1-5. Rotation number of compressor limitation by outdoor
temperature
The minimum rotation number of compressor is limited by outdoor temperature as below.
•
Cooling/Dry mode
F zone
E zone
D zone
C zone
B zone
A zone
G zone
J zone
H zone
I zone
87.8°F
(31°C)
35.6°F
(2°C)
69.8°F
(21°C)
44.6°F
(7°C)
23.0°F
(-5°C)
5.0°F
(-15°C)
14.0°F
(-10°C)
100.4°F
(38°C)
107.6°F
(42°C)
K zone
55.4°F
(13°C)
Model name
Outdoor temperature zone
Limitation of compressor
frequency
AOUH18LMAS1
A zone
55 rps
B zone
50 rps
C zone
36 rps
D zone
34 rps
E zone
30 rps
F zone
26 rps
G zone
19 rps
H zone
19 rps
I zone
21 rps
J zone
24 rps
K zone
29 rps
AOUH24LMAS1
A zone
60 rps
B zone
55 rps
C zone
52 rps
D zone
45 rps
E zone
36 rps
F zone
28 rps
G zone
21 rps
H zone
19 rps
I zone
21 rps
J zone
24 rps
K zone
29 rps
1-5. Rotation number of compressor limitation by outdoor temperature
- (04-5) -
1. Rotation number control of compressor
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
Summary of Contents for AOUH18LMAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 11 01 SR_CH01_AS052EF_01 ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 11 17 SR_CH02_AS052EF_04 ...
Page 39: ...3 TROUBLESHOOTING 2021 11 17 SR_CH03_AS052EF_01 ...
Page 42: ......
Page 135: ...4 CONTROL AND FUNCTIONS 2021 11 17 SR_CH04_AS052EF_01 ...
Page 138: ......
Page 173: ...5 FILED WORKING 2021 11 17 SR_CH05_AS052EF_01 ...