7-6. POWERFUL operation
The PO→ERFUL operation starts by pressing PO→ERFUL button on the remote controller.
The indoor unit and outdoor unit operate at maximum power as shown in the table below.
ASUH18LMAS
ASUH24LMAS
Compressor frequency
Maximum
Fan mode
PO→ERFUL
Vertical airflow direction
louver setting
Cooling
3
Dry
Heating
6
5
Release condition:
• Cooling/Dry
Room temperature ≤ Setting temperature -1°F (-0.5°C) or Operation time has passed 20 minutes.
• Heating
Room temperature ≥ Setting tempe1°F (+0.5°C) or Operation time has passed 20 minutes.
7-7. Fresh air control
The fan motor for Fresh Air is operated in synchronization with the indoor fan operation as below.
Operation
Stop
Operation
Stop
Fan motor
(Indoor unit)
Fan motor
(for Fresh Air)
7-8. Compressor preheating
By preheating the compressor, warm airflow is quickly discharged when the operation is started.
•
Triggering condition 1
– Outdoor temperature ≤ 68°F (20°C)
→hen outdoor temperature reaches 78.8°F (26°C), compressor preheating stops.
– 30 minutes after compressor stopped
•
Triggering condition 2
32.0°F
(0°C)
Off
On
Tn
Tn
35.6°F
(2°C)
Tn: Outdoor unit heat exchanger temp.
7-6. PO→ERFUL operation
- (04-25) -
7. Various control
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
Summary of Contents for AOUH18LMAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 11 01 SR_CH01_AS052EF_01 ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 11 17 SR_CH02_AS052EF_04 ...
Page 39: ...3 TROUBLESHOOTING 2021 11 17 SR_CH03_AS052EF_01 ...
Page 42: ......
Page 135: ...4 CONTROL AND FUNCTIONS 2021 11 17 SR_CH04_AS052EF_01 ...
Page 138: ......
Page 173: ...5 FILED WORKING 2021 11 17 SR_CH05_AS052EF_01 ...