3. Dimensions

3-1. Compact cassette type

¢

Models: AUXG07KVLA, AUXG09KVLA, AUXG12KVLA, and
AUXG14KVLA

Unit: mm

285

285

Ceiling

1

1

4

B

View A

5

7

0

In

d

o

o

u

n

it

3

7

0

5

4

0

H

a

n

g

in

g

 b

o

lt

 p

o

si

ti

o

n

a

C

e

ili

n

g

 o

p

e

n

in

g

s

5

3

0

530

Hanging bolt position

Drain hose

A

2

1

5

1

9

3

0

1

2

3

3

0

2

6

2

183

Control Box

146

40

C

6

2

0

620

IR receiver

Grid type grille

View B

View C

1

1

4

a: Ceiling openings

Cassette grille (Option [Grid type])

mm

580 to 610

- 13 -

3-1. Compact cassette type

3. Dimensions

2-UNIT

MULTI-SPLIT TYPE

2-UNIT

MULTI-SPLIT TYPE

Summary of Contents for AGYG09KVCA

Page 1: ...ARXG07KLLAP ARXG09KLLAP ARXG12KLLAP ARXG14KLLAP ASYG07KGTB ASYG09KGTB ASYG12KGTB ASYG14KGTB ASYG07KMTB ASYG09KMTB ASYG12KMTB ASYG14KMTB ASYG07KMCC ASYG09KMCC ASYG12KMCC ASYG14KMCC ASYG07KETA ASYG09KETA ASYG12KETA ASYG14KETA ASYG07KETA B ASYG09KETA B ASYG12KETA B ASYG14KETA B OUTDOOR AGYG09KVCA AGYG12KVCA AGYG14KVCA AOYG14KBTA2 AOYG18KBTA2 DR_MU021EF_06 2021 04 19 ...

Page 2: ...ease check with our authorized dealer Trademarks FGLair is trademark of Fujitsu General Limited in the United States other countries or both Google Play is trademark of Google Inc App Store is a service mark of Apple Inc registered in the U S and other countries Copyright 2019 2021 Fujitsu General Limited All rights reserved ...

Page 3: ...ing diagrams 27 4 1 Compact cassette type 27 4 2 Mini duct type and Slim duct type 28 4 3 Wall mounted type 29 4 4 Floor type 33 5 Air velocity and temperature distributions 34 5 1 Compact cassette type 34 5 2 Mini duct type 40 5 3 Slim duct type 48 5 4 Wall mounted type 56 5 5 Floor type 58 6 Fan performance 59 6 1 Mini duct type 59 6 2 Slim duct type 67 7 Airflow 75 7 1 Compact cassette type 75 ...

Page 4: ...er UTY RNNYM Optional part 142 13 6 Wired remote controller UTY RLRY Optional part 146 13 7 Wired remote controller UTY RVNYM Optional part 149 13 8 Wired remote controller UTY RNRYZ Optional part 157 13 9 Simple remote controller UTY RSNYM Optional part 160 13 10 Simple remote controller UTY RSRY and UTY RHRY Optional parts 164 14 Function settings 167 14 1 Compact cassette Mini duct Slim duct ty...

Page 5: ... Controllers 222 16 2 Cassette grille 224 16 3 Others 225 17 Indoor unit installation precautions 228 17 1 Places where prohibited for use 228 17 2 Points to remember when installing 228 CONTENTS continued ...

Page 6: ... Capacity compensation rate for pipe length and height difference 279 7 1 Model AOYG14KBTA2 279 7 2 Model AOYG18KBTA2 281 8 Additional charge calculation 283 8 1 Model AOYG14KBTA2 283 8 2 Model AOYG18KBTA2 283 9 Airflow 284 9 1 Model AOYG14KBTA2 284 9 2 Model AOYG18KBTA2 284 10 Operation noise sound pressure 285 10 1 Noise level curve 285 10 2 Sound level check point 286 11 Electrical characterist...

Page 7: ...YG07KMTB ASYG09KMTB ASYG12KMTB ASYG14KMTB ASYG07KMCC ASYG09KMCC ASYG12KMCC ASYG14KMCC ASYG07KETA ASYG09KETA ASYG12KETA ASYG14KETA ASYG07KETA B ASYG09KETA B ASYG12KETA B ASYG14KETA B SLIM DUCT TYPE ARXG07KLLAP ARXG09KLLAP ARXG12KLLAP ARXG14KLLAP MINI DUCT TYPE ARXG07KSLAP ARXG09KSLAP ARXG12KSLAP ARXG14KSLAP FLOOR TYPE AGYG09KVCA AGYG09KVCA AGYG09KVCA ...

Page 8: ...AP ASYG07KGTB ASYG09KGTB ASYG12KGTB ASYG14KGTB ASYG07KMTB ASYG09KMTB ASYG12KMTB ASYG14KMTB ASYG07KMCC ASYG09KMCC ASYG12KMCC ASYG14KMCC ASYG07KETA ASYG09KETA ASYG12KETA ASYG14KETA ASYG07KETA B ASYG09KETA B ASYG12KETA B ASYG14KETA B AGYG09KVCA AGYG12KVCA AGYG14KVCA Outdoor unit AOYG14KBTA2 AOYG18KBTA2 2 1 Model lineup 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 9: ... 14KGTB Btu class 07 09 12 14 07 09 12 14 kW class 2 0 2 5 3 5 4 0 2 0 2 5 3 5 4 0 AOYG14KBTA2 AOYG18KBTA2 Outdoor unit Wall mounted KM KE ASYG07 14KMTB ASYG07 14KMCC ASYG07 14KETA ASYG07 14KETA B Btu class 07 09 12 14 07 09 12 14 kW class 2 0 2 5 3 5 4 0 2 0 2 5 3 5 4 0 AOYG14KBTA2 AOYG18KBTA2 Outdoor unit Floor AGYG09 14KVCA Btu class 09 12 14 kW class 2 5 3 5 4 0 AOYG14KBTA2 AOYG18KBTA2 3 1 1 C...

Page 10: ...ion no Unit 1 Unit 2 Total 1 7 7 14 2 7 9 16 3 7 12 19 4 7 14 21 5 9 9 18 6 9 12 21 7 9 14 23 8 12 12 24 9 12 14 26 Numbers in column Unit 1 2 and Total indicate the indoor unit capacities as follows 7 7 000 Btu h 9 9 000 Btu h 12 12 000 Btu h 14 14 000 Btu h 4 1 2 Indoor unit connection patterns 1 Model lineup 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 11: ...es Main1 1 10 Main2 1 10 Pipe type Copper tube Fin type Aluminum Dimensions H W D Net mm 245 570 570 Gross 265 730 625 Weight Net kg 15 Gross 19 Connection pipe Size Liquid mm in Ø6 35 Ø1 4 Gas Ø9 52 Ø3 8 Method Flare Operation range Cooling C 18 to 32 RH 80 or less Heating C 16 to 30 Drain hose Material PVC Size mm VP25 Ø 25 I D Ø 32 O D Cassette grille Grid type Option Model name UTG UFYF W Mate...

Page 12: ...oling dB A 52 54 55 60 Heating 53 56 57 62 Heat exchanger type Dimensions H W D mm 336 490 26 6 Fin pitch mm 1 3 Rows Stages 2 16 Pipe type Copper tube Fin type Aluminum Enclosure Material Steel sheet Color Dimensions H W D Net mm 198 700 450 Gross 250 930 580 Weight Net kg 15 5 Gross 19 0 Connection pipe Size Liquid mm in Ø6 35 Ø1 4 Gas Ø9 52 Ø3 8 Method Flare Operation range Cooling C 18 to 32 R...

Page 13: ... Heat exchanger type Dimensions H W D mm 294 500 26 6 294 500 39 9 Fin pitch mm 1 3 Rows Stages 2 14 3 14 Pipe type Copper tube Fin type Aluminum Enclosure Material Steel sheet Color Dimensions H W D Net mm 198 700 620 Gross 276 968 772 Weight Net kg 16 17 Gross 21 22 Connection pipe Size Liquid mm in Ø6 35 Ø1 4 Gas Ø9 52 Ø3 8 Method Flare Operation range Cooling C 18 to 32 RH 80 or less Heating C...

Page 14: ...1 Sub 1 4 Rows Stages Main1 2 10 Main2 2 7 Main1 2 10 Main2 2 7 Sub 1 4 Pipe type Copper tube Fin type Aluminum Enclosure Material Polystyrene Color White Pearl white painted Approximate color of Munsell N 9 25 Dimensions H W D Net mm 270 834 215 Gross 277 914 332 Weight Net kg 10 0 Gross 12 5 13 0 Connection pipe Size Liquid mm in Ø6 35 Ø1 4 Gas Ø9 52 Ø3 8 Method Flare Drain hose Material PP HDPE...

Page 15: ...ows Stages Main1 2 10 Main2 2 7 Main1 2 10 Main2 2 7 Sub 1 4 Pipe type Copper tube Fin type Aluminum Enclosure Material Polystyrene Color White Pearl white painted Approximate color of Munsell N 9 25 Dimensions H W D Net mm 270 834 222 Gross 277 914 332 Weight Net kg 10 0 Gross 12 5 13 0 Connection pipe Size Liquid mm in Ø6 35 Ø1 4 Gas Ø9 52 Ø3 8 Method Flare Drain hose Material PP HDPE Size mm Ø1...

Page 16: ...Main1 2 10 Main2 2 7 Main1 2 10 Main2 2 7 Sub 1 4 Pipe type Copper tube Fin type Aluminum Enclosure Material Polystyrene Color White Pearl white painted Approximate color of Munsell N 9 25 Dimensions H W D Net mm 270 834 222 Gross 277 914 332 Weight Net kg 10 0 Gross 12 5 13 0 Connection pipe Size Liquid mm in Ø 6 35 Ø 1 4 Gas Ø 9 52 Ø 3 8 Method Flare Drain hose Material PP HDPE Tip diameter mm Ø...

Page 17: ... Main2 2 7 Main1 2 10 Main2 2 7 Sub 1 4 Pipe type Copper tube Fin type Aluminum Enclosure Material Polystyrene Color KETA White Pearl white painted Approximate color of Munsell N 9 25 KETA B Dark Gray Silver painted Approximate color of Munsell 0 5P 3 5 0 2 Dimensions H W D Net mm 295 950 230 Gross 284 1 027 357 Weight Net kg 11 0 11 5 Gross 14 5 15 0 Connection pipe Size Liquid mm in Ø6 35 Ø1 4 G...

Page 18: ... mm 600 740 200 Gross 700 820 310 Weight Net kg 14 Gross 18 Connection pipe Size Liquid mm in Ø6 35 Ø1 4 Gas Ø9 52 Ø3 8 Method Flare Drain hose Material PP LLDPE Tip diameter mm Ø13 8 I D Ø15 8 to Ø16 7 O D Operation range Cooling C 18 to 32 RH 80 or less Heating C 30 or less Remote controller type Wireless Wired Simple mobile app option NOTES Specifications are based on the following conditions C...

Page 19: ...370 540 Hanging bolt position a Ceiling openings 530 530 Hanging bolt position Drain hose A 215 19 30 123 30 262 183 Control Box 146 40 C 620 620 IR receiver Grid type grille View B View C 114 a Ceiling openings Cassette grille Option Grid type mm 580 to 610 13 3 1 Compact cassette type 3 Dimensions 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 20: ...S To set 3 direction optional Air outlet shutter plate UTR YDZB must be installed and the out let direction need to be switched to 3 way by remote controller When installing the indoor unit be careful about the maintenance space In 3 way outlet mode changing of ceiling height setting by function setting 20 is prohibited Ceiling height setting function setting 20 is allowed to be changed only in 4 ...

Page 21: ...mm Drain port 575 174 752 650 43 33 665 700 650 49 49 92 78 169 56 66 85 P 100 6 600 A 295 198 168 150 78 57 10 30 150 182 193 450 30 153 72 52 Rear view Top view Front view Bottom view Side view View A 15 3 2 Mini duct type 3 Dimensions 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 22: ... 5 or more 20 or more 300 or more Air When intaking air from bottom 100 or more Air Maintenance space requirement For future maintenance and service access provide sufficient maintenance space NOTE Do not place any wiring or illumination in the maintenance space as they will impede ser vice Unit mm Top view Service access Air Air Control box 400 or more 100 or more 300 or more Service space More t...

Page 23: ...View A Top view Side view Front view Bottom view Drain hose Drain port 51 574 174 71 152 100 x 6 600 82 48 650 734 30 377 167 119 89 78 55 47 10 620 371 264 144 69 650 664 700 43 20 198 168 151 78 55 Unit mm 17 3 3 Slim duct type 3 Dimensions 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 24: ...no ceiling Floor 240 or more 20 or more 20 or more 300 or more Unit mm Maintenance space requirement For future maintenance and service access provide sufficient maintenance space NOTE Do not place any wiring or illumination in the maintenance space as they will impede ser vice Service access Unit mm Unit Control box Service space 400 or more 300 or more 100 or more 18 3 3 Slim duct type 3 Dimensi...

