5-2. Outdoor unit
¢
Heatsink thermistor
Temperature (°C)
Resistance (kΩ)
Voltage (V)
-30.0
94.26
0.08
-25.0
67.95
0.11
-20.0
49.62
0.15
-15.0
36.68
0.20
-10.0
27.42
0.26
-5.0
20.73
0.34
0.0
15.83
0.43
5.0
12.21
0.55
10.0
9.50
0.68
15.0
7.46
0.84
20.0
5.90
1.01
25.0
4.71
1.21
30.0
3.78
1.42
35.0
3.06
1.64
40.0
2.50
1.88
45.0
2.05
2.11
50.0
1.69
2.35
55.0
1.40
2.58
60.0
1.17
2.81
65.0
0.98
3.02
70.0
0.83
3.22
75.0
0.70
3.41
80.0
0.60
3.58
85.0
0.51
3.73
90.0
0.44
3.87
95.0
0.38
3.99
100.0
0.33
4.10
5-2. Outdoor unit