally, a lifter is required in the following cases:
– The server weighs more than 50 kg.
– The server weighs more than 21 kg and is to be installed above the
height of 25 U.
When using a lifter, this installation procedure needs to be carried out by
maintenance personnel.
For configurations below 32 kg:
At least two people are needed to lift the server
into the rack cabinet.
For configurations below 55 kg:
At least three people are needed to lift the server
into the rack cabinet.
For configurations above 55 kg:
At least four people are needed to lift the server
into the rack cabinet.
Summary of Contents for PRIMERGY RX2520 M4
Page 6: ...6 Upgrade and Maintenance Manual RX2520 M4 ...
Page 22: ...Upgrade and Maintenance Manual RX2520 M4 Content ...
Page 98: ...98 Upgrade and Maintenance Manual RX2520 M4 Basic software procedures ...
Page 118: ...118 Upgrade and Maintenance Manual RX2520 M4 Power supply unit PSU ...
Page 194: ...194 Upgrade and Maintenance Manual RX2520 M4 Fans ...
Page 232: ...232 Upgrade and Maintenance Manual RX2520 M4 Expansion cards and backup units ...
Page 310: ...310 Upgrade and Maintenance Manual RX2520 M4 Accessible drives ...
Page 338: ...338 Upgrade and Maintenance Manual RX2520 M4 Front panel ...
Page 410: ...410 Upgrade and Maintenance Manual RX2520 M4 Appendix A ...
Page 412: ...412 Upgrade and Maintenance Manual RX2520 M4 Appendix B ...
Page 451: ...List of all used screws for PRIMERGY Servers Assembled in Germany and Japan January 2017 ...