2-4. E: 18. External communication error (Indoor unit)
Indicator
Indoor unit
Operation indicator
1 time flash
Timer indicator
8 time flash
Economy indicator
Continuous flash
Error code
E: 18
Detective actuator Indoor unit
External
communication
error
After receiving a signal from the external input and
output PCB, the same signal has not been received for
15 seconds.
Forecast of cause
Connection failure
→LAN adapter failure
Main PCB
Check point 1. Check the connection
•
Check any loose or removed connection between the main PCB to the →AN adapter.
-> If there is an abnormal condition, correct it by refer to the installation manual or the “DESIGN
& TECHNICAL MANUAL”.
•
Check the connection condition on the →LAN adapter and the main PCB (If there is loose con-
nector, open cable or mis-wiring.)
Check point 2. Replace the →LAN adapter
If check point 1 do not improve the symptom, change →LAN adapter.
Check point 3. Replace main PCB
If check point 2 do not improve the symptom, change main PCB
End
2-4. E: 18. External communication error (Indoor unit)
- (03-9) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Summary of Contents for GENERAL AOHG18KMTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 03 11 SR_CH01_AS070EG_01 ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2022 03 11 SR_CH02_AS070EG_02 ...
Page 41: ...3 TROUBLESHOOTING 2022 03 25 SR_CH03_AS070EG_01 ...
Page 44: ......
Page 103: ...4 CONTROL AND FUNCTIONS 2022 03 25 SR_CH04_AS070EG_01 ...
Page 105: ...8 8 High temperature and high pressure release control heating mode 04 29 CONTENTS continued ...
Page 106: ......
Page 137: ...5 FILED WORKING 2022 03 25 SR_CH05_AS070EG_01 ...