FUNCTION DETAILS
Functions
Compact wall
mounted
1)
Filter sign
z
2)
Cooler room temperature correction
z
3)
Heater room temperature correction
z
4)
Auto restart
z
5)
Indoor room temperature sensor
switching function
z
6)
Remote controller signal code
z
7)
External input control
z
1) Filter sign
The indoor unit has a sign to inform the user that it is time to clean the filter. Select the time
setting for the filter sign display interval in the table below according to the amount of dust or
debris in the room. If you do not wish the filter sign to be displayed, select the setting value for
"No indication".
(
... Factory setting)
Setting description
Function number
Setting value
Standard
11
00
Long interval
01
Short interval
02
No indication
03
The filter sign interval time is different according to Indoor unit type as follows.
Setting description
Compact Wall
Mounted
Standard
400 hours
Long interval
1000 hours
Short interval
200 hours
2) Cooler room temperature correction
Depending on the installed environment, the room temperature sensor may require correction.
The settings may be selected as shown in the table below.
(
... Factory setting)
Setting description
Function number
Setting value
Standard
30
00
Slightly lower control
01
Lower control
02
Warmer control
03
3) Heater room temperature correction
Depending on the installed environment, the room temperature sensor may require correction.
The settings may be changed as shown in the table below.
(
... Factory setting)
Setting description
Function number
Setting value
Standard
31
00
Lower control
01
Slightly warmer control
02
Warmer control
03