![Fujitsu General AOHH30KMTB Service Manual Download Page 143](http://html.mh-extra.com/html/fujitsu/general-aohh30kmtb/general-aohh30kmtb_service-manual_2343870143.webp)
3-1. External input
With using external input function, some functions on this product can be controlled from an external
device.
• “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit.
• A twisted pair cable should be used. Maximum length of cable is 150 m.
• Use an external input and output cable with appropriate external dimension, depending on the
number of cables to be installed.
• The wire connection should be separate from the power cable line.
¢
Indoor unit
Indoor unit functions such as Operation/Stop can be done by using indoor unit connectors.
1
2
3
CN46
PCB
Connected device
*1: The switch can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
3-1. External input
- (05-13) -