Page 25: ...12KGTB and ASYG14KGTB Unit mm 834 834 Outline of indoor unit 327 273 273 54 215 3 0 270 270 43 43 9 5 220 for pipe inlet Ø65 for pipe inlet Ø65 182 182 356 346 48 84 63 63 19 3 4 Wall mounted type 3 Dimensions 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 26: ... Unit mm Wall hook bracket Outline of the indoor unit 50 or more 67 or more The flare connection part should be installed outdoors 40 or more 70 or more 107 or more 1 500 or more 1 800 or more 183 or more 20 3 4 Wall mounted type 3 Dimensions 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 27: ...09KMCC ASYG12KMCC and ASYG14KMCC Unit mm 834 Outline of indoor unit 327 273 273 54 270 43 43 9 5 220 for pipe inlet Ø65 for pipe inlet Ø65 182 182 356 346 48 84 63 63 834 270 222 3 0 21 3 4 Wall mounted type 3 Dimensions 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 28: ... Unit mm Wall hook bracket Outline of the indoor unit 50 or more 67 or more The flare connection part should be installed outdoors 40 or more 70 or more 107 or more 1 500 or more 1 800 or more 183 or more 22 3 4 Wall mounted type 3 Dimensions 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 29: ...ETA B ASYG12KETA B and ASYG14KETA B 950 Outline of indoor unit 327 273 273 54 295 43 43 9 5 220 for pipe inlet Ø65 for pipe inlet Ø65 182 182 356 346 106 142 63 63 950 295 230 3 0 Unit mm 23 3 4 Wall mounted type 3 Dimensions 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 30: ... Unit mm Wall hook bracket Outline of the indoor unit 50 or more 67 or more The flare connection part should be installed outdoors 40 or more 40 or more 166 or more 1 500 or more 1 800 or more 211 or more 24 3 4 Wall mounted type 3 Dimensions 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 31: ...GYG12KVCA and AGYG14KVCA 600 200 Side view Front view 740 Unit mm Installation space 100 or more 80 or more 80 or more 150 or below from the floor 50 or more 25 3 5 Floor type 3 Dimensions 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 32: ...arger than X m2 Amount of refrigerant charge M kg Minimum room area X m2 M 1 22 1 22 M 1 23 12 99 1 23 M 1 50 19 31 1 50 M 1 75 26 28 1 75 M 2 0 34 33 2 0 M 2 5 53 63 2 5 M 3 0 77 23 3 0 M 3 5 105 12 3 5 M 4 0 137 29 IEC 60335 2 40 26 3 5 Floor type 3 Dimensions 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 33: ...4 Wiring diagrams 4 1 Compact cassette type Models AUXG07KVLA AUXG09KVLA AUXG12KVLA and AUXG14KVLA 27 4 1 Compact cassette type 4 Wiring diagrams 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 34: ...ls ARXG07KSLAP ARXG09KSLAP ARXG12KSLAP ARXG14KSLAP ARXG07KLLAP ARXG09KLLAP ARXG12KLLAP and ARXG14KLLAP WLAN adapter Converter etc Option 28 4 2 Mini duct type and Slim duct type 4 Wiring diagrams 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 35: ...4 3 Wall mounted type Models ASYG07KGTB ASYG09KGTB ASYG12KGTB and ASYG14KGTB 29 4 3 Wall mounted type 4 Wiring diagrams 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 36: ... Models ASYG07KMTB ASYG09KMTB ASYG12KMTB and ASYG14KMTB 30 4 3 Wall mounted type 4 Wiring diagrams 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 37: ... Models ASYG07KMCC ASYG09KMCC ASYG12KMCC and ASYG14KMCC 31 4 3 Wall mounted type 4 Wiring diagrams 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 38: ... Models ASYG07KETA ASYG09KETA ASYG12KETA ASYG14KETA ASYG07KETA B ASYG09KETA B ASYG12KETA B and ASYG14KETA B 32 4 3 Wall mounted type 4 Wiring diagrams 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 39: ...4 4 Floor type Models AGYG09KVCA AGYG12KVCA and AGYG14KVCA 33 4 4 Floor type 4 Wiring diagrams 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 40: ...ew Vertical airflow direction louver up 2 0 2 0 2 0 2 0 1 0 1 0 1 0 1 0 0 5 0 5 0 5 0 5 0 25 0 25 0 25 0 25 Unit m s 4 3 2 1 0 1 2 3 4 4 3 2 1 0 1 2 3 4 m m Side view Vertical airflow direction louver up 2 0 1 0 0 5 0 5 0 25 0 25 4 3 2 1 0 1 2 3 4 m 0 1 2 2 7 m Unit m s 34 5 1 Compact cassette type 5 Air velocity and temperature distributions 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 41: ... 4 3 2 1 0 1 2 3 4 m 0 1 2 2 7 m 2 5 Unit m s Air temperature distribution Measuring conditions NOTE Reference data Fan speed Operation mode Outlet directions HIGH HEAT 4 way air outlet Side view Vertical airflow direction louver down 30 30 28 28 26 26 24 24 22 22 4 3 2 1 0 1 2 3 4 m 0 1 2 2 7 m 2 5 Unit C 35 5 1 Compact cassette type 5 Air velocity and temperature distributions 2 UNIT MULTI SPLIT...

Page 42: ... 2 0 2 0 2 0 1 0 1 0 1 0 1 0 0 5 0 5 0 5 0 5 0 25 0 25 0 25 0 25 4 3 2 1 0 1 2 3 4 m Unit m s 4 3 2 1 0 1 2 3 4 m Side view Vertical airflow direction louver up 2 0 1 0 0 5 0 5 0 25 0 25 4 3 2 1 0 1 2 3 4 m 0 1 2 2 7 m Unit m s 36 5 1 Compact cassette type 5 Air velocity and temperature distributions 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 43: ... 2 2 7 m 2 5 4 3 2 1 0 1 2 3 4 m Unit m s Air temperature distribution Measuring conditions NOTE Reference data Fan speed Operation mode Outlet directions HIGH HEAT 4 way air outlet Side view Vertical airflow direction louver down 30 30 28 28 26 26 24 24 22 22 0 1 2 2 7 m 2 5 4 3 2 1 0 1 2 3 4 m Unit C 37 5 1 Compact cassette type 5 Air velocity and temperature distributions 2 UNIT MULTI SPLIT TYP...

Page 44: ...r up 1 0 5 0 5 1 2 0 25 0 25 1 0 25 2 0 25 0 5 2 0 5 1 2 4 3 2 1 0 1 2 3 4 m Unit m s 4 3 2 1 0 1 2 3 4 m Side view Vertical airflow direction louver up 0 25 0 25 0 5 0 5 1 1 2 2 4 3 2 1 0 1 2 3 4 m 0 1 2 2 7 m Unit m s 38 5 1 Compact cassette type 5 Air velocity and temperature distributions 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 45: ...1 2 2 7 m 2 5 4 3 2 1 0 1 2 3 4 m Unit m s Air temperature distribution Measuring conditions NOTE Reference data Fan speed Operation mode Outlet directions HIGH HEAT 4 way air outlet Side view Vertical airflow direction louver down 22 24 26 28 30 0 1 2 2 7 m 2 5 4 3 2 1 0 1 2 3 4 m Unit C 39 5 1 Compact cassette type 5 Air velocity and temperature distributions 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI...

Page 46: ...r 2 1 0 1 2 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 1 0 5 Top view Vertical airflow direction louver Up Horizontal airflow direction louver Left Right 2 1 0 1 2 m m Unit m s 0 1 2 3 4 5 6 7 5 4 3 8 9 10 5 4 3 2 1 0 5 2 1 0 5 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 1 0 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 1 0 5 2 40 5 2 Mini duct type 5 Air vel...

Page 47: ... m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 2 1 0 5 Air temperature distribution Measuring conditions Fan speed Operation mode HIGH HEAT Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 2 1 0 m Unit C m 0 1 2 3 4 5 6 7 8 9 2 5 3 10 30 28 26 24 22 41 5 2 Mini duct type 5 Air velocity and temperature distributions 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 48: ... 2 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 1 0 5 Top view Vertical airflow direction louver Up Horizontal airflow direction louver Left Right 2 1 0 1 2 m m Unit m s 0 1 2 3 4 5 6 7 5 4 3 8 9 10 5 4 3 2 1 0 5 2 1 0 5 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 1 0 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 1 0 5 2 42 5 2 Mini duct type 5 Air velocity and...

Page 49: ... m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 2 1 0 5 Air temperature distribution Measuring conditions Fan speed Operation mode HIGH HEAT Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 2 1 0 m Unit C m 0 1 2 3 4 5 6 7 8 9 2 5 3 10 30 28 26 24 22 43 5 2 Mini duct type 5 Air velocity and temperature distributions 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 50: ... 2 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 1 0 5 Top view Vertical airflow direction louver Up Horizontal airflow direction louver Left Right 2 1 0 1 2 m m Unit m s 0 1 2 3 4 5 6 7 5 4 3 8 9 10 5 4 3 2 1 0 5 2 1 0 5 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 1 0 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 1 0 5 2 44 5 2 Mini duct type 5 Air velocity and...

Page 51: ...3 4 5 6 7 8 9 10 2 5 3 2 1 0 5 Unit m s Air temperature distribution Measuring conditions Fan speed Operation mode HIGH HEAT Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 2 1 0 m Unit C m 0 1 2 3 4 5 6 7 8 9 2 5 3 10 30 28 26 24 22 45 5 2 Mini duct type 5 Air velocity and temperature distributions 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 52: ... 2 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 1 0 5 Top view Vertical airflow direction louver Up Horizontal airflow direction louver Left Right 2 1 0 1 2 m m Unit m s 0 1 2 3 4 5 6 7 5 4 3 8 9 10 5 4 3 2 1 0 5 2 1 0 5 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 1 0 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 1 0 5 2 46 5 2 Mini duct type 5 Air velocity and...

Page 53: ... m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 2 1 0 5 Air temperature distribution Measuring conditions Fan speed Operation mode HIGH HEAT Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 2 1 0 m Unit C m 0 1 2 3 4 5 6 7 8 9 2 5 3 10 30 28 26 24 22 47 5 2 Mini duct type 5 Air velocity and temperature distributions 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 54: ...r 2 1 0 1 2 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 1 0 5 Top view Vertical airflow direction louver Up Horizontal airflow direction louver Left Right 2 1 0 1 2 m m Unit m s 0 1 2 3 4 5 6 7 5 4 3 8 9 10 5 4 3 2 1 0 5 2 1 0 5 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 1 0 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 1 0 5 2 48 5 3 Slim duct type 5 Air vel...

Page 55: ... m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 2 1 0 5 Air temperature distribution Measuring conditions Fan speed Operation mode HIGH HEAT Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 2 1 0 m Unit C m 0 1 2 3 4 5 6 7 8 9 2 5 3 10 30 28 26 24 22 49 5 3 Slim duct type 5 Air velocity and temperature distributions 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 56: ... 2 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 1 0 5 Top view Vertical airflow direction louver Up Horizontal airflow direction louver Left Right 2 1 0 1 2 m m Unit m s 0 1 2 3 4 5 6 7 5 4 3 8 9 10 5 4 3 2 1 0 5 2 1 0 5 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 1 0 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 1 0 5 2 50 5 3 Slim duct type 5 Air velocity and...

Page 57: ... m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 2 1 0 5 Air temperature distribution Measuring conditions Fan speed Operation mode HIGH HEAT Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 2 1 0 m Unit C m 0 1 2 3 4 5 6 7 8 9 2 5 3 10 30 28 26 24 22 51 5 3 Slim duct type 5 Air velocity and temperature distributions 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 58: ... 2 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 1 0 5 Top view Vertical airflow direction louver Up Horizontal airflow direction louver Left Right 2 1 0 1 2 m m Unit m s 0 1 2 3 4 5 6 7 5 4 3 8 9 10 5 4 3 2 1 0 5 2 1 0 5 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 1 0 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 1 0 5 2 52 5 3 Slim duct type 5 Air velocity and...

Page 59: ...3 4 5 6 7 8 9 10 2 5 3 2 1 0 5 Unit m s Air temperature distribution Measuring conditions Fan speed Operation mode HIGH HEAT Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 2 1 0 m Unit C m 0 1 2 3 4 5 6 7 8 9 2 5 3 10 30 28 26 24 22 53 5 3 Slim duct type 5 Air velocity and temperature distributions 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 60: ... 2 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 1 0 5 Top view Vertical airflow direction louver Up Horizontal airflow direction louver Left Right 2 1 0 1 2 m m Unit m s 0 1 2 3 4 5 6 7 5 4 3 8 9 10 5 4 3 2 1 0 5 2 1 0 5 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 1 0 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 1 0 5 2 54 5 3 Slim duct type 5 Air velocity and...

Page 61: ... m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 2 1 0 5 Air temperature distribution Measuring conditions Fan speed Operation mode HIGH HEAT Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 2 1 0 m Unit C m 0 1 2 3 4 5 6 7 8 9 2 5 3 10 30 28 26 24 22 55 5 3 Slim duct type 5 Air velocity and temperature distributions 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 62: ...7 8 9 10 Top view Vertical airflow direction louver Up Horizontal airflow direction louver Left Right 2 0 2 0 1 0 1 0 0 5 0 5 Unit m s m m 3 2 1 0 1 2 3 0 1 2 3 4 5 6 7 8 9 10 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center m m 3 2 1 0 0 1 2 3 4 5 6 7 8 9 10 Unit m s 2 0 0 5 1 0 Side view Vertical airflow direction louver Down Horizontal airflow direction ...

