3-2. Outdoor fan control
¢
Outdoor fan motor
This outdoor unit has a DC fan motor. (Control method is different between AC and DC motors.)
¢
Fan speed
Model: AOYG09KVCBN
Fan speed is defined by outdoor temperature and compressor frequency.
•
Outside air temperature zone selection
21
°C
Outside air
temperature rises
Z zone
Y zone
F zone
G zone
Outside air
temperature drops
12
°C
2
°C
19
°C
10
°C
0
°C
Unit: rpm
Fan step
Cooling
Heating
Dry
Cooling or dry at low outdoor temp.
Y zone
Y zone
Z zone
F zone
G zone
S-HIGH2
—
1,140
—
—
—
—
S-HIGH1
1,050
1,140
—
—
—
—
HIGH
1,050
870
—
—
—
—
10
—
870
—
—
—
—
9
1,050
870
1,050
1,050
200
190
8
970
850
970
970
200
190
7
750
850
750
750
200
190
6
750
700
750
750
200
190
5
650
700
650
650
200
190
4
510
700
510
510
200
190
3
400
420
400
400
200
190
2
400
420
400
400
200
190
1
400
420
400
400
200
190
NOTE:
After defrost control on the heating mode, the fan speed is kept higher regardless of the
compressor frequency.
Fan speed after defrost control: 1,140 rpm
3-2. Outdoor fan control
- (04-14) -
3. Fan control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for AGYG09KVCB
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 10 05 SR_CH01_AG002EF_01 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 25 SR_CH02_AG002EF_02 ...
Page 37: ...3 TROUBLESHOOTING 2020 11 11 SR_CH03_AG002EF_01 ...
Page 39: ...5 1 Indoor unit 03 44 5 2 Outdoor unit 03 45 CONTENTS continued ...
Page 40: ......
Page 87: ...4 CONTROL AND FUNCTIONS 2020 11 11 SR_CH04_AG002EF_01 ...
Page 121: ...5 FILED WORKING 2020 11 11 SR_CH05_AG002EF_01 ...