2-5. ADDITIONAL CHARGE CALCULATION
●
The outdoor unit is charged refrigerant at the factory.
●
Additional refrigerant required to be charged on site depending on pipe length.
●
The additional refrigerant charge amount is calculated according to the following formula.
●
Round up the calculated result to two decimal places.
CALCULATION OF ADDITIONAL CHARGE REFRIGERANT
1. Calculation of additional amount for outdoor unit
Model
Ton
b
Factory charged
amount [lbs. (kg)]
AOU36RLAVM 3
10.6 (4.80)
AOU48RLAVM 4
11.7 (5.30)
AOU60RLAVM 5
11.7 (5.30)
Diameter of liquid
pipe [in. (mm)]
a
Additional amount for pipe
length [lbs./ft. (kg/m)]
ø1/4" (6.35)
0.014 (0.021)
ø3/8" (9.52)
0.039 (0.058)
2. Calculation of additional amount for pipe length
Total length
of ø
3/8"
(
9.52mm)
liquid pipe
a :
x 0.039 lbs/ft.
(0.058 kg/m)
ft. (m)
lbs. (kg)
Total
length
of ø
1/4"
(
6.35mm)
liquid pipe
a :
x 0.014 lbs/ft.
(0.021 kg/m)
ft. (m)
lbs. (kg)
+
A=
=
Total
lbs. (kg)
3. Calculation of additional charge refrigerant
A =
lbs. (kg)
Round up A to 2 decimal place.
4. Factory charged amount
b : Outdoor unit
factory charged amount
lbs. (kg)
B=
5. Total refrigerant amount check
C = A + B =
lbs. (kg)
Note : Check the total refrigerant amount under the following conditions.
Condition
Computational formula
Total amount of refrigerant ≤ 34.61 lbs. (15.70kg)
C ≤ 34.61 lbs. (15.70kg)
When total refrigerant amount exceed limitation.
●
Reduce pipe length for refrigerant system.
●
Change the refrigerant system configuration.
- (06 - 21) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Summary of Contents for Airstage AGUA12TLAV1
Page 1: ...Small VRF system for light commercial and home use DESIGN TECHNICAL MANUAL ...
Page 22: ...1 GENERAL INFORMATION DTV_J2U045E_06 CHAPTER01 2018 03 16 ...
Page 38: ...2 MODEL SELECTION DTV_J2U045E_05 CHAPTER02 2018 03 16 ...
Page 113: ...3 OUTDOOR UNITS DTV_J2U045E_02 CHAPTER03 2016 04 13 ...
Page 122: ...5 WIRING DIAGRAM MODELS AOU36RLAVM AOU48RLAVM 03 08 OUTDOOR UNITS OUTDOOR UNITS ...
Page 123: ... MODELS AOU60RLAVM 03 09 OUTDOOR UNITS OUTDOOR UNITS ...
Page 127: ... SOUND LEVEL CHECK POINT Microphone Airflow 39 3 8 in 1 m 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Page 130: ...4 INDOOR UNITS DTV_VR2U025E_10 CHAPTER04 2018 01 26 ...
Page 203: ...4 WIRING DIAGRAMS 4 1 COMPACT CASSETTE TYPE MODEL AUUA4TLAV1 04 70 INDOOR UNITS INDOOR UNITS ...
Page 207: ...4 4 MINI DUCT TYPE MODEL ARUL4TLAV1 04 74 INDOOR UNITS INDOOR UNITS ...
Page 211: ... MODELS ARUH72TLAV1 ARUH96TLAV 04 78 INDOOR UNITS INDOOR UNITS ...
Page 215: ...4 11 CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV 04 82 INDOOR UNITS INDOOR UNITS ...
Page 217: ... MODELS ASUA12TLAV1 ASUA14TLAV1 04 84 INDOOR UNITS INDOOR UNITS ...
Page 218: ... MODELS ASUB18TLAV1 ASUB24TLAV1 04 85 INDOOR UNITS INDOOR UNITS ...
Page 219: ... MODELS ASUB30TLAV1 ASUB36TLAV1 04 86 INDOOR UNITS INDOOR UNITS ...
Page 220: ... MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 04 87 INDOOR UNITS INDOOR UNITS ...
Page 221: ... MODELS ASUB18TLAV ASUB24TLAV 04 88 INDOOR UNITS INDOOR UNITS ...
Page 361: ...5 CONTROL SYSTEM DTV_VR2U025E_14 CHAPTER05 2018 03 16 ...
Page 563: ...6 SYSTEM DESIGN DTV_J2U045E_05 CHAPTER06 2017 12 26 ...
Page 645: ...7 FUNCTION SETTING DTV_VR2U025E_12 CHAPTER07 2018 03 16 ...
Page 819: ...8 EXTERNAL INPUT OUTPUT DTV_VR2U025E_08 CHAPTER08 2017 12 26 ...
Page 878: ...9 NOTES DTV_VR2U025E_10 CHAPTER09 2017 12 26 ...
Page 894: ...10 OPTIONAL PARTS DTV_VR2U025E_12 CHAPTER10 2018 03 16 ...
Page 935: ...4 5 WIRING DIAGRAMS MODEL UTP RU01AH MODEL UTP RU01BH 10 40 OPTIONAL PARTS OPTIONAL PARTS ...
Page 936: ... MODEL UTP RU01CH 10 41 OPTIONAL PARTS OPTIONAL PARTS ...
Page 937: ... MODEL UTP RU04BH 10 42 OPTIONAL PARTS OPTIONAL PARTS ...