Page 63: ...orizontal airflow direction louver Left Right 1 0 1 0 0 5 0 5 2 0 2 0 Unit m s m m 3 2 1 0 1 2 3 0 1 2 3 4 5 6 7 8 9 10 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 0 0 5 1 0 m m 3 2 1 0 0 1 2 3 4 5 6 7 8 9 10 Unit m s Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 0 5 0 5 2 0 1 0 m m 3 2 1 0 0 1 2 3 4 5 6 ...

Page 64: ...tical airflow direction louver Up Horizontal airflow direction louver Left Right 1 0 0 5 1 0 0 5 Unit m s 2 1 0 1 2 m m 1 2 3 4 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 1 0 0 5 3 2 1 0 Unit m s m m 1 2 3 4 Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 1 0 0 5 3 2 1 0 m m 1 2 3 4 Unit m s 58 5 5 Floor typ...

Page 65: ... 03 upper limit SP mode 03 lower limit Normal SP upper limit Quiet Normal SP Hi Normal SP Hi SP mode 00 SP mode 00 upper limit 60 50 40 30 20 10 0 300 External static pressure Pa Airflow m3 h 400 500 600 700 1 Available airflow rate range when Auto louver grille option is installed Fan speed HIGH Vertical airflow direction louver Up Available airflow rate range High level 1 Hi SP mode 00 Hi Normal...

Page 66: ...g 300 400 500 700 600 Airflow m3 h 0 20 40 60 80 100 140 120 Capacity Capacity Heating 0 20 40 60 80 100 120 140 300 400 500 700 600 Capacity Airflow m3 h Capacity 60 6 1 Mini duct type 6 Fan performance 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 67: ...ormal SP Hi SP mode 00 SP mode 00 upper limit 1 Available airflow rate range when Auto louver grille option is installed Fan speed HIGH Vertical airflow direction louver Up 60 50 40 30 20 10 0 300 External static pressure Pa Airflow m3 h 400 500 600 700 Available airflow rate range High level 1 Hi SP mode 00 Hi Normal SP Hi SP mode 02 Hi SP mode 03 61 6 1 Mini duct type 6 Fan performance 2 UNIT MU...

Page 68: ...g 300 400 500 700 600 Airflow m3 h 0 20 40 60 80 100 140 120 Capacity Capacity Heating 0 20 40 60 80 100 120 140 300 400 500 700 600 Capacity Airflow m3 h Capacity 62 6 1 Mini duct type 6 Fan performance 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 69: ... mode 00 SP mode 00 upper limit Hi SP mode 00 60 50 40 30 20 10 0 300 400 500 600 800 External static pressure Pa Airflow m3 h Available airflow rate range High level 1 700 1 Available airflow rate range when Auto louver grille option is installed Fan speed HIGH Vertical airflow direction louver Up Hi SP mode 03 Hi Normal SP Hi SP mode 02 Hi SP mode 00 63 6 1 Mini duct type 6 Fan performance 2 UNI...

Page 70: ...pacity 800 500 400 700 600 Airflow m3 h 300 0 20 40 60 80 100 140 Capacity 120 Heating 300 500 600 800 700 Airflow m3 h 400 0 20 40 60 80 100 120 Capacity 140 Capacity 64 6 1 Mini duct type 6 Fan performance 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 71: ...ode 00 Quiet SP mode 00 80 70 60 50 40 30 20 10 0 External static pressure Pa 300 400 500 600 700 Airflow m3 h 800 900 1 Available airflow rate range when Auto louver grille option is installed Fan speed HIGH Vertical airflow direction louver Up Hi SP mode 01 Hi SP mode 05 Hi SP mode 04 Hi SP mode 03 Hi Normal SP Hi SP mode 02 Hi SP mode 00 Available airflow rate range High level 1 65 6 1 Mini duc...

Page 72: ...0 60 80 100 120 Capacity 140 500 600 700 900 800 Airflow m3 h 400 300 Capacity Heating 0 20 40 60 80 100 120 Capacity 140 500 600 700 900 800 Airflow m3 h 400 300 Capacity 66 6 1 Mini duct type 6 Fan performance 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 73: ... SP lower limited 110 100 90 80 70 60 50 40 30 20 10 0 300 External static pressure Pa Airflow m3 h 400 500 600 700 1 Available airflow rate range when Auto louver grille option is installed Fan speed HIGH Vertical airflow direction louver Up Hi SP mode 09 Hi SP mode 08 Hi SP mode 07 Hi SP mode 06 Hi SP mode 05 Hi SP mode 04 Hi SP mode 03 Hi Normal SP Hi SP mode 02 Hi SP mode 01 Hi SP mode 00 Avai...

Page 74: ...oling 0 20 40 60 80 100 120 400 500 600 800 700 Capacity Capacity Airflow m3 h Heating 0 20 40 60 80 100 120 400 500 600 800 700 Capacity Capacity Airflow m3 h 68 6 2 Slim duct type 6 Fan performance 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 75: ... 100 90 80 70 60 50 40 30 20 10 0 300 External static pressure Pa Airflow m3 h Hi SP mode 09 Hi SP mode 08 Hi SP mode 07 Hi SP mode 06 Hi SP mode 05 Hi SP mode 04 Hi SP mode 03 Hi Normal SP Hi SP mode 02 Hi SP mode 01 Hi SP mode 00 Available airflow rate range High level 1 400 500 600 800 700 1 Available airflow rate range when Auto louver grille option is installed Fan speed HIGH Vertical airflow...

Page 76: ...oling 0 20 40 60 80 100 120 400 500 600 800 700 Capacity Capacity Airflow m3 h Heating 0 20 40 60 80 100 120 400 500 600 800 700 Capacity Capacity Airflow m3 h 70 6 2 Slim duct type 6 Fan performance 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 77: ... 100 90 80 70 60 50 40 30 20 10 0 300 400 500 600 800 External static pressure Pa Airflow m3 h Hi SP mode 09 Hi SP mode 08 Hi SP mode 07 Hi SP mode 06 Hi SP mode 05 Hi SP mode 04 Hi SP mode 03 Hi Normal SP Hi SP mode 02 Hi SP mode 01 Hi SP mode 00 Available airflow rate range High level 1 700 1 Available airflow rate range when Auto louver grille option is installed Fan speed HIGH Vertical airflow...

Page 78: ...oling 0 20 40 60 80 100 120 900 500 600 800 700 Capacity Capacity Airflow m3 h Heating 900 0 20 40 60 80 100 120 500 600 800 700 Capacity Capacity Airflow m3 h 72 6 2 Slim duct type 6 Fan performance 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 79: ...100 90 80 70 60 50 40 30 20 10 0 300 400 500 600 700 External static pressure Pa Airflow m3 h 800 900 1 000 120 1 Available airflow rate range when Auto louver grille option is installed Fan speed HIGH Vertical airflow direction louver Up Hi SP mode 09 Hi SP mode 08 Hi SP mode 07 Hi SP mode 06 Hi SP mode 05 Hi SP mode 04 Hi SP mode 03 Hi Normal SP Hi SP mode 02 Hi SP mode 01 Hi SP mode 00 Availabl...

Page 80: ...ing 0 20 40 60 80 100 120 1 000 600 700 900 800 Capacity Capacity Airflow m3 h Heating 0 20 40 60 80 100 120 1 000 600 700 900 800 Capacity Capacity Airflow m3 h 74 6 2 Slim duct type 6 Fan performance 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 81: ...igh 540 150 318 Med 490 136 288 Low 440 122 259 Quiet 390 108 230 AUXG12KVLA Cooling High 610 169 359 Med 530 147 312 Low 470 131 277 Quiet 410 114 241 Heating High 610 169 359 Med 530 147 312 Low 470 131 277 Quiet 410 114 241 AUXG14KVLA Cooling High 680 189 400 Med 580 161 341 Low 490 136 288 Quiet 410 114 241 Heating High 790 219 465 Med 680 189 400 Low 580 161 341 Quiet 450 125 265 75 7 1 Compa...

Page 82: ...235 Quiet 360 100 212 Heating High 600 167 353 Med 450 125 265 Low 400 111 235 Quiet 360 100 212 ARXG12KSLAP Cooling High 650 181 383 Med 490 136 288 Low 430 119 253 Quiet 360 100 212 Heating High 650 181 383 Med 490 136 288 Low 430 119 253 Quiet 360 100 212 ARXG14KSLAP Cooling High 800 222 471 Med 640 178 377 Low 530 147 312 Quiet 360 100 212 Heating High 800 222 471 Med 640 178 377 Low 530 147 3...

Page 83: ...294 Quiet 450 125 265 Heating High 600 167 353 Med 550 153 324 Low 500 139 294 Quiet 450 125 265 ARXG12KLLAP Cooling High 650 181 383 Med 600 167 353 Low 550 153 324 Quiet 480 133 283 Heating High 650 181 383 Med 600 167 353 Low 550 153 324 Quiet 480 133 283 ARXG14KLLAP Cooling High 800 222 471 Med 700 194 412 Low 600 167 353 Quiet 480 133 283 Heating High 800 222 471 Med 700 194 412 Low 600 167 3...

Page 84: ...9 253 Quiet 270 75 159 Heating High 770 214 453 Med 640 178 377 Low 520 144 306 Quiet 330 92 194 ASYG14KGTB Cooling High 770 214 453 Med 600 167 353 Low 450 125 265 Quiet 280 78 165 Heating High 800 222 471 Med 660 183 388 Low 520 144 306 Quiet 340 94 200 ASYG07KMTB Cooling High 650 181 383 Med 540 150 318 Low 430 119 253 Quiet 270 75 159 Heating High 720 200 424 Med 580 161 341 Low 460 128 271 Qu...

Page 85: ... 320 89 188 Heating High 720 200 424 Med 580 161 341 Low 460 128 271 Quiet 330 92 194 ASYG09KMCC Cooling High 700 194 412 Med 560 156 330 Low 430 119 253 Quiet 320 89 188 Heating High 750 208 441 Med 610 169 359 Low 470 131 277 Quiet 330 92 194 ASYG12KMCC Cooling High 700 194 412 Med 560 156 330 Low 430 119 253 Quiet 320 89 188 Heating High 780 217 459 Med 640 178 377 Low 520 144 306 Quiet 330 92 ...

Page 86: ... 270 75 159 Heating High 750 208 441 Med 610 169 359 Low 470 131 277 Quiet 330 92 194 ASYG12KETA ASYG12KETA B Cooling High 700 194 412 Med 560 156 330 Low 430 119 253 Quiet 270 75 159 Heating High 770 214 453 Med 640 178 377 Low 520 144 306 Quiet 330 92 194 ASYG14KETA ASYG14KETA B Cooling High 770 214 453 Med 600 167 353 Low 450 125 265 Quiet 280 78 165 Heating High 800 222 471 Med 660 183 388 Low...

Page 87: ...Quiet 270 75 159 AGYG12KVCA Cooling High 600 167 353 Med 490 136 288 Low 380 106 224 Quiet 270 75 159 Heating High 600 167 353 Med 510 142 300 Low 410 114 241 Quiet 270 75 159 AGYG14KVCA Cooling High 650 181 383 Med 520 144 306 Low 400 131 277 Quiet 270 75 159 Heating High 650 181 383 Med 540 150 318 Low 430 119 253 Quiet 270 75 159 81 7 5 Floor type 7 Airflow 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI ...

Page 88: ...C 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 HIGH QUIET Model AUXG09KVLA Cooling Octave band sound pressure level dB 0 dB 0 00020 μbar Octave band center frequency Hz 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 HIGH QUIET Heating Octave band sound pressure level dB 0 dB 0 00020 μbar Octave ba...

Page 89: ...NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 HIGH QUIET Model AUXG14KVLA Cooling Octave band sound pressure level dB 0 dB 0 00020 μbar Octave band center frequency Hz 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 HIGH QUIET Heating Octave band sound pressure level dB 0 dB 0 00020 μbar Octave band center frequency Hz ...

Page 90: ... NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 HIGH QUIET Model ARXG09KSLAP Cooling 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 Octave band sound pressure level dB 0 dB 0 00020 μbar Octave band center frequency Hz HIGH QUIET NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 Heating NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 HIGH Q...

Page 91: ...30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 Model ARXG14KSLAP Cooling 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 Octave band sound pressure level dB 0dB 0 00020 μbar Octave band center frequency Hz QUIET HIGH NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Heating 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 Octave band sound...

Page 92: ...0 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 HIGH QUIET Model ARXG09KLLAP Cooling NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 QUIET HIGH Heating NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Octave...

Page 93: ... 10 0 63 125 250 500 1 000 2 000 4 000 8 000 HIGH QUIET Model ARXG14KLLAP Cooling 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 Octave band sound pressure level dB 0 dB 0 00020 μbar Octave band center frequency Hz NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 HIGH QUIET Heating 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 Octave band sound...

