2-6. Ceiling type
Model name
ABYG30LRTE
ABYG36LRTE
ABYG45LRTA
Power supply
1Ø 230 V ~50 Hz
Available voltage range
198—264 V
Fan
Airflow rate
Cooling
HIGH
m
3
/h
1,660
1,900
2,100
MED
1,500
1,500
1,700
LOW
1,200
1,200
1,400
QUIET
1,000
1,000
1,100
Heating
HIGH
1,660
1,900
2,100
MED
1,500
1,500
1,700
LOW
1,200
1,200
1,400
QUIET
1,000
1,000
1,100
Type × Q'ty
Sirocco fan × 4
Motor output
W
120
Sound pressure level *
Cooling
HIGH
dB (A)
45
47
49
MED
43
43
45
LOW
37
37
39
QUIET
32
32
34
Heating
HIGH
45
47
49
MED
43
43
45
LOW
37
37
39
QUIET
32
32
34
Heat exchanger type
Dimensions (H × W × D)
mm
252 × 1,350 × 39.9
Fin pitch
mm
1.45
Rows × Stages
3 × 12
Pipe type
Copper tube
Fin type
Aluminum
Enclosure
Material
ABS
Color
White
(Approximate color of Munsell N 9.25/)
Dimensions
(H × W × D)
Net
mm
240 × 1,660 × 700
Gross
318 × 1,800 × 790
318 × 1,800 × 795
Weight
Net
kg
46
Gross
58
Connection
pipe
Size
Liquid
mm (in)
Ø9.52 (Ø3/8)
Gas
Ø15.88 (Ø5/8)
Method
Flare
Drain hose
Material
ABS
Size
mm
Ø22.0 (I.D.), Ø25.6 (O.D.)
Ø21.5 (I.D.), Ø26.0 (O.D.)
Operation range
Cooling
°C
18 to 32
%RH
80 or less
Heating
°C
16 to 30
Remote controller type
Wireless
NOTES:
• The protective function might work when using it outside the operation range.
• *Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
- 9 -
2-6. Ceiling type
2. Specifications
INDOOR UNITS
SIMULTANEOUS
MULTI
INDOOR UNITS
SIMULTANEOUS
MULTI
Summary of Contents for AUYG18LVLB
Page 151: ...Part 2 OUTDOOR UNIT SIMULTANEOUS MULTI AOYG72LRLA AOYG90LRLA ...
Page 181: ...Part 3 SYSTEM DESIGN ...
Page 333: ...Part 4 OPTIONAL PARTS ...