![Fujitsu GENERAL AOHG18KMTA Service Manual Download Page 57](http://html.mh-extra.com/html/fujitsu/general-aohg18kmta/general-aohg18kmta_service-manual_2343866057.webp)
2-8. E: 29. Connected unit number error (Indoor unit)
Indicator
Indoor unit
Operation indicator
2 time flash
Timer indicator
9 time flash
Economy indicator
Continuous flash
Error code
E: 29
Detective actuator →ired remote controller (2-wire)
→hen the number of the connected indoor unit exceeds
the limitation.
Indoor unit main PCB
Forecast of cause
→rong wiring of indoor unit or remote controller
Number of indoor unit or remote controller in remote
controller group
Indoor unit main PCB failure
Check point 1. →ire installation
•
→rong number of connected indoor unit
-> If there is an abnormal condition, correct it by refer to the installation manual or the “DESIGN
& TECHNICAL MANUAL”.
Check point 2. Check indoor unit main PCB
•
Check if main PCB is damaged.
•
Change main PCB and check the error after setting remote controller address.
End
2-8. E: 29. Connected unit number error (Indoor unit)
- (03-13) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Summary of Contents for GENERAL AOHG18KMTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 03 11 SR_CH01_AS070EG_01 ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2022 03 11 SR_CH02_AS070EG_02 ...
Page 41: ...3 TROUBLESHOOTING 2022 03 25 SR_CH03_AS070EG_01 ...
Page 44: ......
Page 103: ...4 CONTROL AND FUNCTIONS 2022 03 25 SR_CH04_AS070EG_01 ...
Page 105: ...8 8 High temperature and high pressure release control heating mode 04 29 CONTENTS continued ...
Page 106: ......
Page 137: ...5 FILED WORKING 2022 03 25 SR_CH05_AS070EG_01 ...