Page 94: ... NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH QUIET Model ASYG09KGTB Cooling Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH QUIET Heating Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center fr...

Page 95: ...0 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH QUIET Model ASYG14KGTB Cooling Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH QUIET Heating Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz ...

Page 96: ...0 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH QUIET Models ASYG09KMTB ASYG09KMCC ASYG09KETA and ASYG09KETA B Cooling Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 QUIET HIGH Heating Octave band sound pressure level dB 0 dB 0 00...

Page 97: ...0 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH QUIET Models ASYG14KMTB ASYG14KMCC ASYG14KETA and ASYG14KETA B Cooling Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH QUIET Heating Octave band sound pressure level dB 0 dB 0 00...

Page 98: ...NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 QUIET Model AGYG12KVCA Cooling Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 HIGH NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 QUIET Heating Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center fr...

Page 99: ... NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 QUIET Heating Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 HIGH NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 QUIET 93 8 5 Floor type 8 Noise level curve 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 100: ...8 6 Sound level check point Compact cassette type Microphone Microphone 1 5 m 94 8 6 Sound level check point 8 Noise level curve 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 101: ... Side view 1 5 m 2 m 1 m Microphone Measuring duct Measuring duct Microphone Set the static pressure as rating in this area Wall mounted type 0 8 m 1 m Microphone Microphone NOTE Detailed shape of the actual indoor unit might be slightly different from the one illustrated above 95 8 6 Sound level check point 8 Noise level curve 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 102: ... Floor type Microphone Microphone 1m 1m Airflow Airflow 96 8 6 Sound level check point 8 Noise level curve 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 103: ...35 ARXG14KLLAP 0 64 76 0 51 Wall mounted ASYG07KGTB 0 25 23 0 20 ASYG09KGTB 0 30 27 0 24 ASYG12KGTB 0 30 27 0 24 ASYG14KGTB 0 37 33 0 29 ASYG07KMTB 0 25 23 0 20 ASYG09KMTB 0 30 27 0 24 ASYG12KMTB 0 30 27 0 24 ASYG14KMTB 0 38 33 0 30 ASYG07KMCC 0 25 23 0 20 ASYG09KMCC 0 30 27 0 24 ASYG12KMCC 0 30 27 0 24 ASYG14KMCC 0 38 33 0 30 ASYG07KETA ASYG07KETA B 0 25 23 0 20 ASYG09KETA ASYG09KETA B 0 30 27 0 ...

Page 104: ... Off ASYG09KGTB ASYG12KGTB Activate 125 10 C Fan motor stop Reset 100 10 C Fan motor restart ASYG14KGTB ASYG07KMTB Activate More than 95 C Fan motor speed down Reset 95 C or less Fan motor speed recover ASYG09KMTB ASYG12KMTB ASYG14KMTB Activate 125 10 C Fan motor stop Reset 100 10 C Fan motor restart ASYG07KMCC Activate 170 25 30 C Fan motor stop Reset 145 25 30 C Fan motor restart ASYG09KMCC ASYG...

Page 105: ...im duct types CN47 Ext out Terminal Ext in Indoor unit PCB External input and output Connector Input select Input signal External connect kit Optional parts External input Operation Stop Forced stop Terminal Dry contact Edge External output Operation status CN47 UTY XWZXZG Error status Indoor unit fan operation status External heater output 99 11 1 Compact cassette Mini duct and Slim duct types 11...

Page 106: ...t Use an external output cable with appropriate external dimension depending on the number of ca bles to be installed A twisted pair cable 22AWG should be used Maximum length of cable is 25 m Output voltage High DC 12 V 2 V Low 0 V Permissible current 50 mA For details refer to Combination of external input and output on page 101 When indicator etc are connected directly Example Function setting 6...

Page 107: ...ibited 9 60 09 Operation Stop Error status 10 60 10 Operation Stop Indoor unit fan operation status 11 60 11 Operation Stop External heater output NOTE Input of Operation Stop depends on the setting of function setting 46 00 Operation Stop mode 1 R C enabled 01 Setting prohibited 02 Forced stop 03 Operation Stop mode 2 R C disabled Input signal type Indoor unit Input signal type is only Edge Edge ...

Page 108: ...ced stop mode Function setting External input Input signal Command 46 02 Terminal Off On Forced stop On Off Normal On Off Forced stop Normal Operation Stop Remote controller On On Indoor unit On Input NOTES When the forced stop is triggered indoor unit stops and Operation Stop operation by the re mote controller is restricted When forced stop function is used with forming a remote controller group...

Page 109: ...it within the group Control output function Function setting External output Output signal Command 60 00 CN47 Low High Operation High Low Stop The output is low when the unit is stopped Operation Stop High Low CN47 Indoor unit Error status Function setting External output Output signal Command 60 09 CN47 Low High Error High Low Normal The output is ON when an error is generated for the indoor unit...

Page 110: ...gram of heating temperature Off On High Low Heater turns off as shown in diagram of heating temperature Other than Heating mode Error occurred On Off Forced thermo off Fan stop protection Specifications of the signal output performance are as shown as follows Example When set temperature Ts is set at 22 C And room temperature Tr increase above 12 C signal output is on And Tr increase above 21 C si...

Page 111: ...nput and output UTY XCSXZ2 Operation Stop CN313 CN314 Dry contact Apply voltage Edge Pulse Forced stop Forced thermostat off CN313 Edge Operation status CN310 Error status CN311 Indoor unit fan operation status CN312 NOTE KETA KETA B External input and output PCB cannot be used with Wireless LAN adapter simultaneously 105 11 2 Wall mounted type Models ASYG07KGTB ASYG09KGTB ASYG12KGTB ASYG14KGTB AS...

Page 112: ...t In case of internal power supply set the slide switch of SW301 to NON VOL side 1 2 3 Input 1 PCB Connected unit 1 2 3 Input 2 Connector CN313 Connector CN314 1 The switches can be used on the following condition DC 12 V to 24 V 1 mA to 15 mA Apply voltage In case of external power supply set the slide switch of SW301 to VOL side 1 2 3 Input 1 Power supply PCB Connected unit 2 1 2 3 Input 2 Conne...

Page 113: ...n status PCB Resistor Connected unit 1 2 Connector CN311 LED 2 Error status Resistor 1 2 Connector CN312 LED 3 Indoor unit fan operation status Resistor When connecting with a device equipped with a power supply Example Function setting 60 is set to 00 1 2 Connected device 1 Connector CN310 PCB Connected unit Relay Operation status 1 2 Connected device 2 Connector CN311 Error status 1 2 Connected ...

Page 114: ...etting External input and output PCB Rotary SW External output External input and output PCB CN310 CN311 CN312 0 1 60 00 1 Operation Stop Error status Indoor unit fan operation status 0 2 60 00 2 Error status Indoor unit fan operation status Not available 1 8 60 01 to 60 08 3 9 A Setting prohibited 9 60 09 B Operation Stop Indoor unit fan operation status Not available 10 60 10 C Operation Stop Er...

Page 115: ...2 on the External input and out put PCB Pulse The width of pulse must be longer than 200 msec Edge 109 11 2 Wall mounted type Models ASYG07KGTB ASYG09KGTB ASYG12KGTB ASYG14KGTB ASYG07KETA ASYG09KETA ASYG12KETA ASYG14KETA ASYG07KETA B ASYG09KETA B ASYG12KETA B and ASYG14KETA B 11 External input and output 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 116: ...y SW on External input and output PCB External input Input signal Command 46 00 60 00 1 External input and output PCB CN313 Pulse Operation CN314 Pulse Stop On On Off Operation Stop Remote controller On Off Indoor unit CN313 CN314 NOTES The last command has priority The indoor units within the same remote controller group operates in the same mode 110 11 2 Wall mounted type Models ASYG07KGTB ASYG0...

Page 117: ... input and output PCB CN313 Pulse Forced stop CN314 Pulse Normal On Off Operation Stop Remote controller On Off Forced stop Normal CN313 CN314 On On On Indoorunit NOTES When the forced stop is triggered indoor unit stops and Operation Stop operation by the re mote controller is restricted When forced stop function is used with forming a remote controller group connect the same equipment to each in...

Page 118: ...xternal input Input signal Command 46 03 60 00 1 External input and output PCB CN313 Pulse Operation CN314 Pulse Stop R C disabled On On Off Operation Stop Remote controller On Off Indoor unit CN313 CN314 R C disabled Off On NOTE When Operation Stop mode 2 function is used with forming a remote controller group connect the same equipment to each indoor unit within the group 112 11 2 Wall mounted t...

Page 119: ...ff On Off Compressor Room temp Set temp Input NOTE When the signal is received from another unit on the refrigerant circuit there may be a de lay in thermostat off function at the unit 113 11 2 Wall mounted type Models ASYG07KGTB ASYG09KGTB ASYG12KGTB ASYG14KGTB ASYG07KETA ASYG09KETA ASYG12KETA ASYG14KETA ASYG07KETA B ASYG09KETA B ASYG12KETA B and ASYG14KETA B 11 External input and output 2 UNIT M...

Page 120: ...door unit Error Normal On Off CN311 312 Indoor unit Indoor unit fan operation status Function setting Rotary SW on External input and output PCB External output Output signal Command 60 00 1 External input and output PCB CN312 Off On Fan run On Off Fan stop Output signal Condition On The indoor unit fan is operating Low High Off The fan is stopped or during cold air prevention High Low During ther...

Page 121: ...n should be separate from the power cable line Control input Operation Stop or Forced stop The air conditioner can be remotely operated by means of the following on site work Unit operation is started at the following contents by adding the contact input of a commercial on off switch to a connector on the external control PCB and turning it on Unit operation Initial setting after power is on Start...

Page 122: ...top mode Remote controller On On On Input signal Indoor unit Command Remote control operation invalidity On Off Operation Stop Forced stop Normal When function setting is Operation Stop mode 2 On Input Off Operation Indoor unit Stop R C disabled Remote controller On On Off NOTE When Operation Stop mode 2 function is used with forming a remote controller group connect the same equipment to each ind...

Page 123: ...For operating the external function the wall mounted type requires the communication kit in addi tion to the wire UTY XWZXZ5 117 11 3 Wall mounted type Models ASYG07KMTB ASYG09KMTB ASYG12KMTB ASYG14KMTB ASYG07KMCC ASYG09KMCC ASYG12KMCC and ASYG14KMCC 11 External input and output 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 124: ...r supply V Connector 10 m DC 24 V Make the distance from the PCB to the connected unit within 10 m Relay spec Max DC 24 V 10 mA to less than 500 mA On Off Operation Stop Indoor unit Output signal Optional part Part name Model name Exterior External connect kit UTY XWZXZ5 External output wire Communication kit UTY TWBXF2 For operating the external function the wall mounted type requires the communi...

Page 125: ...y spec Max DC 24 V 10 mA to less than 500 mA On Off Error Normal Error status Output signal Optional part Part name Model name Exterior External connect kit UTY XWZXZ5 External output wire Communication kit UTY TWBXF2 For operating the external function the wall mounted type requires the communication kit in addi tion to the wire UTY XWZXZ5 119 11 3 Wall mounted type Models ASYG07KMTB ASYG09KMTB A...

Page 126: ...his product can be controlled from an external device Operation Stop mode can be selected with function setting of indoor unit A twisted pair cable 22AWG should be used Maximum length of cable is 150 m The wire connection should be separate from the power cable line Indoor unit Indoor unit functions such as Operation Stop can be done by using indoor unit connectors 1 2 3 Connector CN14 CN15 PCB Co...

Page 127: ... 11 4 3 Combination of external input and output on page 122 When indicator or other components are connected directly Example Function setting 60 is set to 00 1 2 Connector CN20 CN21 CN22 CN23 LED PCB Resistor Connected unit When connecting with a device equipped with a power supply Example Function setting 60 is set to 00 1 2 Connected device Connector CN20 CN21 CN22 CN23 PCB Connected unit Rela...

Page 128: ... unit CN20 CN21 CN22 CN23 0 60 00 Operation Stop Error status Indoor unit fan operation status External heater output 9 60 09 Error status Operation Stop Indoor unit fan operation status External heater output 10 60 10 Indoor unit fan operation status Operation Stop Error status External heater output 11 60 11 External heater output Operation Stop Indoor unit fan operation status Error status NOTE...

Page 129: ... Operation Stop Remote controller On Off Indoor unit On CN15 When function setting is Forced stop mode In the case of Edge input Mode Function setting External input Input signal Command 0 46 02 Input of indoor unit CN14 Off On Forced stop On Off Normal 60 00 CN15 Off On Forced stop On Off Normal On Off Forced stop Normal Operation Stop Remote controller On On Indoor unit On CN15 123 11 4 Floor ty...

Page 130: ...signal Command 0 46 03 Input of indoor unit CN14 Off On Operation On Off Stop R C disabled 60 00 CN15 Off On Operation On Off Stop R C disabled On CN15 Off Operation Indoor unit Stop R C disabled Remote contoller On On Off 124 11 4 Floor type 11 External input and output 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 131: ... stopped Operation Stop High Low CN15 On Off CN20 Indoor unit Error status Mode Function setting External output Output signal Command 9 60 09 Output of indoor unit CN15 Low High Error High Low Normal 0 60 00 CN21 Off On Error On Off Normal The output is ON when an error is generated for the indoor unit Error Normal High Low CN15 On Off CN21 Indoor unit 125 11 4 Floor type 11 External input and ou...

