2-16. E: 53. Drain pump error (Indoor unit)
Indicator
Wired remote
controller
Error code
E: 53
Detective actuator
Indoor unit main PCB
When Float switch is ON for more than 3 minutes.
Float switch
Forecast of cause
Float switch failure
Shorted connector/wire failure
Main PCB failure
Drain pump failure
Hose clogging
Check point 1. Check float switch
•
Check operation of float switch. (any blocking by dust, etc.)
•
Remove float switch and check ON/OFF switching operation by using a meter.
-> If float switch is abnormal, replace it.
↓
Check point 2. Check connector and wire
Check loose contact of CN9 and shorted wire (pinched wire).
-> Replace float switch if the wire is abnormal
↓
Check point 3. Check drain hose
Check drain hose.
-> If there is hose clogging. Please clear the clog.
↓
Check point 4. Replace drain pump
If check point 1 to 3 do not improve the symptom, replace drain pump.
↓
Check point 5. Replace main PCB
If check point 4 do not improve the symptom, replace main PCB.
↓
End
2-16. E: 53. Drain pump error (Indoor unit)
- (03-23) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for AUXG18KVLA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 05 19 SR_CH01_SM001EG_02 ...
Page 22: ...3 4 Outdoor unit 01 16 3 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 23: ...2 TECHNICAL DATA AND PARTS LIST 2021 06 15 SR_CH02_SM001EG_04 ...
Page 69: ...3 TROUBLESHOOTING 2021 06 15 SR_CH03_SM001EG_03 ...
Page 72: ......
Page 143: ...4 CONTROL AND FUNCTIONS 2021 05 19 SR_CH04_SM001EG_02 ...
Page 146: ......
Page 185: ...5 FILED WORKING 2021 06 15 SR_CH05_SM001EG_03 ...