11. Safety devices
Type of
protection
Protection form
Model
AOYG09KATA
AOYG12KATA
Circuit
protection
Current fuse (Main PCB)
250 V, 20 A
250 V, 5 A
Fan motor
protection
Terminal protection
program
Activate
127 ±5 °C
Fan motor stop
Reset
95 °C or less
Fan motor restart
Compressor
protection
Terminal protection
program
(Discharge temp.)
Activate
110 °C
Compressor stop
Reset
After 7 minutes
Compressor restart
Thermal protection
program (Outdoor temp.)
Activate
-20 °C
Compressor stop
Reset
-15 °C
Compressor restart
Type of
protection
Protection form
Model
AOYG14KATA
AOYG18KATA
Circuit
protection
Current fuse (Main PCB)
250 V, 20 A
250 V, 5 A
Fan motor
protection
Terminal protection
program
Activate
127 ±5 °C
Fan motor stop
Reset
95 °C or less
Fan motor restart
Compressor
protection
Terminal protection
program
(Discharge temp.)
Activate
110 °C
Compressor stop
Reset
After 7 minutes
Compressor restart
Thermal protection
program (Outdoor temp.)
Activate
-20 °C
Compressor stop
Reset
-15 °C
Compressor restart
- 73 -
11. Safety devices
OUTDOOR UNIT
AOYG09-18KATA
OUTDOOR UNIT
AOYG09-18KATA