8-4. Details of function
¢
Control input function
•
When function setting is "Operation/Stop" mode 1
Function setting
External input
Input signal
Command
46—00
Terminal
Off → On
Operation
On → Off
Stop
Operation
Stop
Remote controller
On
Off
Indoor unit
On
Input
NOTES:
• The last command has priority.
• The indoor units within the same remote controller group operates in the same mode.
•
When function setting is "Forced stop" mode
Function setting
External input
Input signal
Command
46—02
Terminal
Off → On
Forced stop
On → Off
Normal
On
Off
Forced stop
Normal
Operation
Stop
Remote controller
On
On
Indoor unit
On
Input
NOTES:
• When the forced stop is triggered, indoor unit stops and Operation/Stop operation by the re-
mote controller is restricted.
• When forced stop function is used with forming a remote controller group, connect the same
equipment to each indoor unit within the group.
- 38 -
8-4. Details of function
8. External input and output
DUCT TYPE
ARXG09-18KLLAP
DUCT TYPE
ARXG09-18KLLAP