Site Planning Guide
45
2. Rack Installation Specifications
This chapter provides the installation specification of the ETERNUS AX/HX.
Rack Installation Requirements
This section explains the requirements for installing the ETERNUS AX/HX in a 19-inch rack.
Placement in the Rack
Note the following when installing the ETERNUS AX/HX in the rack.
•
Secure a space of 1U at the bottom of a rack.
•
The space from 2U to 7U is dedicated to PDUs. Since the height of a PDU is 2U, a maximum of three PDUs can
be installed.
•
Install the controller shelf in 8U.
•
Drive shelves must be installed in a higher position than the controller shelf.
•
If size of the drive shelves is mixture of 2U and 4U, the 4U shelves must be installed below the 2U shelves.
•
The center of gravity must be taken into consideration to prevent a rack from toppling over. Shelves should
generally be installed from bottom to top to lower the center of gravity and to ensure the safe use of racks.
•
Shelves are installed in the following order (from bottom to top).
Table 26 Shelf Installation Order
*1: Uninterruptible Power Supply.
•
When an AX4100 or HX6100 is ordered together with a rack, drive shelves are installed according to the fol-
lowing priority.
Table 27 Priority of the Drive Shelf Types Connected to the AX4100
Installation order
Shelf
Size (height)
6
DS214C drive shelf
2U
DS224C drive shelf
2U
NS224 drive shelf
2U
5
DS460C drive shelf
4U
4
Controller shelf
2U
3
Controller shelf
4U
2
Power distribution unit
2U
1
UPS (*1)
-
Priority
Drive shelf
1
Drive shelf included in the controller shelf
2
A drive shelf that is different from the one included in the controller shelf
Summary of Contents for ETERNUS AX Series