1-2. Heating operation
A sensor (room temperature thermistor) built in indoor unit body will usually perceive difference or
variation between setting temperature and present room temperature, and controls operation rota-
tion number of compressor.
• If the room temperature is 11 °F (6.0 °C) lower than a set temperature, the operation rotation num-
ber of compressor will attain to maximum performance.
• If the room temperature is 2 °F (1.0 °C) higher than a set temperature, the compressor will be
stopped.
• When the room temperature is within the range of +2 °F (1.0°C) to -11 °F (6.0°C) of the setting
temperature, the rotation number of compressor is controlled within the range shown below.
•
Rotation number range of compressor
Unit: rps
Model name
Minimum frequency
Maximum frequency
ASUH18LPAS
ASUH24LPAS
8
130
•
Limit of maximum speed based on outdoor temperature
In heating operation, maximum rotation number is defined by outdoor temperature and fan mode.
A zone
B zone
57.2°F
(14°C)
C zone
14.0°F
(-10°C)
Outdoor
temperature rises
Outdoor
temperature drops
53.6°F
(12°C)
10.4°F
(
-12
°C)
Unit: rps
Model name
Outdoor
temperature zone
Indoor unit fan mode
HIGH
MED
LOW
QUIET
ASUH18LPAS
A zone
130
111
68
50
B zone
130
111
68
50
C zone
130
111
68
50
ASUH24LPAS
A zone
130
130
102
68
B zone
130
130
102
68
C zone
130
130
102
68
1-2. Heating operation
- (04-3) -
1. Rotation number control of compressor
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for AOUH18LPAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 10 12 SR_CH01_AS051EF_02 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2021 07 04 SR_CH02_AS051EF_01 ...
Page 33: ...3 TROUBLESHOOTING 2021 08 04 SR_CH03_AS051EF_01 ...
Page 36: ......
Page 95: ...4 CONTROL AND FUNCTIONS 2021 08 04 SR_CH04_AS051EF_01 ...
Page 129: ...5 FILED WORKING 2021 08 04 SR_CH05_AS051EF_01 ...