CHAPTER 3
Small Configuration
Installing Power, Ground, and Alarm Cables
3-85
FLASHWAVE 7500 Release 6.1
Equipment Installation
Fujitsu and Fujitsu Customer Use Only
FNC-7500-0061-200
Issue 1, May 2009
Table 3-8: Power,
G
round, and Alarm Cable Connections
(Small Configuration)
Part Number
Use
Description
Term Type
Wire
G
auge
HA15B-0001-C413
–48 V DC and
ground
5-wire rack/shelf power harness,
one set per shelf
10 AWG crimp
lugs
10 AWG
HA660-1106-T003
Rack alarms
6-connector daisy-chained alarm
harness, one connector per shelf
(CNA through CNF), one harness
per rack
D-sub 25-pin,
terminates with
wire-wrap at CBP
24 AWG
HA660-1102-T015
Shelf alarms
Alarm cable from rack alarm cable
connector to shelf backplane alarm
connector, one per shelf
D-sub 25-pin,
CN1 at rack
alarm end, CN2
at shelf alarm end
24 AWG
PC15L-0001-C045
Frame ground
Frame ground stranded wire cable
from rack to CBP, one per rack
Terminal lugs,
both ends,
installed
6 AWG, stranded
Revision 1, June 2009