6-2. Model: AOYG22KATA
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5
7.5
10
15
20
25
Height difference H (m)
Indoor unit is higher than
outdoor unit *
1
20
—
—
—
—
0.932
0.930
15
—
—
—
0.953
0.950
0.947
10
—
—
0.983
0.968
0.966
0.962
7.5
—
0.988
0.987
0.972
0.970
0.966
5
0.992
0.992
0.991
0.976
0.974
0.970
0
1.000
1.000
0.999
0.984
0.982
0.978
Indoor unit is lower than
outdoor unit *
2
-5
1.000
1.000
0.999
0.984
0.982
0.978
-7.5
—
1.000
0.999
0.984
0.982
0.978
-10
—
—
0.999
0.984
0.982
0.978
-15
—
—
—
0.984
0.982
0.978
-20
—
—
—
—
0.982
0.978
HEATING
Pipe length (m)
5
7.5
10
15
20
25
Height difference H (m)
Indoor unit is higher than
outdoor unit *
1
20
—
—
—
—
0.894
0.867
15
—
—
—
0.920
0.894
0.867
10
—
—
0.982
0.920
0.894
0.867
7.5
—
1.000
0.982
0.920
0.894
0.867
5
1.000
1.000
0.982
0.920
0.894
0.867
0
1.000
1.000
0.982
0.920
0.894
0.867
Indoor unit is lower than
outdoor unit *
2
-5
0.995
0.995
0.977
0.916
0.889
0.862
-7.5
—
0.993
0.975
0.913
0.887
0.860
-10
—
—
0.972
0.911
0.885
0.858
-15
—
—
—
0.902
0.876
0.849
-20
—
—
—
—
0.863
0.834
- 57 -
6-2. Model: AOYG22KATA
6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOYG18, 22KATA
OUTDOOR UNIT
AOYG18, 22KATA