1-3. Dry operation
The rotation number of compressor shall change according to the temperature, set temperature, and
room temperature variation which the room temperature sensor of the indoor unit has detected as
shown in the table below.
Zone is defined by set temperature and room temperature.
•
Rotation number range of compressor
Unit: rps
Model name
Outdoor temperature zone
Operating frequency
ASUH18LPAS
X zone
22
J zone
16
Y zone
0
ASUH24LPAS
X zone
26
J zone
22
Y zone
0
•
Compressor control based on room temperature
Ts+1°F
(Ts+0.5°C)
Ts-3°F
(Ts-1.5
°C)
Ts+3°F
(Ts+1.5
°C)
X zone
J zone
Y zone
Room temperature drops
Room temperature rises
Ts: Set temperature
Ts-1°F
(Ts-0.5°C)
1-4. Rotation number of compressor at normal start-up
Compressor frequency soon after starting is controlled as below.
Rotation number I
Rotation number II
Rotation number III
Rotation number IV
Rotation number V
Rotation number VI
Time 1
Time 2
Time 3
Time 4
Time 5
Time 6
Frequency
(rps)
I
II
III
IV
V
VI
35
52
64
71
89
97
Time (sec)
1
2
3
4
5
6
60
140
170
200
350
410
1-3. Dry operation
- (04-4) -
1. Rotation number control of compressor
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for AOUH18LPAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 10 12 SR_CH01_AS051EF_02 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2021 07 04 SR_CH02_AS051EF_01 ...
Page 33: ...3 TROUBLESHOOTING 2021 08 04 SR_CH03_AS051EF_01 ...
Page 36: ......
Page 95: ...4 CONTROL AND FUNCTIONS 2021 08 04 SR_CH04_AS051EF_01 ...
Page 129: ...5 FILED WORKING 2021 08 04 SR_CH05_AS051EF_01 ...