Page 132: ...xternal factor such as the outdoor temperature change signal is output to tell the attainment status of set point Mode Function setting External output Output signal Command 12 60 12 Outputof indoor unit CN15 On Off Normal Off On Set point attainment Output signal Condition Off Reached the set point Tr Tsα 0 5 C On Unreached the set point Tr Tsα 2 5 C However even if the set point unreached the si...

Page 133: ...r heating device On Off ON OFF Example of heating device Floor heating device WARNING Design and install external heater appropriately with considering its protection Inappropriate designing and installation of external heater may cause a fire by emitted heat from the external heater Fujitsu General Ltd is not responsible for inappropriate designing or installation of external heating device 127 1...

Page 134: ...r Ts 1 C Tr Ts Tr Ts Thon 3 C Tr Ts 10 C Tr Ts 12 C Tr Room temperature Ts Set temperature Thon Heater on temperature Tr Ts 1 C Tr Ts Tr Ts Thon 3 C Tr Ts 12 C Tr Room temperature Ts Set temperature Thon Heater on temperature Off Off On A Tr Ts 10 C When room temperature stays in this zone for a specific time auxiliary heater is turned on For details refer to function number 71 Example When set te...

Page 135: ...ing group control system some functions may no longer be available 1 Connect up to 16 indoor units in a system A B C D E I U I U I U I U Remote controller A B C D E Remote controller cable Wiring length limitation A B C D E 500 m Example of wiring method 1 2 R W Remote controller cable Bus wire Remote controller Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4 Example of wiring method 1 2 R...

Page 136: ... Refer to Remote con troller address setting in Contents of function setting on page 203 NOTES Do not use the same setting value Setting is reflected after the power is turned on again Also set the R C address for the remote controller For details refer to the remote controller installation manual NOTE In manual setting connect up to 15 indoor units in a system RC AD 01 RC AD 02 RC AD 03 RC AD 04 ...

Page 137: ...ton ON OFF button SLEEP button MODE button FAN button RESET button CLOCK ADJUST button TEST RUN button ECONOMY button NOTE Functions may differ by type of the indoor unit For details refer to the operation manual Display panel Mode indicator LOW NOISE mode indicator Clock and Timer indicator SEND indicator Temperature indicator Fan speed indicator Swing indicator Transmit indicator 131 13 1 Wirele...

Page 138: ...ton FAN button RESET button CLOCK ADJUST button TEST RUN button ECONOMY button NOTE Functions may differ by type of the indoor unit For details refer to the operation manual Display panel Mode indicator LOW NOISE mode indicator Clock and Timer indicator SEND indicator Temperature indicator Fan speed indicator Swing indicator Transmit indicator To facilitate explanation the accompanying illustratio...

Page 139: ...or unit For details refer to the operation manual Display panel Mode indicator Clock and Timer indicator LOW NOISE mode indicator Transmit indicator Temperature indicator Fan speed indicator Swing indicator To facilitate explanation the accompanying illustration has been drawn to show all possible indicators in actual operation however the display will only show those indicators appropriate to the...

Page 140: ...t g 124 without batteries Holder Unit mm 48 5 5 5 26 2 69 3 6 5 Front View Side View Bottom View Ø 3 5 Hole 150 106 8 Hole 3 5 2 R Size H W D mm 150 69 3 26 2 Weight g 27 134 13 1 Wireless remote controller AR REW4E AR REM4E and AR REB1E 13 Remote controller 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 141: ...E Functions may differ by type of the indoor unit For details refer to the operation manual Display panel Mode indicator Clock and Timer indicator SEND indicator Temperature indicator Fan speed indicator Swing indicator Transmit indicator LOW NOISE mode indicator To facilitate explanation the accompanying illustration has been drawn to show all possible indicators in actual operation however the d...

Page 142: ...61 17 Weight g 124 without batteries Holder Unit mm 48 5 5 5 26 2 69 3 6 5 Front View Side View Bottom View Ø 3 5 Hole 150 106 8 Hole 3 5 2 R Size H W D mm 150 69 3 26 2 Weight g 27 136 13 2 Wireless remote controller AR REM7E 13 Remote controller 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 143: ...s may differ by type of the indoor unit For details refer to the operation manual Display panel Mode indicator Clock and Timer indicator Fan speed indicator Swing indicator Temperature indicator Transmit indicator To facilitate explanation the accompanying illustration has been drawn to show all possible indicators in actual operation however the display will only show those indicators appropriate...

Page 144: ...eight g 124 without batteries Holder Unit mm 48 5 5 5 26 2 69 3 6 5 Front View Side View Bottom View Ø 3 5 Hole 150 106 8 Hole 3 5 2 R Size H W D mm 150 69 3 26 2 Weight g 27 138 13 3 Wireless remote controller UTY LNTY Optional part 13 Remote controller 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 145: ...s may differ by type of the indoor unit For details refer to the operation manual Display panel Mode indicator Clock and Timer indicator Fan speed indicator Swing indicator Temperature indicator Transmit indicator To facilitate explanation the accompanying illustration has been drawn to show all possible indicators in actual operation however the display will only show those indicators appropriate...

Page 146: ... without batteries Holder Unit mm 48 5 5 5 26 2 69 3 6 5 Front View Side View Bottom View Ø 3 5 Hole 150 106 8 Hole 3 5 2 R Size H W D mm 150 69 3 26 2 Weight g 27 140 13 4 IR receiver kit with Wireless remote controller UTY LBTYM Optional part 13 Remote controller 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 147: ... 7 2 17 57 4 13 6 145 22 9 118 4 60 72 4 8 3 5 57 6 Side view Rear view Size H W D mm 145 90 30 Weight g 150 141 13 4 IR receiver kit with Wireless remote controller UTY LBTYM Optional part 13 Remote controller 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 148: ... DELETE button Deletes the weekly timer schedule k TIMER SET button Sets the date hour minute and on off time l Vertical airflow direction and swing button Push for 2 seconds to change the swing mode m Horizontal airflow direction and swing but ton Push for 2 seconds to change the swing mode n FILTER RESET button o Operation lamp Lights during operation and when the timer is on p Timer and clock i...

Page 149: ...iring 1 remote controller Remote controller 1 Red 12 V 2 White Signal 3 Black COM Indoor unit Remote controller 1 2 3 1 2 3 G G 2 remote controllers Remote controllers 1 Red 12 V 2 White Signal 3 Black COM Primary Secondary Indoor unit 1 2 3 1 2 3 1 2 3 Remote controller G G G 143 13 5 Wired remote controller UTY RNNYM Optional part 13 Remote controller 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT T...

Page 150: ...varies by the type of the connected indoor unit When connecting to terminal block for Compact cassette Slim duct and Mini duct types Connect the end of remote controller cable directly to the exclusive terminal block PCB M4 screw Terminal block Remote controller cable Remote controller terminal block Outdoor unit or Power supply terminal block or Remote controller terminal block NOTE It may be fai...

Page 151: ...roller cable Connecting cable White Red White Red Black Insulated connection Black 2 Connect the remote controller cable Connect the cable made in step 1 to the terminal 1 of optional Communication kit Connect the cable from the terminal 2 of Communication kit to the indoor unit PCB 1 CNC01 on UTY TWBXF2 2 CND01 on UTY TWBXF2 Remote controller cable Connecting cable Terminal 1 Terminal 2 Communica...

Page 152: ...tons Used to select setting items during the setting item selec tion screen is displayed g MENU button Used to display the setting item selection screen h MODE button Each time the button is pressed operation mode switches as follows Auto Cool Dry Fan Heat i On Off button Starts or stops the operation NOTE On Off button cannot be operated at screens other than the Monitor mode screen j Display pan...

Page 153: ...ler Indoor unit Y1 Y1 Y2 Y2 Y3 2 remote controllers When there is a functional grounding Remote controller Remote controller Y1 Y1 Y2 Y2 Y1 Y2 Y3 Indoor unit Group control When there is a functional grounding Remote controller Indoor units Y2 Y2 Y2 Y2 Y2 Y3 Y3 Y3 Y3 Y1 Y1 Y1 Y1 Y1 NOTE Group connection with Polar 3 wired remote controller is not allowed 147 13 6 Wired remote controller UTY RLRY Op...

Page 154: ...isted pair Use sheathed PVC cable Installation Connect the end of remote controller cable directly to the exclusive terminal block Terminal block Indoor unit PCB Functional earthing If necessary Remote controller cable Non polar Y1 Y2 TO REMOTE CONTROL UNIT Ex IN Y3 1 2 NOTES Layout of terminal block and PCB is varies depending on the type of indoor unit Operation may fail if it is connected to th...

Page 155: ...el with backlight b Screen switch button Left c Menu button d Cancel button e Cursor button f Screen switch button Right g Power indicator h On off button i Enter button 149 13 7 Wired remote controller UTY RVNYM Optional part 13 Remote controller 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 156: ...ontroller 1 2 3 1 2 3 2 remote controllers Remote controllers 1 Red 12 V 2 White Signal 3 Black COM Primary Secondary Indoor unit 1 2 3 1 2 3 1 2 3 Remote controller Controller combination As for the combined usage of the controller refer to following figures Good UTY RVNYM UTY RNNYM UTY RVNYM UTY RSNYM Indoor unit UTY RVNYM SET TEMP START STOP Indoor unit Indoor unit UTY RVNYM 150 13 7 Wired remo...

Page 157: ...20 120 21 3 Weight g 220 Wiring specifications Use Cable size Wire type Remarks Remote controller cable 0 33 mm2 Polar 3 core Use sheathed PVC cable 151 13 7 Wired remote controller UTY RVNYM Optional part 13 Remote controller 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 158: ...ve the case can be inserted Installation procedures 1 Process the remote controller cable 8 8 8 30 45 55 Unit mm 1 12V Red 2 Signal White 3 COM Black 2 Insert the flat blade screwdriver and twist it slightly to separate the front case and rear case 152 13 7 Wired remote controller UTY RVNYM Optional part 13 Remote controller 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 159: ... remote controller cable b Put a remote controller cable through the back hole of the rear case of the main body c Fix the rear case by securing it with attached screws 2 places When routing the cable on wall a Cut off the cable guide of the front case with using a knife or a nipper b Deburr the edge of the cable guide c Fix the rear case by securing it with attached screws 2 places 153 13 7 Wired...

Page 160: ...able sheath Hole for cable tie 2 mm Good Prohibited To avoid an excessive tension or pressure to the terminal block fix the remote controller cable with the cable tie properly CAUTION Be careful to avoid breaking the cable by over tightening the cable tie When connecting the remote controller cables do not over tighten the screws 154 13 7 Wired remote controller UTY RVNYM Optional part 13 Remote c...

Page 161: ...d indoor unit When connecting to terminal block for Compact cassette Slim duct and Mini duct types Connect the end of remote controller cable directly to the exclusive terminal block PCB M4 screw Terminal block Remote controller cable Remote controller terminal block Outdoor unit or Power supply terminal block or Remote controller terminal block NOTE It may be failed if it is connected to the outd...

Page 162: ...roller cable Connecting cable White Red White Red Black Insulated connection Black 2 Connect the remote controller cable Connect the cable made in step 1 to the terminal 1 of optional Communication kit Connect the cable from the terminal 2 of Communication kit to the indoor unit PCB 1 CNC01 on UTY TWBXF2 2 CND01 on UTY TWBXF2 Remote controller cable Connecting cable Terminal 1 Terminal 2 Communica...

Page 163: ...tor d Touch panel display e Set temperature Operating temperature can be set f Remote controller group name g Mode Operation mode can be set h Status icons i Clock j Fan Fan speed can be set k Room temperature l Menu Various settings can be set m Status Status of the indoor unit and error can be checked NOTE Functions may differ by type of the in door unit For details refer to the opera tion manua...

Page 164: ...ler Indoor unit Y1 Y1 Y2 Y2 Y3 2 remote controllers When there is a functional grounding Remote controller Remote controller Y1 Y1 Y2 Y2 Y1 Y2 Y3 Indoor unit Group control When there is a functional grounding Remote controller Indoor units Y2 Y2 Y2 Y2 Y2 Y3 Y3 Y3 Y3 Y1 Y1 Y1 Y1 Y1 NOTE Group connection with Polar 3 wired remote controller is not allowed 158 13 8 Wired remote controller UTY RNRYZ O...

Page 165: ...ons Use Cable size Wire type Remarks Remote controller cable 0 33 to 1 25 mm2 Non polar 2 core Twisted pair Use sheathed PVC cable Installation Connect the end of remote controller cable directly to the exclusive terminal block Terminal block Indoor unit PCB Functional earthing If necessary Remote controller cable Non polar Y1 Y2 TO REMOTE CONTROL UNIT Ex IN Y3 1 2 NOTES Layout of terminal block a...

