Preliminary steps
▶
"Shutting down the server" on page 37
▶
"Disconnecting the power cord (AC PSU)" on page 38
.
▶
"Getting access to the component" on page 39
▶
Remove the riser module 1, see
"Removing the riser module 1" on page 51
.
Installing the RAID controller in riser module 1
Figure 67: Removing the slot cover
▶
Remove the screw (see circle) and remove the slot cover.
CAUTION
▶
Keep the slot cover for future use.
▶
If the expansion card is removed and not replaced with a new
one, the slot cover must be reinstalled due to cooling, to comply
with applicable EMC regulations and to protect against fire.
Expansion cards and riser cards
106
Upgrade and Maintenance Manual
RX2450 M1