1-5. Control device design limitation
Central control
Central controller
Necessary
device
Maximum units number
Connectable
units
Manageable
indoor units
Connectable
outdoor units
System controller
UTY-APGXZ1
USB adapter
1/system
1,600
(4 VRF
networks)
400
(4 VRF
networks)
System controller
lite
UTY-ALGXZ1
USB adapter
1/system
400
(1 VRF
networks)
100
(1 VRF
networks)
Touch panel
controller
UTY-DTGYZ1
—
16/system
400
100
Central remote
controller
UTY-DCGY
UTY-DCGYZ1
—
100
Adaptor/Convertor
Necessary
device
Maximum units number
Connectable
units
Manageable
indoor units
Connectable
outdoor units
Network convertor
UTY-VTGX
UTY-VGGXZ1
—
100/system
—
—
Network convertor
for LonWorks*
1
UTY-VLGX
—
1/system
128*
2
100
BACnet gateway
UTY-VBGX
—
4/system
128*
2
100
UTY-ABGXZ1
USB adapter
1/system
1,600
(4 VRF
networks)
400
(4 VRF
networks)
Modbus convertor
UTY-VMGX
—
9/system
128*
2
100
Thermostat
convertor
UTY-TTRX
—
—
16*
3
—
Signal amplifier
UTY-VSGXZ1
—
40/system
—
—
Wireless LAN
adapter
UTY-TFSXZ2
—
—
—
—
• *1: A maximum of 4 Network convertors for LonWorks can be connected to 1 BMS.
• *2: Maximum controllable indoor unit number per one convertor. (For proper configuration, re-
fer to system diagram of each device.)
• *3: Maximum connectable indoor unit number per one remote controller group.
Service and Maintenance
Necessary
device
Maximum units number
Connectable
units
Manageable
indoor units
Connectable
outdoor units
Service tool
UTY-ASGXZ1
USB adapter
1/system
400
100
Web monitoring
tool
UTY-AMGXZ1
1,600
(4 VRF
networks)
400
(4 VRF
networks)
1-5. Control device design limitation
- (05-12) -
1. Control system
CONTROL
SYSTEM
CONTROL
SYSTEM
Summary of Contents for AIRSTAGE J-IIIL
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION 2019 11 01 DV_CH01_J3LU061EF_02 ...
Page 20: ...2 5 Others 01 16 2 Optional parts GENERAL INFORMATION GENERAL INFORMATION ...
Page 21: ...2 MODEL SELECTION 2019 11 01 DV_CH02_J3LU061EF_02 ...
Page 94: ...5 1 Stand alone 02 72 5 Heating capacity table Outdoor unit MODEL SELECTION MODEL SELECTION ...
Page 95: ...3 OUTDOOR UNITS 2019 03 07 DV_CH03_J3LU061EF_01 ...
Page 120: ...11 1 Stand alone 03 24 11 Accessories OUTDOOR UNITS OUTDOOR UNITS ...
Page 121: ...4 INDOOR UNITS 2019 11 01 DV_CH04_J3LU061EF_02 ...
Page 337: ...5 CONTROL SYSTEM 2019 11 01 DV_CH05_VR2E018EF_04 ...
Page 521: ...6 SYSTEM DESIGN 2019 11 01 DV_CH06_J3LU061EF_02 ...
Page 599: ...7 FUNCTION SETTINGS 2019 11 01 DV_CH07_J3LU061EF_02 ...
Page 753: ...8 EXTERNAL INPUT AND OUTPUT 2019 11 01 DV_CH08_J3LU061EF_02 ...
Page 831: ...9 NOTES 2019 11 01 DV_CH09_J3LU061EF_04 ...
Page 850: ...4 2 Wiring connection 09 18 4 About connection between series NOTES NOTES ...
Page 851: ...10 OPTIONAL PARTS 2019 11 01 DV_CH10_VR2E018EF_05 ...