9-2. Function settings by using remote controller
Some function settings can be changed on the remote controller. After confirming the setting proce-
dure and the content of each function setting, select appropriate functions for your installation envi-
ronment.
¢
Setting procedure by using remote controller
Remote controller is not attached for this product. For details of the installing remote controller, refer
to following information.
• Overview information: Operating manual of the remote controller
• Setting procedure: Installation manual of the remote controller
¢
Contents of function setting
Each function setting listed in this section is adjustable in accordance with the installation environ-
ment.
NOTE:
Setting will not be changed if invalid numbers or setting values are selected.
Function setting list
Function no.
Functions
1)
11
Filter sign
2)
20
Ceiling height
3)
22
Outlet directions
4)
30/31
Room temperature control for indoor unit sensor
5)
35/36
Room temperature control for wired remote controller sensor
6)
40
Auto restart
7)
42
Room temperature sensor switching
8)
44
Remote controller custom code
9)
46
External input control
10)
48
Room temperature sensor switching (Aux.)
11)
49
Indoor unit fan control for energy saving for cooling
12)
60
Switching functions for external output terminal
1) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated
amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Function number
Setting value
Setting description
Factory setting
11
00
Standard (2,500 hours)
01
Long interval (4,400 hours)
02
Short interval (1,250 hours)
03
No indication
♦
- 41 -
9-2. Function settings by using remote controller
9. Function settings
CASSETTE TYPE
AUXG09-22KVLA
CASSETTE TYPE
AUXG09-22KVLA
Summary of Contents for AUXG09KVLA
Page 5: ...12 1 Models AOYG09KATA AOYG12KATA AOYG14KATA AOYG18KATA and AOYG22KATA 78 CONTENTS continued ...
Page 6: ......
Page 7: ...Part 1 INDOOR UNIT CASSETTE TYPE AUXG09KVLA AUXG12KVLA AUXG14KVLA AUXG18KVLA AUXG22KVLA ...
Page 56: ... 50 11 3 Others 11 Optional parts CASSETTE TYPE AUXG09 22KVLA CASSETTE TYPE AUXG09 22KVLA ...
Page 57: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG09KATA AOYG12KATA AOYG14KATA AOYG18KATA AOYG22KATA ...