Page 166: ...tes the main power is on i Central control indicator Indicates when function is locked j Fan speed indicator Deletes the weekly timer schedule k Set temperature Indicates error history number in error code history dis play mode Indicates indoor unit address in address display mode l Operating mode indicator m Indicator Upper Indicates the error code in error code history display mode and in self d...

Page 167: ...cal wiring 1 remote controller Remote controller 1 Red 12 V 2 White Signal 3 Black COM Indoor unit Remote controller 1 2 3 1 2 3 2 remote controllers Remote controllers 1 Red 12 V 2 White Signal 3 Black COM Primary Secondary Indoor unit 1 2 3 1 2 3 1 2 3 Remote controller 161 13 9 Simple remote controller UTY RSNYM Optional part 13 Remote controller 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 168: ...n of wired remote controller varies by the type of the connected indoor unit When connecting to terminal block for Compact cassette Slim duct and Mini duct types Connect the end of remote controller cable directly to the exclusive terminal block PCB M4 screw Terminal block Remote controller cable Remote controller terminal block Outdoor unit or Power supply terminal block or Remote controller term...

Page 169: ...oller cable Connecting cable White Red White Red Black Insulated connection Black 2 Connect the remote controller cable Connect the cable made in step 1 to the terminal 1 of optional Communication kit Connect the cable from the terminal 2 of Communication kit to the indoor unit PCB 1 CNC01 on UTY TWBXF2 2 CND01 on UTY TWBXF2 Remote controller cable Connecting cable Terminal 1 Terminal 2 Communicat...

Page 170: ...ed indicator k Remote controller address indicator l Status icons Mode mismatch Filter sign 5 Defrost operation Oil recovery operation Under maintenance Error Special state Conducting electricity Emergency stop Operation controlled Forced stop Remote controller sensor is enabled 5 Central controlled Setting temperature range is enabled Operation prohibited m Set temperature Indicates indoor unit a...

Page 171: ...or unit Y1 Y1 Y2 Y2 Y3 2 remote controllers When there is a functional grounding Remote controller Remote controller Y1 Y1 Y2 Y2 Y1 Y2 Y3 Indoor unit Group control When there is a functional grounding Remote controller Indoor units Y2 Y2 Y2 Y2 Y2 Y3 Y3 Y3 Y3 Y1 Y1 Y1 Y1 Y1 NOTE Group connection with Polar 3 wired remote controller is not allowed 165 13 10 Simple remote controller UTY RSRY and UTY ...

Page 172: ... core Twisted pair Use sheathed PVC cable Installation Connect the end of remote controller cable directly to the exclusive terminal block Terminal block Indoor unit PCB Functional earthing If necessary Remote controller cable Non polar Y1 Y2 TO REMOTE CONTROL UNIT Ex IN Y3 1 2 NOTES Layout of terminal block and PCB is varies depending on the type of indoor unit Operation may fail if it is connect...

Page 173: ...on settings Related components on the PCB and the applicable settings Component Setting content DIP switch SW100 1 Remote controller address setting 2 3 4 SW101 1 Drainage function setting 2 Auto louver grille setting 3 Fan delay setting Component location Components on the indoor unit main PCB used for the function settings are located as shown in the following figure SW100 1 2 3 4 SW101 1 2 3 16...

Page 174: ... 14 OFF ON ON ON 15 ON ON ON ON 00 01 02 Remote controller address Indoor unit Remote controller SW101 Switch 1 Drainage function setting Switch 1 Drainage function Factory setting ON Disabled OFF Enabled SW101 Switch 2 Auto louver grille setting When Auto louver grille kit optional parts is attached set to Enabled Switch 2 Auto louver grille setting Factory setting ON Enabled OFF Disabled SW101 S...

Page 175: ...e settings may be selected between the following two Function number or Setting number Settings will not be changed if invalid numbers or setting numbers are selected Preparation Before connecting the power supply of the indoor unit reconfirm following items Piping air tight test and vacuuming have been performed firmly There is no wiring mistake Then connect the power supply of the indoor unit Br...

Page 176: ...reases and decreases Changes the display digits Transmits function setting Transmits function mode POWERFUL button SET TEMP button START STOP button RESET button MODE button NOTE The number of buttons varies by the remote controller model Function setting procedure 1 Connect the power supply of the outdoor unit 2 To enter the function setting mode while holding down the POWERFUL and TEMP button pr...

Page 177: ...on To return to the function number selection press the POWERFUL button again 5 Select the function number by pressing the or the button Each time the 10 C HEAT but ton is pressed it switches between the right digit and the left digit Change digit 6 Press the MODE button once to transmit the function mode information 171 14 2 Indoor unit setting by wireless remote controller 14 Function settings 2...

Page 178: ...ds after pressing MODE button For the function details refer to Chapter 14 5 Function details on page 203 8 Exit the function setting mode by pressing the RESET button RESET Setting up each indoor unit Repeat step from 1 to 8 to set up each indoor unit If the custom code is other than steps from 1 to 2 and 8 need to be performed 172 14 2 Indoor unit setting by wireless remote controller 14 Functio...

Page 179: ...ng the power supply and then recon necting it Record the latest configuration of the indoor unit function setting on a label and put the label on the unit so it can be used for after sales service operations Once the RESET button is pressed on the remote controller the operation mode will be set to the AUTO MODE Adjust the operation mode to either cooling or heating before starting the operation o...

Page 180: ...utton to change the custom code between 4 Press the MODE button again to return to the clock display The custom code will be changed If no buttons are pressed within 30 seconds after the custom code is displayed the system returns to the original clock display In this case start again from step 1 The air conditioner custom code is set to A prior to shipment If you do not know the air conditioner c...

Page 181: ...ed number Increases and decreases Changes the displayed digits Fixes function setting Transmits function mode POWERFUL button TEMP button Start Stop button RESET button MODE button Function setting procedure 1 Connect the power supply of the outdoor unit 2 To enter the function setting mode while holding down the POWERFUL and SET TEMP buttons press the RESET button POWERFUL SET TEMP RESET Function...

Page 182: ...eturn to the function number selection press the POWERFUL button again 5 Select the function number by pressing the or the button Each time the 10 C HEAT but ton is pressed it switches between the right digit and the left digit Change digit 6 Press the MODE button once to transmit the function mode information 2 short beeps 176 14 2 Indoor unit setting by wireless remote controller 14 Function set...

Page 183: ...ds after pressing MODE button For the function details refer to Chapter 14 5 Function details on page 203 8 Exit the function setting mode by pressing the RESET button RESET Setting up each indoor unit Repeat step from 1 to 8 to set up each indoor unit If the custom code is other than steps from 1 to 2 and 8 need to be performed 177 14 2 Indoor unit setting by wireless remote controller 14 Functio...

Page 184: ...ng the power supply and then recon necting it Record the latest configuration of the indoor unit function setting on a label and put the label on the unit so it can be used for after sales service operations Once the RESET button is pressed on the remote controller the operation mode will be set to the AUTO MODE Adjust the operation mode to either cooling or heating before starting the operation o...

Page 185: ... button to change the custom code between 4 Press the MODE button again to return to the clock display The custom code will be changed If no buttons are pressed within 30 seconds after the custom code is displayed the system returns to the original clock display In this case start again from step 1 The air conditioner custom code is set to A prior to shipment If you do not know the air conditioner...

Page 186: ...mber top line The displayed number Increases and decreases Changes the displayed digits Fixes function setting Transmits function mode ECONOMY button TEMP button Start Stop button RESET button MODE button Function setting procedure 1 Connect the power supply of the outdoor unit 2 To enter the function setting mode while holding down the ECONOMY and SET TEMP buttons press the RESET button ECONOMY S...

Page 187: ...on To return to the function number selection press the ECONOMY button again 5 Select the function number by pressing the or the button Each time the 10 C HEAT but ton is pressed it switches between the right digit and the left digit Change digit 6 Press the MODE button once to transmit the function mode information 181 14 2 Indoor unit setting by wireless remote controller 14 Function settings 2 ...

Page 188: ...ode is set no beep sound will be emitted 1 short beep NOTE Press button within 30 seconds after pressing MODE button For the function details refer to Chapter 14 5 Function details on page 203 8 Exit the function setting mode by pressing the RESET button RESET 182 14 2 Indoor unit setting by wireless remote controller 14 Function settings 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 189: ...oor unit is turned off However setting function is effective after disconnecting the power supply and then recon necting it Record the latest configuration of the indoor unit function setting on a label and put the label on the unit so it can be used for after sales service operations Once the RESET button is pressed on the remote controller the operation mode will be set to the AUTO MODE Adjust t...

Page 190: ... button to change the custom code between 4 Press the MODE button again to return to the clock display The custom code will be changed If no buttons are pressed within 30 seconds after the custom code is displayed the system returns to the original clock display In this case start again from step 1 The air conditioner custom code is set to A prior to shipment If you do not know the air conditioner...

Page 191: ...ected between the following two Function number or Setting number Settings will not be changed if invalid numbers or setting numbers are selected This function cannot be used on the secondary units Preparation Before connecting the power supply of the indoor unit reconfirm following items Piping air tight test and vacuuming have been performed firmly There is no wiring mistake Then connect the pow...

Page 192: ... setting Function setting procedure 1 Connect the power supply of the outdoor unit 2 Switch to the function setting mode To enter the function setting mode hold down the 3 buttons of SET TEMP SET TEMP and FAN at the same time for 5 seconds or longer 3 Select the function number by pressing the SET TIME or the SET TIME button 4 Select the setting number by pressing the SET TEMP or the SET TEMP butt...

Page 193: ...c cording to the procedure in step 2 Setting up each indoor unit Repeat the procedures from step 1 to 6 and set up the indoor units requiring function setting Resetting the power after setting up function of all indoor units NOTES If the reset is not performed function cannot be read correctly After all the functions have been set the circuit breaker needs to be switched off for at least 2 minutes...

Page 194: ...uming have been performed firmly There is no wiring mistake 1 Connect the power supply 2 To activate the address setting mode hold down the three buttons of MENU and EN TER at the same time for 2 seconds or longer Menu 2 setting screen is displayed 3 Select the 13 in Menu 2 settings Then press the ENTER button 4 Pressing the or button select a remote controller address select the indoor unit you w...

Page 195: ...e indoor units requiring function setting Resetting the power after setting up function of all indoor units NOTES If the reset is not performed function cannot be read correctly After all the functions have been set the circuit breaker needs to be switched off for at least 2 minutes After the 2 minutes has passed power can be restored The set function is stored in the PCB and will remain in memory...

Page 196: ... switch button Right simultaneously for 5 seconds to switch to Service screen Back Setting Service Mo 10 00AM Function setting Error history I U address verification Version Test run Back Setting Date and time Submenu 1 2 Monitor Screen Filter sign R C sensor control Room temp display Off Off Mo 10 00AM Select Function setting with pressing the Cursor button Up Down and press the Enter but ton Bac...

Page 197: ...address No No Version Error history 00 30 01 5 Pressing the Enter button confirm the setting The data will be transferred to the indoor unit Cancel OK Function setting Mo 10 00AM R C Function Setting address No No Version Error history 00 30 01 Cancel OK Function setting Mo 10 00AM R C Function Setting address No No Version Error history 00 30 Cancel OK Function setting Mo 10 00AM R C Function Set...

Page 198: ...step 1 to 6 and set up the indoor units requiring function setting Resetting the power after setting up function of all indoor units NOTES If the reset is not performed function cannot be read correctly After all the functions have been set the circuit breaker needs to be switched off for at least 2 minutes After the 2 minutes has passed power can be restored The set function is stored in the PCB ...

Page 199: ...Func tion Setting screen is displayed Previous Page Back Next Page Page 2 3 Maintenance Test Run R C Address Setting Function Setting I U Address Setting 002 01 00 00 Address Function No Setting No Function Setting Back Setting Address setting mode initial display 3 Touch the Address on the Function Setting screen 002 01 00 00 Address Function No Setting No Function Setting Back Setting 4 Address ...

Page 200: ...hen All is chosen by 5 and different set up Setting No from two or more indoor units is displayed on Setting No 8 Setting screen of Setting No is displayed Set the Function No with or 01 002 01 30 Function Setting Cancel OK Address Function No Setting No Example Function number 30 Setting Number 01 When the OK is touched the Function Setting verification screen is displayed 194 14 3 Indoor unit se...

Page 201: ...the procedure from step 1 to 6 and set up the indoor units requiring function setting Resetting the power after setting up function of all indoor units NOTES If the reset is not performed function cannot be read correctly After all the functions have been set the circuit breaker needs to be switched off for at least 2 minutes After the 2 minutes has passed power can be restored The set function is...

Page 202: ...ected between the following two Function number or Setting number Settings will not be changed if invalid numbers or setting numbers are selected This function cannot be used on the secondary units Preparation Before connecting the power supply of the indoor unit reconfirm following items Piping air tight test and vacuuming have been performed firmly There is no wiring mistake Then connect the pow...

Page 203: ...ET TEMP p and q button Switches the various numbers Function setting procedure 1 Connect the power supply of the outdoor unit 2 Switch to the function setting mode To enter the function setting mode hold down the 3 buttons of SET TEMP SET TEMP and FAN at the same time for 5 seconds or longer Function setting mode initial display 3 Press the FAN button The Function number indicator flashes Then pre...

