8-5. Low outdoor temperature protection
→hen the outdoor temperature sensor detects lower than the trigger condition below, the compres-
sor is stopped.
Operation mode
Cooling/Dry
Trigger condition
-15 °C
Release condition
-10 °C
8-6. High temperature and high pressure release control
(heating mode)
The compressor is controlled as follows.
Indoor unit heat exchanger
temperature rises
Indoor unit heat exchanger
temperature drops
Stable zone
AB
BC
CD
DE
Zone A
Zone B
Zone C
Zone D
Zone E
AB: 63°C
BC: 55°C
CD: 53°C
DE: 50°C
Zone
Operation
Zone A
Compressor is stopped.
Zone B
The rotation number of compressor is decreased.
-25 rps/120 sec.
Zone C
-3 rps/60 sec.
Zone D
The protection is released and the operation is returned to normal mode.
Zone E
8-5. Low outdoor temperature protection
- (04-32) -
8. Various protections
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
Summary of Contents for AOHG07KGCA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 3 11 SR_CH01_AS069EG_01 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 3 11 SR_CH02_AS069EG_01 ...
Page 33: ...3 TROUBLESHOOTING 2022 03 25 SR_CH03_AS069EG_01 ...
Page 36: ......
Page 89: ...4 CONTROL AND FUNCTIONS 2022 03 25 SR_CH04_AS069EG_01 ...
Page 91: ...8 6 High temperature and high pressure release control heating mode 04 32 CONTENTS continued ...
Page 92: ......
Page 125: ...5 FILED WORKING 2022 03 25 SR_CH05_AS069EG_01 ...