1-3. Error code table (Indoor unit and wired remote controller)
The operation, timer, and economy indicators operate according to the error contents.
For confirmation of the error contents, refer the flashing pattern as follows.
Error contents
Indoor unit display
Wired
remote
controller
display
Operation [ ]
(Green)
Timer [ ]
(Orange)
Economy [ ]
(Green)
E: 11. Serial communication error (Serial
reverse transfer error) (Outdoor unit)
1 times
1 times
Continuous
11
E: 11. Serial communication error (Serial
forward transfer error) (Indoor unit)
1 times
1 times
Continuous
11
E: 12. Wired remote controller
communication error (Indoor unit)
1 times
2 times
Continuous
12
E: 22. Indoor unit capacity error (Indoor
unit)
2 times
2 times
Continuous
22
E: 32. Indoor unit main PCB error (Indoor
unit)
3 times
2 times
Continuous
32
E: 35. MANUAL AUTO button error (Indoor
unit)
3 times
5 times
Continuous
35
E: 41. Room temperature sensor error
(Indoor unit)
4 times
1 times
Continuous
41
E: 42. Indoor unit heat exchanger sensor
error (Indoor unit)
4 times
2 times
Continuous
42
E: 51. Indoor unit fan motor error (Indoor
unit)
5 times
1 times
Continuous
51
E: 62. Outdoor unit main PCB error
(Outdoor unit)
6 times
2 times
Continuous
62
E: 63. Inverter error (Outdoor unit)
6 times
3 times
Continuous
63
E: 64. PFC circuit error (Outdoor unit)
6 times
4 times
Continuous
64
E: 65. Trip terminal L error (Outdoor unit)
6 times
5 times
Continuous
65
E: 71. Discharge thermistor error (Outdoor
unit)
7 times
1 times
Continuous
71
E: 73. Heat exchanger (Middle/Outlet)
temperature thermistor error (Outdoor unit)
7 times
3 times
Continuous
73
E: 74. Outdoor temperature thermistor error
(Outdoor unit)
7 times
4 times
Continuous
74
E: 77. Heat sink thermistor error (Outdoor
unit)
7 times
7 times
Continuous
77
E: 84. Current sensor error (Outdoor unit)
8 times
4 times
Continuous
84
E: 86. High pressure switch error (Outdoor
unit)
8 times
6 times
Continuous
86
E: 94. Trip detection (Outdoor unit)
9 times
4 times
Continuous
94
E: 95. Compressor motor control error
(Outdoor unit)
9 times
5 times
Continuous
95
E: 97. Outdoor unit fan motor error
(Outdoor unit)
9 times
7 times
Continuous
97
E: 99. 4-way valve error (Outdoor unit)
9 times
9 times
Continuous
99
E: A1. Discharge temperature error
(Outdoor unit)
10 times
1 times
Continuous
A1
E: AC. Heat sink temperature error
(Outdoor unit)
10 times
12 times
Continuous
AC
1-3. Error code table (Indoor unit and wired remote controller)
- (03-2) -
1. Error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for General AOHH30KMTB
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 07 19 SR_CH01_AS073EG_02 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 07 19 SR_CH02_AS073EG_01 ...
Page 33: ...3 TROUBLESHOOTING 2022 08 22 SR_CH03_AS073EG_01 ...
Page 36: ......
Page 90: ...5 2 Outdoor unit 03 54 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 91: ...4 CONTROL AND FUNCTIONS 2022 08 22 SR_CH04_AS073EG_01 ...
Page 94: ......
Page 129: ...5 FILED WORKING 2022 08 22 SR_CH05_AS073EG_01 ...