Preparation
Before performing the setting, be sure to conducting necessary preparations.
1.
Make sure that the operation of the outdoor unit has stopped (if it is still running, stop the oper-
ation), and turn off the power.
2.
Remove the front panel of the outdoor unit.
3.
Remove the lid of the electrical component box to expose the PCB.
4.
Turn on the power of the outdoor unit. When the system is operated normally, the indicator
lamps may light as in following figure:
LED101
(GREEN)
POWER
MODE
LED105
LED104
LED102
(RED)
ERROR
Off
Off
Off
On
• Make sure that the POWER/MODE indicator lamp (LED101) is on and the ERROR indicator
lamp (LED102) is off.
• If there is a system error, the ERROR indicator lamp (LED102) flashes. Check the wiring and
power supply. After confirming the ERROR indicator lamp (LED102) has turned off, proceed
to the setting procedure.
¢
Automatic address setting of signal amplifier
CAUTION
• This function can be used for a maximum of 8 signal amplifiers installed within a same refriger-
ant system.
• Perform this setting on only 1 outdoor unit (master unit) within the same network. No duplicate
setting of this function from other outdoor unit is allowed.
• When setting the address of a signal amplifier automatically, be sure to always set the address
on the PCB of the signal amplifier to “1” (factory setting).
1.
After verifying that the system is operating normally, press the MODE/EXIT button (SW107)
once.
LED105
LED104
LED105
LED104
2.
Press the SELECT button (SW108) to display “F3” on LED104.
*
1
: Do not set “F1” and “F9” usually since they are used for maintenance.
(The display of the LED104 changes each time the SELECT button is pressed.)
LED105
LED104
LED105
LED104
LED105
LED104
LED105
LED104
*
1
*
1
Monitoring mode
Setting mode
Function mode
Error history mode
1-5. Automatic address setting
- (07-50) -
1. System settings
FUNCTION
SETTINGS
FUNCTION
SETTINGS
Summary of Contents for AIRSTAGE J-IIIL
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION 2019 11 01 DV_CH01_J3LU061EF_02 ...
Page 20: ...2 5 Others 01 16 2 Optional parts GENERAL INFORMATION GENERAL INFORMATION ...
Page 21: ...2 MODEL SELECTION 2019 11 01 DV_CH02_J3LU061EF_02 ...
Page 94: ...5 1 Stand alone 02 72 5 Heating capacity table Outdoor unit MODEL SELECTION MODEL SELECTION ...
Page 95: ...3 OUTDOOR UNITS 2019 03 07 DV_CH03_J3LU061EF_01 ...
Page 120: ...11 1 Stand alone 03 24 11 Accessories OUTDOOR UNITS OUTDOOR UNITS ...
Page 121: ...4 INDOOR UNITS 2019 11 01 DV_CH04_J3LU061EF_02 ...
Page 337: ...5 CONTROL SYSTEM 2019 11 01 DV_CH05_VR2E018EF_04 ...
Page 521: ...6 SYSTEM DESIGN 2019 11 01 DV_CH06_J3LU061EF_02 ...
Page 599: ...7 FUNCTION SETTINGS 2019 11 01 DV_CH07_J3LU061EF_02 ...
Page 753: ...8 EXTERNAL INPUT AND OUTPUT 2019 11 01 DV_CH08_J3LU061EF_02 ...
Page 831: ...9 NOTES 2019 11 01 DV_CH09_J3LU061EF_04 ...
Page 850: ...4 2 Wiring connection 09 18 4 About connection between series NOTES NOTES ...
Page 851: ...10 OPTIONAL PARTS 2019 11 01 DV_CH10_VR2E018EF_05 ...