8. Various protections
8-1. Discharge gas temperature over-rise prevention control
The discharge gas temperature sensor (discharge thermistor: outdoor unit side) detects the dis-
charge gas temperature.
• When the discharge temperature becomes higher than the trigger condition, the compressor fre-
quency is decreased as the table below, and it continues to decrease until the discharge tempera-
ture becomes lower than the trigger condition.
• When the discharge temperature becomes lower than the release condition, control of compressor
frequency is released.
• When the discharge temperature becomes higher than the compressor protection temperature,
the compressor is stopped and the indoor unit LED starts blinking.
Trigger condition
104°C
Compressor frequency
30 model
-20 rps/120 seconds
34 model
-14 rps/120 seconds
Release condition
101°C
Compressor protection temperature
110°C
8-2. Anti-freezing control (cooling and dry mode)
The compressor frequency is decrease in cooling and dry mode when the indoor unit heat exchang-
er temperature sensor detects the temperature lower than the trigger condition.
When the indoor unit heat exchanger temperature reaches release condition, the anti-freezing con-
trol is stopped.
Trigger condition
4°C
Release condition
Outdoor temp. ≥ 10°C*
1
Outdoor temp. ≥ 12°C*
2
7°C
Outdoor temp. < 10°C*
1
Outdoor temp. < 12°C*
2
13°C
*1: During the outdoor temperature dropping
*2: During the outdoor temperature rising
8-3. Current release control
The compressor frequency is controlled so that the outdoor unit input current does not exceeds cur-
rent limit value set according to the outdoor temperature.
The compressor frequency returns according to the operation mode, when the current becomes low-
er than the release value.
¢
Model: AOTG30KMTC
Operation mode
Outdoor temp. (Ta)
Trigger condition
Release condition
Cooling
50°C ≤ Ta
7.5 A
7.0 A
46°C ≤ Ta < 50°C
10.0 A
9.5 A
40°C ≤ Ta < 46°C
12.5 A
12.0 A
Ta < 40°C
14.5 A
14.0 A
Heating
17°C ≤ Ta
10.0 A
9.5 A
12°C ≤ Ta < 17°C
11.5 A
11.0 A
Ta < 12°C
14.5 A
14.0 A
8-1. Discharge gas temperature over-rise prevention control
- (04-26) -
8. Various protections
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for AOTG30KMTC
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2019 06 27 SR_CH01_AS004EF_01 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 05 12 SR_CH02_AS004EF_05 ...
Page 35: ...3 TROUBLESHOOTING 2020 05 08 SR_CH03_AS004EF_02 ...
Page 38: ......
Page 128: ...6 2 Outdoor unit 03 90 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 129: ...4 CONTROL AND FUNCTIONS 2020 05 08 SR_CH04_AS004EF_02 ...
Page 132: ......
Page 163: ...5 FILED WORKING 2019 07 24 SR_CH05_AS004EF_01 ...