2. Specifications
Type
Duct
Inverter heat pump
Model name
ARHG72LHTA
ARHG90LHTA
Power supply
230 V ~ 50 Hz
Available voltage range
198—264 V
Capacity
Cooling
Rated
kW
19.0
22.0
Btu/h
64,800
75,000
Min.—Max.
kW
8.40 —20.90
10.30—24.20
Btu/h
28,600 —71,300
35,100 —82,500
Heating
Rated
kW
22.4
27.0
Btu/h
76,400
92,100
Min.—Max.
kW
7.20—24.60
8.50—29.70
Btu/h
24,500 —83,900
29,000—101,300
Input power
Cooling
Rated
kW
0.47
0.53
Heating
0.47
0.53
Fan
HIGH
W
580
640
MED
450
470
LOW
320
350
QUIET
210
250
Current
Cooling
Rated
A
3.2
3.5
Heating
3.2
3.5
Power factor
Cooling
%
63.9
65.8
Heating
63.9
65.8
EER
Cooling
kW/kW
2.94
2.83
COP
Heating
3.40
3.30
Moisture removal
L/h (pints/h)
4.5 (7.92)
6.0 (10.56)
Maximum operating current *1
Cooling
A
4.6
6.0
Heating
4.6
6.0
Fan
Airflow rate
Cooling
HIGH
m
3
/h
4,300
4,300
MED
3,900
3,900
LOW
3,450
3,450
QUIET
3,000
3,000
Heating
HIGH
4,300
4,300
MED
3,900
3,900
LOW
3,450
3,450
QUIET
3,000
3,000
Type × Q'ty
Sirocco fan × 2
Motor output
W
750
1,070
Static pressure range
Pa
50 to 150 (Standard: 72)
50 to 200 (Standard: 72)
Sound pressure level *2
Cooling
HIGH
dB (A)
46
47
MED
43
44
LOW
41
42
QUIET
39
40
Heating
HIGH
46
47
MED
43
44
LOW
41
42
QUIET
39
40
Sound power level
Cooling
dB (A)
79
79
Heating
80
80
Heat exchanger type
Dimensions (H × W × D)
mm
546 × 1,158 × 39.9
Main: 546 × 1,158 × 39.9
Sub: (252 × 1,158 × 13.3) × 2
Fin pitch
1.3
Main: 1.3
Sub: 1.45
Rows × Stages
3 × 26
Main: 3 × 26
Sub: (1 × 12) × 2
Pipe type
Copper
Fin type
Aluminium
Enclosure
Material
Steel
Color
―
Dimensions
(H × W × D)
Net
mm
360 × 1,400 × 850
Gross
460 × 1,640 × 1,030
Weight
Net
kg
69
80
Gross
80
91
Connection pipe
Size
Liquid
mm (in)
Ø 12.70 (Ø 1/2)
Gas
Ø 25.40 (Ø 1)
Method
Brazing
Drain hose
Material
PVC
Size
mm
Ø 24.4 (I.D.), Ø 32 (O.D.) (VP25)
Operation range
Cooling
°C
18 to 32
%RH
80 or less
Heating
°C
16 to 30
Remote controller type
Wired
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 7.5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.).
• Protective function might work when using it outside the operation range.
• *1: Maximum current:
– The maximum value when operated within the operation range.
– The total current of indoor unit and outdoor unit.
• *2: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
- 3 -
DUCT TYPE
ARHG72-90LHTA
Summary of Contents for GENERAL ARHG72LHTA
Page 5: ...Part 1 INDOOR UNIT DUCT TYPE ARHG72LHTA ARHG90LHTA ...
Page 12: ...4 2 Model ARHG90LHTA I O PCB WLAN adapter Converter etc 8 DUCT TYPE ARHG72 90LHTA ...
Page 57: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOHG72LRLA AOHG90LRLA ...
Page 64: ...5 Wiring diagrams 5 1 Models AOHG72LRLA and AOHG90LRLA 60 OUTDOOR UNIT AOHG72 90LRLA ...