Page 204: ...page 203 6 Exit the function setting mode by pressing the 3 buttons of SET TEMP SET TEMP and FAN at the same time for 5 seconds or longer After exiting the function setting mode the display returns to the normal mode Normal mode display If no button is pressed within 60 seconds after buttons mentioned above are pressed it will au tomatically exit the function setting mode If you exit the function ...

Page 205: ...e set function is stored in the PCB and will remain in memory even when the power of in door unit is turned off However setting function is effective after disconnecting the power supply and then recon necting it Record the latest configuration of the indoor unit function setting on a label and put the label on the unit so it can be used for after sales service operations 199 14 4 Indoor unit sett...

Page 206: ...ing mistake NOTE Set only one Master remote controller 1 Connect the power supply 2 With Monitor mode screen displayed press and hold the SET TEMP button and FAN button simultaneously for at least 2 seconds 3 The Menu 1 screen is displayed Press and hold the SET TEMP button at least 2 seconds Setting mode selection screen is displayed 4 Press the SET TEMP or SET TEMP button to select F1 Menu 2 F1 ...

Page 207: ...SET TEMP or SET TEMP button Then press the button Select the 2 wire remote controller address Ex Select the 002 03 9 Set the function number with the SET TEMP or SET TEMP button Then press the button Function number 10 Set the setting number with the SET TEMP or SET TEMP button Then press the button Setting number 201 14 4 Indoor unit setting by simple remote controller 14 Function settings 2 UNIT...

Page 208: ... cannot be read correctly After all the functions have been set the circuit breaker needs to be switched off for at least 2 minutes After the 2 minutes has passed power can be restored The set function is stored in the PCB and will remain in memory even when the power of in door unit is turned off However setting function is effective after disconnecting the power supply and then recon necting it ...

Page 209: ...tting 2 11 Filter sign 3 20 Ceiling height 4 22 Outlet directions 5 26 Static pressure 6 30 31 Room temperature control for indoor unit sensor 7 35 36 Room temperature control for wired remote controller sensor 8 40 Auto restart 9 42 Room temperature sensor switching 10 44 Remote controller custom code 11 46 External input control 12 48 Room temperature sensor switching Aux 13 49 Indoor unit fan c...

Page 210: ...wired remote controller set the remote controller address in the order of 0 1 2 and 15 When different type of indoor units such as wall mounted type and cassette type cassette type and duct type or other combinations are connected using group control system some func tions may no longer be available 2 Filter sign Select appropriate intervals for displaying the filter sign on the indoor unit accord...

Page 211: ...f cassette type models The ceiling height values are for the 4 way outlet Do not change this setting in the 3 way outlet mode 7 000 or 9 000 Btu h models cannot be installed in high ceilings Do not change this setting 4 Outlet directions Select the appropriate number of outlet directions according to the installation conditions Function number Setting value Setting description Factory setting 22 0...

Page 212: ...by model Model Range of static pressure 07 09 12 models 0 to 30 Pa 14 models 0 to 50 Pa Setting number in 07 09 12 models is 04 to 30 Operation is same as that 03 Setting number in 14 models is 06 to 30 Operation is same as that 05 Setting number value cannot be set to 32 or more For slim duct type Function number Setting value Setting description Factory setting 26 00 0 Pa 01 10 Pa 02 20 Pa 03 30...

Page 213: ...om temp sensor is 26 C and the setting value is 03 1 0 C corrected temp will be 27 C 26 C 1 0 C The temperature correction values show the difference from the Standard setting 00 manufactur er s recommended value Function number Setting value Setting description Factory setting 30 For cooling 31 For heating 00 Standard setting 01 No correction 0 0 C 02 0 5 C More cooling Less heating 03 1 0 C 04 1...

Page 214: ...14 2 5 C 15 3 0 C 16 3 5 C 17 4 0 C 8 Auto restart Enables or disables automatic restart after a power interruption Function number Setting value Setting description Factory setting 40 00 Enable 01 Disable NOTE Auto restart is an emergency function such as for power outage etc Do not attempt to use this function in normal operation Be sure to operate the unit by remote controller or exter nal devi...

Page 215: ...ng description Factory setting 48 00 Both 01 Wired remote controller 13 Indoor unit fan control for energy saving for cooling Enables or disables the power saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation Function number Setting value Setting description Factory setting 49 00 Disable 01 Enable 02 Remote controller 00 When the out...

Page 216: ...al can be switched For details refer to External input and output Function number Setting value Setting description Factory setting 60 00 Operation status 01 08 Setting prohibited 09 Error status 10 Indoor unit fan operation status 11 External heater 210 14 5 Function details 14 Function settings 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 217: ...e remote controller SW2 according to the following table Number of remote controller Primary unit Secondary unit Factory setting SW2 SW2 1 Normal OFF 2 Dual OFF ON 1 2 3 1 2 3 1 2 3 Indoor unit Remote controller cable Primary unit Secondary unit Remote controller SW4 Switching temperature unit F C Displayed temperature unit can be switched between Fahrenheit F and Celsius C SW4 Fahrenheit F Celsiu...

Page 218: ...up When batteries are not used all of settings stored in memory will be deleted if there is a power failure SW6 Memory backup Factory setting OFF Disable ON Enable 212 14 6 Wired remote controller UTY RNNYM 14 Function settings 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 219: ... if there is a power failure SW1 Memory backup Factory setting OFF Disable ON Enable SW2 Dual remote controller setting Set the remote controller SW2 according to the following table Number of remote controller Primary unit Secondary unit Factory setting SW2 SW2 1 Normal OFF 2 Dual OFF ON 1 2 3 1 2 3 1 2 3 Indoor unit Remote controller cable Primary unit Secondary unit Remote controller 213 14 7 W...

Page 220: ...ackup Factory setting OFF Disable ON Enable 14 9 Wired remote controller UTY RNRYZ DIP switch Memory backup setting Switch location Front case back side Set the DIP switch to ON OFF ON ON Dip switch setting SW1 Memory backup setting Set to ON to use batteries for the memory backup When batteries are not used all of settings stored in memory will be deleted if there is a power failure SW1 Memory ba...

Page 221: ...the following table Number of remote controller Primary unit Secondary unit Factory setting SW2 SW2 1 Normal OFF 2 Dual OFF ON 1 2 3 1 2 3 1 2 3 Indoor unit Remote controller cable Primary unit Secondary unit Remote controller SW3 Switching temperature unit F C Displayed temperature unit can be switched between Fahrenheit F and Celsius C SW3 Fahrenheit F Celsius C Factory setting OFF C ON F 215 14...

Page 222: ... Drain hose insulation 1 Operating manual CD ROM 1 Hose band 1 Installation manual 1 Coupler heat insulation large 1 Template Carton top 1 Coupler heat insulation small 1 M10 nut A with flange 4 Cable tie 2 M10 nut B with spring lock washer 4 Wire cramper 1 Drain hose 1 216 15 1 Compact cassette type 15 Accessories 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 223: ...rating manual CD ROM 1 Hose band 1 Installation manual 1 Drain hose insulation B 1 Installation template Carton top 1 Washer 8 Cable tie large 4 Coupler heat insulation large 1 Cable tie medium 3 Coupler heat insulation small 1 Filter small 2 Insulation For electrical wiring 2 217 15 2 Mini duct type 15 Accessories 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 224: ...l 2 Operating manual CD ROM 1 Drain hose 1 Installation manual 1 Hose band 1 Installation template 1 Drain hose insulation B 1 Washer 8 Insulation for electrical wiring 2 Cable tie large 4 Coupler heat insulation large 1 Cable tie medium 3 Coupler heat insulation small 1 218 15 3 Slim duct type 15 Accessories 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 225: ...erating manual 1 Cloth tape 1 Operating manual CD ROM 1 Tapping screw large 5 Installation manual 1 Tapping screw small 2 Remote controller 1 Wall hook bracket 1 Battery 2 Filter holder 2 Remote controller holder 1 Air cleaning filters 1 219 15 4 Wall mounted type 15 Accessories 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 226: ...rating manual 1 Cloth tape 1 Operating manual CD ROM 1 Tapping screw large 5 Installation manual 1 Tapping screw small 2 Remote controller 1 Wall hook bracket 1 Battery 2 Filter holder 2 Remote controller holder 1 Air cleaning filters 1 Template for pipe cover cutting 1 220 15 4 Wall mounted type 15 Accessories 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 227: ... Operating manual 1 Operating manual CD ROM 1 Installation manual 1 Cloth tape 1 Wall hook bracket 1 Tapping screws large 9 Remote controller 1 Tapping screws small 2 Battery 2 Air cleaning filters 1 Remote controller holder 1 221 15 5 Floor type 15 Accessories 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 228: ...t with Wireless remote controller Simple remote controller UTY LBTYM UTY RSNYM UTY RSRY UTY RHRY Compact cassette Mini duct Slim duct Wall mounted KG 2 2 KM 1 KE 2 2 Floor 3 3 Accessory Optional Not applicable 1 Optional Communication kit UTY TWBXF2 is necessary for the installation 2 Optional Communication kit UTY TWRXZ2 is necessary for the installation 3 Optional Communication kit UTY TWRXZ3 is...

Page 229: ... UTY LNTY Wired remote controller UTY RNNYM UTY RVNYM UTY RLRY UTY RNRYZ IR receiver kit with Wireless remote controller Simple remote controller UTY LBTYM UTY RSNYM UTY RSRY UTY RHRY 223 16 1 Controllers 16 Optional parts 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 230: ...16 2 Cassette grille Lineup Indoor unit type Model Compact cassette UTG UFYF W Part Cassette grille UTG UFYF W 224 16 2 Cassette grille 16 Optional parts 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 231: ...r unit type Type Remote sensor unit Communication kit Wireless LAN adapter 4 Half concealed kit UTY XSZX UTY TWBXF2 UTY TWRXZ2 UTY TWRXZ3 UTY TFSXW1 UTY TFSXF2 UTY TFSXZ1 UTR STA Compact cassette Mini duct Slim duct Wall mounted KG KM KE Floor Accessory Optional Not applicable 1 Optional Communication kit UTY TWBXF2 is necessary for the installation 2 Optional Communication kit UTY TWRXZ2 is neces...

Page 232: ...del UTY XWZXZG External connect kit Model UTY XWZX External connect kit Model UTY XWZXZ5 x 1 x 1 x 1 x 2 External input and output PCB Model UTY XCSXZ2 Communication kit Model UTY TWRXZ2 Communication kit Model UTY TWRXZ3 Communication kit Model UTY TWBXF2 MODBUS converter Model UTY VMSX 226 16 3 Others 16 Optional parts 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 233: ... Models UTY TERX Remote sensor unit Model UTY XSZX Auto louver grille kit Models UTD GXTA W Wireless LAN adapter Models UTY TFSXZ1 Wireless LAN adapter Models UTY TFSXW1 Wireless LAN adapter Models UTY TFSXF2 Half concealed kit Models UTR STA 227 16 3 Others 16 Optional parts 2 UNIT MULTI SPLIT TYPE 2 UNIT MULTI SPLIT TYPE ...

Page 234: ...s installed where the installation height given in the installation manual is exceeded the temperature difference between the floor and ceiling of the room will be large and the heating effect will be poor Moreover even if the indoor unit is installed within the installation height a similar phenomena will occur when installed in a room in which the doors are opened and closed frequently and hot a...

Page 235: ...controller where it will not be directly exposed to sunlight or strong lighting When installation environment is quiet When the wall mounted type was installed in a bedroom living room or other quiet place the sound of the refrigerant flow may be sensed as noise and must be taken into account 1 Plan installation of a model with external expansion valve 2 Plan installation of a branch box farther f...

Page 236: ...ating material locally purchased Small exposed part of copper pipe is desirable Fit tightly purpose is to cover the sealant Binding material Flare connection To indoor unit Heat insulation reinforcement material locally purchased Figure 17 2 Work method when reinforcing the heat insulation of on site piping 230 17 2 Points to remember when installing 17 Indoor unit installation precautions 2 UNIT ...

Page 237: ...Part 2 OUTDOOR UNIT 2 UNITS TYPE MULTI SPLIT TYPE AOYG14KBTA2 AOYG18KBTA2 ...

Page 238: ...nclosure Material Steel sheet Color Beige Approximate color of Munsell 10YR 7 5 1 0 NN Dimensions H x W x D Net mm 542 799 290 632 799 290 Gross 602 940 375 692 940 375 Weight Net kg 33 37 Gross 37 41 Connection pipe Size Liquid mm in Ø6 35 Ø1 4 2 Gas Ø9 52 Ø3 8 2 Method Flare Pre charge length Total m 20 Maximum length Total 30 Maximum length Each 20 Minimum length Total 5 Minimum length Each 2 5...

Page 239: ...gn Cooling kW 4 0 35 C 5 0 35 C Heating Average 3 5 10 C 4 2 10 C SEER Cooling kWh kWh 8 70 8 60 SCOP Heating Average 4 70 4 70 Annual energy consumption QCE kWh a 209 263 QHE Average 1 296 1 434 Sound power level Cooling HIGH dB A 60 Heating 62 233 1 Specifications OUTDOOR UNIT AOYG14 18KBTA2 OUTDOOR UNIT AOYG14 18KBTA2 ...

