6-13. Unit status monitoring and the detected value indication
The wired remote controller can monitor the indoor and outdoor units' status and display the detect-
ed result as a relevant ID.
For details of the display method, refer to the Chapter of “Display Sensor Values” in the
Installation
Manual
of Wired remote controller (Touch panel).
The status can be monitored and displayed on the wired remote controller by assigning an arbitrary
ID. For available ID list, refer to the table below.
NOTE:
Operating time for each part cannot be reset when the part is replaced. Take notes of the
operating time before replacing to count the operating time of the replaced part.
Available Sensor ID
Sensor ID
Item
Unit
Remarks
00: Indoor unit
00
000
Suction temp.
01: °C or °F
00
001
Room temp.
01: °C or °F
When the wired remote controller
thermistor is enabled, temperature of
the wired remote controller thermistor
is displayed.
00
002
Wired remote controller detected
temp.
01: °C or °F
00
003
Wireless remote controller detected
temp.
01: °C or °F
Temperature detected by wireless
remote controller
00
004
Discharge air temp.
01: °C or °F
00
005
Heat exchanger inlet temp.
01: °C or °F
00
006
Heat exchanger middle temp.
01: °C or °F
00
007
Heat exchanger outlet temp.
01: °C or °F
00
020
Fan rotation number
03: rpm
00
021
Fan 2 rotation number
03: rpm
00
022
Fan 3 rotation number
03: rpm
00
030
Expansion valve
05: pls
00
040
Operating pulse for right filter
05: pls
00
041
Operating pulse for left filter
05: pls
00
042
Operating pulse for filter brush
05: pls
00
050
Power relay for outdoor unit On/Off
08: On/Off
0: Off, 1: On
00
051
Float switch On/Off
08: On/Off
0: Off, 1: On (When the water level
rises)
00
052
Drain pump On/Off
08: On/Off
0: Off, 1: On
00
053
Solenoid valve for reheat operation
On/Off
08: On/Off
0: Off (Opened), 1: On (Closed)
00
054
Air cleaner status On/Off
08: On/Off
0: Off, 1: On
00
055
Limit switch 1 (For grille) On/Off
08: On/Off
0: Off, 1: On
00
056
Limit switch 2 (For right filter) On/Off
08: On/Off
0: Off, 1: On
00
057
Limit switch 3 (For left filter) On/Off
08: On/Off
0: Off, 1: On
00
070
Current sensor
09: A
00
080
Indoor unit total energized hours
11: h
00
081
Total filtering hours
11: h
00
082
Indoor unit fan total operation hours
11: h
00
083
Indoor unit fan 2 total operation hours
11: h
00
084
Indoor unit fan 3 total operation hours
11: h
00
090
Temperature sensor
12: %
00
095
Presence or absence detected by
human sensor
00: —
0: Absence, 1: Presence
—: Human sensor error or No human
sensor
6-13. Unit status monitoring and the detected value indication
- (04-24) -
6. Various control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for General AOHG45KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 01 24 SR_CH01_AR040EG_01 ...
Page 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 04 07 SR_CH02_AR040EG_02 ...
Page 33: ...3 TROUBLESHOOTING 2022 04 07 SR_CH03_AR040EG_02 ...
Page 36: ......
Page 93: ...4 CONTROL AND FUNCTIONS 2022 02 04 SR_CH04_AR040EG_01 ...
Page 127: ...5 FILED WORKING 2022 04 07 SR_CH05_AR040EG_02 ...