1-5. Compressor frequency limitation by outdoor temperature
The minimum compressor frequency is limited by outdoor temperature as below.
•
Cooling/Dry mode
F zone
38°C
E zone
19°C
D zone
10°C
C zone
B zone
A zone
0°C
-10°C
Model name
Outdoor temperature zone
Limitation of compressor
frequency
AOYG09KVCBN
A zone
31 rps
B zone
31 rps
C zone
31 rps
D zone
1 rps
E zone
1 rps
F zone
22 rps
AOYG12KVCBN
AOYG14KVCBN
A zone
26 rps
B zone
26 rps
C zone
26 rps
D zone
1 rps
E zone
1 rps
F zone
22 rps
•
Heating mode
F zone
19°C
E zone
5°C
D zone
0°C
C zone
B zone
A zone
-15°C
-25°C
Model name
Outdoor temperature zone
Limitation of compressor
frequency
AOYG09KVCBN
AOYG12KVCBN
AOYG14KVCBN
A zone
39 rps
B zone
39 rps
C zone
17 rps
D zone
10 rps
E zone
1 rps
F zone
1 rps
1-5. Compressor frequency limitation by outdoor temperature
- (04-6) -
1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for AGYG09KVCB
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 10 05 SR_CH01_AG002EF_01 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 25 SR_CH02_AG002EF_02 ...
Page 37: ...3 TROUBLESHOOTING 2020 11 11 SR_CH03_AG002EF_01 ...
Page 39: ...5 1 Indoor unit 03 44 5 2 Outdoor unit 03 45 CONTENTS continued ...
Page 40: ......
Page 87: ...4 CONTROL AND FUNCTIONS 2020 11 11 SR_CH04_AG002EF_01 ...
Page 121: ...5 FILED WORKING 2020 11 11 SR_CH05_AG002EF_01 ...