2-10. E: 35. MANUAL AUTO button error (Indoor unit)
Indicator
Indoor unit
Operation indicator
3 time flash
Timer indicator
5 time flash
Economy indicator
Continuous flash
Error code
E: 35
Detective actuator
Indoor unit controller PCB
→hen the MANUAL AUTO button becomes on for
consecutive 60 or more seconds.
Indicator PCB
Manual auto switch
Forecast of cause
MANUAL AUTO button failure
Controller PCB and indicator PCB failure
Check point 1. Check the MANUAL AUTO but-
ton
If MANUAL AUTO button is disabled (on/off
switching), replace it.
•
Check if MANUAL AUTO button is
kept pressed.
•
Check On/Off switching operation
by using a meter.
Check point 2. Replace main PCB and indicator PCB
If Check Point 1 does not improve the symptom, change main PCB and indicator PCB.
End
2-10. E: 35. MANUAL AUTO button error (Indoor unit)
- (03-14) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Summary of Contents for AOHG07KGCA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 3 11 SR_CH01_AS069EG_01 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 3 11 SR_CH02_AS069EG_01 ...
Page 33: ...3 TROUBLESHOOTING 2022 03 25 SR_CH03_AS069EG_01 ...
Page 36: ......
Page 89: ...4 CONTROL AND FUNCTIONS 2022 03 25 SR_CH04_AS069EG_01 ...
Page 91: ...8 6 High temperature and high pressure release control heating mode 04 32 CONTENTS continued ...
Page 92: ......
Page 125: ...5 FILED WORKING 2022 03 25 SR_CH05_AS069EG_01 ...