1-4. Wiring system
• Wiring configuration of the control system is made of power source wiring, transmission wiring,
and remote controller wiring.
• Total wiring length (total length of transmission line) can be extended up to 11,811 ft (3,600 m) by
using signal amplifier.
Card key
L
ON
W
ORKS
®
To outdoor units
USB Adaptor
NW1
USB
Adaptor
Network Convertor
UTY-VGGXZ1
Network Convertor UTY-VLGX
Network Convertor
UTY-VTGX or UTY-VGGXZ1
UTY-VSGXZ1
Web Monitoring Tool
UTY-AMGXZ1
Web Monitoring Tool
Trouble free operation at all times
by remote monitoring system.
Transmission Line
line is non-polar 2-conductor.
Service Tool
Extensive monitoring and analysis
functions for installation and maintenance.
2 Remote Controllers
Indoor unit can be controlled
from both remote controllers.
External Switch Controller
Indoor units can be controlled by combining
with Card-key switch such as hotel room.
System without Remote Controller
Together with Touch panel controller, it is
possible to build non remote controller system.
Remote controller line (3 wire)
Maximum 16 units can be controlled
Touch Panel Controller
One Touch panel controller can control
up to 400 groups / 400 indoor units.
IR Receiver Kit
Cassette type indoor unit can be
controlled with wireless remote controller
IR Receiver Unit
Duct type indoor unit
can be controlled
with wireless remote
controller.
Service Tool
UTY-ASGXZ1
Single system
(VRF network system side)
(Monitoring side)
(Monitoring side)
BACnet
®
Gateway
UTY-ABGXZ1
BACnet
®
L
ON
W
ORKS
®
Network
BACnet
®
11,811 ft.
(3,600 m)
Max. Transmission
line length
BACnet
®
Operator
Workstation (B-OWS)
NW2
NW3
NW4
Combination of individual remote controller
Wired, simple and wireless remote controllers can be used jointly.
(Monitoring side)
Internet
or
Public Telephone Line
USB
Adaptor
USB Adaptor
Internet
or
Public Telephone Line
Internet
Central Remote Controller
Maximum 100 indoor units can be controlled
Remote controller line (2 wire)
Maximum 16 units can be controlled
Indoor unit
(Cassette)
Indoor unit
(Duct)
RB unit
(Single)
RB unit
(Multi)
Touch Panel
Controller
Wired Remote
Controller
Wired Remote
Controller
Central Remote
Controller
Transmission line
Module link
Remote controller
line (3 line)
Remote controller
line (2 line)
Signal line
(single system)
USB cable
System Controller UTY-APGXZ1 or System Controller Lite UTY-ALGXZ1
• Maximum 1,600 indoor units can be controlled.*¹
• Air conditioning control
• Operation monitoring
• Status monitoring system
• Electricity charge calculation*²
Case of UTY-ALGXZ1
*1: Maximum 400 indoor units can be controlled.
*2: Option is necessary.
*3: Cannot be used.
(Remote / Monitoring side) *²
(Remote / Monitoring side)
Modbus Convertor UTY-VMGX
Modbus
Network
Modbus
Simple Remote
Controller
Simple Remote
Controller
Simple Remote
Controller
Wireless Remote
Controller
External Switch
Controller
IR Receiver unit
1-4. Wiring system
- (05-11) -
1. Control system
CONTROL
SYSTEM
CONTROL
SYSTEM
Summary of Contents for AIRSTAGE J-IIIL
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION 2019 11 01 DV_CH01_J3LU061EF_02 ...
Page 20: ...2 5 Others 01 16 2 Optional parts GENERAL INFORMATION GENERAL INFORMATION ...
Page 21: ...2 MODEL SELECTION 2019 11 01 DV_CH02_J3LU061EF_02 ...
Page 94: ...5 1 Stand alone 02 72 5 Heating capacity table Outdoor unit MODEL SELECTION MODEL SELECTION ...
Page 95: ...3 OUTDOOR UNITS 2019 03 07 DV_CH03_J3LU061EF_01 ...
Page 120: ...11 1 Stand alone 03 24 11 Accessories OUTDOOR UNITS OUTDOOR UNITS ...
Page 121: ...4 INDOOR UNITS 2019 11 01 DV_CH04_J3LU061EF_02 ...
Page 337: ...5 CONTROL SYSTEM 2019 11 01 DV_CH05_VR2E018EF_04 ...
Page 521: ...6 SYSTEM DESIGN 2019 11 01 DV_CH06_J3LU061EF_02 ...
Page 599: ...7 FUNCTION SETTINGS 2019 11 01 DV_CH07_J3LU061EF_02 ...
Page 753: ...8 EXTERNAL INPUT AND OUTPUT 2019 11 01 DV_CH08_J3LU061EF_02 ...
Page 831: ...9 NOTES 2019 11 01 DV_CH09_J3LU061EF_04 ...
Page 850: ...4 2 Wiring connection 09 18 4 About connection between series NOTES NOTES ...
Page 851: ...10 OPTIONAL PARTS 2019 11 01 DV_CH10_VR2E018EF_05 ...