2-3. Setting of external input and output
•
Indoor unit
Input
Connection point
Function setting number 46
Function
CN46
00
Operation/Stop mode 1 (R.C. enabled)
01
(Setting prohibited)
02
Forced stop mode
03
Operation/Stop mode 2 (R.C. disabled)
Output
Connection point
Function setting number 60
Function
CN47
00
Operation status
01 to 08
(Setting prohibited)
09
Error status
10
Indoor unit fan operation status
11
(Setting prohibited)
•
External input and output PCB
Switch setting
Input
Output
Rotary
switch
SW302
CN313
CN314
CN310
CN311
CN312
1
Edge
Operation/Stop Not available
Operation
status
Error status
Indoor unit fan
status
Pulse
Operation
Stop
2
Edge*
Forced
thermostat off
Not available
Error status
Indoor unit fan
operation
status
Not available
3 to 9, A
(Setting prohibited)
B
Forced
thermostat off
Not available
Operation
status
Indoor unit fan
operation
status
Not available
C
Forced
thermostat off
Not available
Operation
status
Error status
Not available
D
(Setting prohibited)
NOTES:
• →hen the rotary switch is selected to “1”, the operation of the connector input of the indoor
unit and the External input and output PCB input are the same. The operation content de-
pends on the setting of function setting number 46.
• *: The external input other than “Operation/Stop” is available only when the S→302 is set to
“Edge”.
2-3. Setting of external input and output
- (05-14) -
2. External input and output
FI
EL
D
W
O
R
K
IN
G
FI
EL
D
W
O
R
K
IN
G
Summary of Contents for GENERAL AOHG18KMTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 03 11 SR_CH01_AS070EG_01 ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2022 03 11 SR_CH02_AS070EG_02 ...
Page 41: ...3 TROUBLESHOOTING 2022 03 25 SR_CH03_AS070EG_01 ...
Page 44: ......
Page 103: ...4 CONTROL AND FUNCTIONS 2022 03 25 SR_CH04_AS070EG_01 ...
Page 105: ...8 8 High temperature and high pressure release control heating mode 04 29 CONTENTS continued ...
Page 106: ......
Page 137: ...5 FILED WORKING 2022 03 25 SR_CH05_AS070EG_01 ...