2-21. DUCT STATIC PRESSURE SETTING
MODEL: ARUL4TLAV1
MODELS: ARUL7TLAV, ARUL9TLAV, ARUL12TLAV, ARUL14TLAV,
ARUL18TLAV
MODELS: ARUM24TLAV, ARUM30TLAV, ARUM36TLAV
MODELS: ARUH72TLAV1, ARUH96TLAV
Change the airflow setting when the external static pressure is different than the default static
pressure.
Static pressure setting can be performed using: wireless remote controller, wired remote
controller, and simple remote controller.
How to set airflow (external static pressure)
●
Wireless remote controller
Airflow is set by function number 26 (static pressure).
Refer to "BUTTON NANE AND FUNCTION", "FUNCTION SETTING" and "FUNCTION
DETAILS" in 2-3. INDOOR UNIT (setting by wireless remote controller).
●
Wired remote controller
Airflow is set by function number 26 (static pressure).
Refer to "BUTTON NANE AND FUNCTION", "FUNCTION SETTING" and "FUNCTION
DETAILS" in 2-4. INDOOR UNIT (setting by wired remote controller).
●
Simple remote controller
Airflow is set by function number 26 (static pressure).
Refer to "BUTTON NANE AND FUNCTION", "FUNCTION SETTING" and "FUNCTION
DETAILS" in 2-5. INDOOR UNIT (setting by simple remote controller).
●
Wired remote controller (Touch panel)
Airflow is set by function number 26 (static pressure).
Refer to "FUNCTION SETTING" and "FUNCTION DETAILS" in 2-6. INDOOR UNIT (setting
by wired remote controller [Touch panel]).
●
FAN PERFORMANCE CURVE
Refer to "7. FAN PERFORMANCE CURVE" in Chapter 4.
NOTE
● If airflow is set incorrectly, unit may perform incorrectly; insufficient airflow or condensate
carry-over (water leakage) are possible.
- (07 - 142) -
FUN
C
TI
O
N
SE
TTI
N
G
FUN
C
TI
O
N
SE
TTI
N
G
Summary of Contents for Airstage AGUA12TLAV1
Page 1: ...Small VRF system for light commercial and home use DESIGN TECHNICAL MANUAL ...
Page 22: ...1 GENERAL INFORMATION DTV_J2U045E_06 CHAPTER01 2018 03 16 ...
Page 38: ...2 MODEL SELECTION DTV_J2U045E_05 CHAPTER02 2018 03 16 ...
Page 113: ...3 OUTDOOR UNITS DTV_J2U045E_02 CHAPTER03 2016 04 13 ...
Page 122: ...5 WIRING DIAGRAM MODELS AOU36RLAVM AOU48RLAVM 03 08 OUTDOOR UNITS OUTDOOR UNITS ...
Page 123: ... MODELS AOU60RLAVM 03 09 OUTDOOR UNITS OUTDOOR UNITS ...
Page 127: ... SOUND LEVEL CHECK POINT Microphone Airflow 39 3 8 in 1 m 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Page 130: ...4 INDOOR UNITS DTV_VR2U025E_10 CHAPTER04 2018 01 26 ...
Page 203: ...4 WIRING DIAGRAMS 4 1 COMPACT CASSETTE TYPE MODEL AUUA4TLAV1 04 70 INDOOR UNITS INDOOR UNITS ...
Page 207: ...4 4 MINI DUCT TYPE MODEL ARUL4TLAV1 04 74 INDOOR UNITS INDOOR UNITS ...
Page 211: ... MODELS ARUH72TLAV1 ARUH96TLAV 04 78 INDOOR UNITS INDOOR UNITS ...
Page 215: ...4 11 CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV 04 82 INDOOR UNITS INDOOR UNITS ...
Page 217: ... MODELS ASUA12TLAV1 ASUA14TLAV1 04 84 INDOOR UNITS INDOOR UNITS ...
Page 218: ... MODELS ASUB18TLAV1 ASUB24TLAV1 04 85 INDOOR UNITS INDOOR UNITS ...
Page 219: ... MODELS ASUB30TLAV1 ASUB36TLAV1 04 86 INDOOR UNITS INDOOR UNITS ...
Page 220: ... MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 04 87 INDOOR UNITS INDOOR UNITS ...
Page 221: ... MODELS ASUB18TLAV ASUB24TLAV 04 88 INDOOR UNITS INDOOR UNITS ...
Page 361: ...5 CONTROL SYSTEM DTV_VR2U025E_14 CHAPTER05 2018 03 16 ...
Page 563: ...6 SYSTEM DESIGN DTV_J2U045E_05 CHAPTER06 2017 12 26 ...
Page 645: ...7 FUNCTION SETTING DTV_VR2U025E_12 CHAPTER07 2018 03 16 ...
Page 819: ...8 EXTERNAL INPUT OUTPUT DTV_VR2U025E_08 CHAPTER08 2017 12 26 ...
Page 878: ...9 NOTES DTV_VR2U025E_10 CHAPTER09 2017 12 26 ...
Page 894: ...10 OPTIONAL PARTS DTV_VR2U025E_12 CHAPTER10 2018 03 16 ...
Page 935: ...4 5 WIRING DIAGRAMS MODEL UTP RU01AH MODEL UTP RU01BH 10 40 OPTIONAL PARTS OPTIONAL PARTS ...
Page 936: ... MODEL UTP RU01CH 10 41 OPTIONAL PARTS OPTIONAL PARTS ...
Page 937: ... MODEL UTP RU04BH 10 42 OPTIONAL PARTS OPTIONAL PARTS ...