8-7. High temperature and high pressure release control
The compressor is controlled as follows.
•
Cooling mode
Indoor unit heat exchanger
temperature rises
Indoor unit heat exchanger
temperature drops
Stable zone
AB
BC
CD
Zone A
Zone B
Zone C
Zone D
AB:
64 °C
BC:
60 °C
CD:
58 °C
Zone
Operation
Zone A
Compressor is stopped.
Zone B
The compressor frequency is decreased.
-7 rps/120 sec.
Zone C
The protection is released and the operation is returned to normal mode.
Zone D
•
Heating mode
Indoor unit heat exchanger
temperature rises
Indoor unit heat exchanger
temperature drops
Stable zone
AB
BC
CD
DE
Zone A
Zone B
Zone C
Zone D
Zone E
AB:
63°C
BC:
55°C
CD:
53°C
DE:
50°C
Zone
Operation
Zone A
Compressor is stopped.
Zone B
The compressor frequency is decreased.
-15 rps/120 sec.
Zone C
-2 rps/120 sec.
Zone D
The protection is released and the operation is returned to normal mode.
Zone E
8-7. High temperature and high pressure release control
- (04-33) -
8. Various protections
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for General AOHH30KMTB
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 07 19 SR_CH01_AS073EG_02 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 07 19 SR_CH02_AS073EG_01 ...
Page 33: ...3 TROUBLESHOOTING 2022 08 22 SR_CH03_AS073EG_01 ...
Page 36: ......
Page 90: ...5 2 Outdoor unit 03 54 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 91: ...4 CONTROL AND FUNCTIONS 2022 08 22 SR_CH04_AS073EG_01 ...
Page 94: ......
Page 129: ...5 FILED WORKING 2022 08 22 SR_CH05_AS073EG_01 ...