1-2. Heating operation
A sensor (room temperature thermistor) built in indoor unit body will usually perceive difference or
variation between setting temperature and present room temperature, and controls operation fre-
quency of compressor.
• If the room temperature is 6.0 °C lower than a set temperature, the compressor operation frequen-
cy will attain to maximum performance.
• If the room temperature is 1.0 °C higher than a set temperature, the compressor will be stopped.
• When the room temperature is within the range of +1.0°C to -6.0°C of the setting temperature, the
compressor frequency is controlled within the range shown below.
•
Compressor frequency range
Unit: rps
Model name
Minimum frequency
Maximum frequency
ASUG09LMAS
ASUG12LMAS
12
110
•
Limit of maximum speed based on outdoor temperature
In heating operation, maximum frequency is defined by outdoor temperature and fan mode.
A zone
12°C
B zone
14°C
C zone
-10°C
-12°C
Outdoor
temperature rises
Outdoor
temperature drops
Unit: rps
Model name
Outdoor
temperature
zone
Indoor unit fan mode
HIGH
MED
LOW
QUIET
ASUG09LMAS
ASUG12LMAS
A zone
110
89
77
67
B zone
110
89
77
67
C zone
110
89
77
36
1-2. Heating operation
- (04-2) -
1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for AOUG09LMAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2019 12 20 SR_CH01_AS023EF_01 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 01 28 SR_CH02_AS023EF_01 ...
Page 33: ...3 TROUBLESHOOTING 2020 01 30 SR_CH03_AS023EF_02 ...
Page 77: ...4 CONTROL AND FUNCTIONS 2020 03 25 SR_CH04_AS023EF_02 ...
Page 107: ...5 FILED WORKING 2020 02 03 SR_CH05_AS023EF_01 ...