Page 240: ...itch of bolts for installation Top view 4 M10 hole Side view Side view Front view 799 68 290 16 33 30 19 542 20 Airflow Bottom view Side view Valve part 37 399 Drain port Ø42 114 57 104 4 150 1 19 7 234 2 1 Model AOYG14KBTA2 2 Dimensions OUTDOOR UNIT AOYG14 18KBTA2 OUTDOOR UNIT AOYG14 18KBTA2 ...

Page 241: ...lve part Top view 580 799 19 68 16 290 33 30 109 353 632 20 330 Pitch of bolts for installation Pitch of bolts for installation 4 M10 hole Airflow Drain port Ø42 37 114 57 104 4 399 150 1 19 7 235 2 2 Model AOYG18KBTA2 2 Dimensions OUTDOOR UNIT AOYG14 18KBTA2 OUTDOOR UNIT AOYG14 18KBTA2 ...

Page 242: ...allation When the upper space is open Unit mm Obstacles at rear only Obstacles at rear and sides 100 or more 250 or more 100 or more 100 or more Obstacles at front Obstacles at front and rear 600 or more 600 or more 100 or more When an obstruction in the upper space Unit mm Obstacles at rear and above Obstacles at rear sides and above 100 or more Max 200 600 or more 250 or more 100 or more Max 200...

Page 243: ... in the following ex ample When an obstruction in the upper space When the upper space is open Unit mm Obstacles at rear only Obstacles at front only 200 or more 250 or more 1 000 or more 250 or more Obstacles at front and rear 200 or more 1 000 or more 250 or more When an obstruction in the upper space Unit mm Obstacles at rear and above 1 500 or more 200 or more 250 or more 250 or more Max 300 1...

Page 244: ... stage where the drain water could freeze Otherwise the drainage from the upper unit may form ice and cause a malfunction of the lower unit When the outdoor temperature is 0 C or less do not use the accessory drain pipe and drain cap If the drain pipe and drain cap are used the drain water in the pipe may freeze in extremely cold climate For reverse cycle model only In area with heavy snowfall if ...

Page 245: ...4 Refrigerant circuit 4 1 Model AOYG14KBTA2 239 4 1 Model AOYG14KBTA2 4 Refrigerant circuit OUTDOOR UNIT AOYG14 18KBTA2 OUTDOOR UNIT AOYG14 18KBTA2 ...

Page 246: ...4 2 Model AOYG18KBTA2 240 4 2 Model AOYG18KBTA2 4 Refrigerant circuit OUTDOOR UNIT AOYG14 18KBTA2 OUTDOOR UNIT AOYG14 18KBTA2 ...

Page 247: ...5 Wiring diagram 5 1 Model AOYG14KBTA2 241 5 1 Model AOYG14KBTA2 5 Wiring diagram OUTDOOR UNIT AOYG14 18KBTA2 OUTDOOR UNIT AOYG14 18KBTA2 ...

Page 248: ...5 2 Model AOYG18KBTA2 242 5 2 Model AOYG18KBTA2 5 Wiring diagram OUTDOOR UNIT AOYG14 18KBTA2 OUTDOOR UNIT AOYG14 18KBTA2 ...

Page 249: ...tal ability of connected indoor unit is from 14 000 Btu h up to 21 000 Btu h Heating Combination of indoor unit Rated capacity for each indoor unit kB tu h Total capacity kBtu h Input power kW COP W W Seasonal data Unit Total Unit Min Rated Max Min Rated Max Pdesign kW SCOP kWh kWh Energy effi ciency class 1 2 1 2 7 7 14 2 20 2 20 1 1 4 40 5 5 0 25 0 95 1 65 4 63 3 5 4 7 A 7 9 16 1 92 2 48 1 1 4 4...

Page 250: ...ed indoor units is from 14 000 Btu h up to 26 000 Btu h Heating Combination of indoor unit Rated capacity for each indoor unit kW Total capacity kW Input power kW COP W W Seasonal data Unit Total Unit Min Rated Max Min Rated Max Pdesign kW SEER kWh kWh Energy effi ciency class 1 2 1 2 7 7 14 2 40 2 40 1 70 4 80 5 60 0 25 0 99 1 35 4 85 3 8 4 7 A 7 9 16 2 40 3 00 1 70 5 40 6 40 0 25 1 15 1 60 4 70 ...

Page 251: ... 0 60 4 30 0 61 4 60 0 62 4 90 0 62 5 10 0 63 25 0 3 60 0 76 4 10 0 78 4 30 0 78 4 60 0 79 4 90 0 80 5 10 0 81 30 0 3 60 0 91 4 10 0 93 4 30 0 94 4 60 0 95 4 90 0 96 5 10 0 96 35 0 3 60 1 21 4 10 1 23 4 30 1 24 4 60 1 25 4 90 1 26 5 10 1 27 40 0 3 10 1 00 3 50 1 02 3 70 1 03 4 00 1 04 4 30 1 05 4 40 1 06 46 0 2 70 1 01 3 10 1 03 3 20 1 04 3 50 1 05 3 70 1 06 3 80 1 07 16 10 0 3 60 0 63 4 10 0 64 4...

Page 252: ... 2 77 2 18 2 85 2 50 20 0 2 03 1 35 2 29 1 54 2 42 1 78 2 59 1 99 2 77 2 18 2 85 2 50 25 0 2 03 1 35 2 29 1 54 2 42 1 78 2 59 1 99 2 77 2 18 2 85 2 50 30 0 2 03 1 35 2 29 1 54 2 42 1 78 2 59 1 99 2 77 2 18 2 85 2 50 35 0 2 03 1 35 2 29 1 54 2 42 1 78 2 59 1 99 2 77 2 18 2 85 2 50 40 0 1 76 1 02 1 99 1 16 2 10 1 34 2 25 1 50 2 40 1 64 2 48 1 88 46 0 1 53 0 77 1 73 0 88 1 83 1 01 1 96 1 14 2 09 1 24...

Page 253: ...77 2 10 2 85 2 40 20 0 2 03 1 30 2 29 1 48 2 42 1 71 2 59 1 92 2 77 2 10 2 85 2 40 25 0 2 03 1 30 2 29 1 48 2 42 1 71 2 59 1 92 2 77 2 10 2 85 2 40 30 0 2 03 1 30 2 29 1 48 2 42 1 71 2 59 1 92 2 77 2 10 2 85 2 40 35 0 2 03 1 30 2 29 1 48 2 42 1 71 2 59 1 92 2 77 2 10 2 85 2 40 40 0 1 76 0 98 1 99 1 12 2 10 1 29 2 25 1 44 2 40 1 58 2 48 1 81 46 0 1 53 0 74 1 73 0 84 1 83 0 97 1 96 1 09 2 09 1 20 2 ...

Page 254: ...77 2 18 2 85 2 50 20 0 2 03 1 35 2 29 1 54 2 42 1 78 2 59 1 99 2 77 2 18 2 85 2 50 25 0 2 03 1 35 2 29 1 54 2 42 1 78 2 59 1 99 2 77 2 18 2 85 2 50 30 0 2 03 1 35 2 29 1 54 2 42 1 78 2 59 1 99 2 77 2 18 2 85 2 50 35 0 2 03 1 35 2 29 1 54 2 42 1 78 2 59 1 99 2 77 2 18 2 85 2 50 40 0 1 76 1 02 1 99 1 16 2 10 1 34 2 25 1 50 2 40 1 64 2 48 1 88 46 0 1 53 0 77 1 73 0 88 1 83 1 01 1 96 1 14 2 09 1 24 2 ...

Page 255: ...29 1 30 2 42 1 50 2 59 1 68 2 77 1 84 2 85 2 11 15 0 2 03 1 14 2 29 1 30 2 42 1 50 2 59 1 68 2 77 1 84 2 85 2 11 20 0 2 03 1 14 2 29 1 30 2 42 1 50 2 59 1 68 2 77 1 84 2 85 2 11 25 0 2 03 1 14 2 29 1 30 2 42 1 50 2 59 1 68 2 77 1 84 2 85 2 11 30 0 2 03 1 14 2 29 1 30 2 42 1 50 2 59 1 68 2 77 1 84 2 85 2 11 35 0 2 03 1 14 2 29 1 30 2 42 1 50 2 59 1 68 2 77 1 84 2 85 2 11 40 0 1 76 0 86 1 99 0 98 2 ...

Page 256: ...9 1 30 2 42 1 50 2 59 1 68 2 77 1 84 2 85 2 11 15 0 2 03 1 14 2 29 1 30 2 42 1 50 2 59 1 68 2 77 1 84 2 85 2 11 20 0 2 03 1 14 2 29 1 30 2 42 1 50 2 59 1 68 2 77 1 84 2 85 2 11 25 0 2 03 1 14 2 29 1 30 2 42 1 50 2 59 1 68 2 77 1 84 2 85 2 11 30 0 2 03 1 14 2 29 1 30 2 42 1 50 2 59 1 68 2 77 1 84 2 85 2 11 35 0 2 03 1 14 2 29 1 30 2 42 1 50 2 59 1 68 2 77 1 84 2 85 2 11 40 0 1 76 0 86 1 99 0 98 2 1...

Page 257: ... 1 84 2 85 2 11 20 0 2 03 1 14 2 29 1 30 2 42 1 50 2 59 1 68 2 77 1 84 2 85 2 11 25 0 2 03 1 14 2 29 1 30 2 42 1 50 2 59 1 68 2 77 1 84 2 85 2 11 30 0 2 03 1 14 2 29 1 30 2 42 1 50 2 59 1 68 2 77 1 84 2 85 2 11 35 0 2 03 1 14 2 29 1 30 2 42 1 50 2 59 1 68 2 77 1 84 2 85 2 11 40 0 1 76 0 86 1 99 0 98 2 10 1 13 2 25 1 27 2 40 1 39 2 48 1 59 46 0 1 53 0 65 1 73 0 74 1 83 0 85 1 96 0 96 2 09 1 05 2 16...

Page 258: ... Indoor temperature CDB CWB 18 0 12 0 21 0 15 0 23 0 16 0 27 0 19 0 29 0 21 0 32 0 23 0 CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 0 2 28 1 46 2 58 1 66 2 72 1 92 2 91 2 15 3 11 2 36 3 21 2 70 5 0 2 28 1 46 2 58 1 66 2 72 1 92 2 91 2 15 3 11 2 36 3 21 2 70 0 0 2 28 1 46 2 58 1 66 2 72 1 92 2 91 2 15 3 11 2 36 3 21 2 70 5 0 2 28 1 46 2 58 1 66 2 72 1 92 2 91 2 15 3 11 2 36 3 21 2 70 10 0 2 28...

Page 259: ... 5 8 0 91 6 2 0 92 6 4 0 93 10 0 4 5 0 48 5 1 0 49 5 4 0 50 5 8 0 50 6 2 0 51 6 4 0 51 15 0 4 5 0 64 5 1 0 65 5 4 0 66 5 8 0 67 6 2 0 67 6 4 0 68 20 0 4 5 0 85 5 1 0 86 5 4 0 87 5 8 0 88 6 2 0 89 6 4 0 89 25 0 4 5 1 05 5 1 1 07 5 4 1 08 5 8 1 09 6 2 1 10 6 4 1 11 30 0 4 5 1 22 5 1 1 24 5 4 1 25 5 8 1 27 6 2 1 28 6 4 1 29 35 0 4 5 1 57 5 1 1 60 5 4 1 61 5 8 1 63 6 2 1 65 6 4 1 66 40 0 3 6 1 28 4 0 ...

Page 260: ... 0 84 4 7 0 85 5 0 0 86 5 3 0 87 5 5 0 87 30 0 3 9 0 97 4 4 0 98 4 7 0 99 5 0 1 00 5 3 1 01 5 5 1 02 35 0 3 9 1 24 4 4 1 26 4 7 1 27 5 0 1 29 5 3 1 30 5 5 1 31 40 0 3 1 1 01 3 5 1 03 3 7 1 04 3 9 1 05 4 2 1 06 4 3 1 06 46 0 3 1 0 78 3 5 0 79 3 7 0 80 3 9 0 81 4 2 0 82 4 3 0 82 NOTES TC Total Capacity kW IP Input Power kW Values mentioned in the table are based on the following conditions Power sou...

Page 261: ...rature Indoor temperature CDB CWB 18 0 12 0 21 0 15 0 23 0 16 0 27 0 19 0 29 0 21 0 32 0 23 0 CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 0 2 87 1 89 3 24 2 15 3 42 2 48 3 66 2 78 3 91 3 04 4 03 3 49 0 0 2 87 1 89 3 24 2 15 3 42 2 48 3 66 2 78 3 91 3 04 4 03 3 49 5 0 2 87 1 89 3 24 2 15 3 42 2 48 3 66 2 78 3 91 3 04 4 03 3 49 10 0 2 87 1 89 3 24 2 15 3 42 2 48 3 66 2 78 3 91 3 04 4 03 3 49 15...

Page 262: ...ure Indoor temperature CDB CWB 18 0 12 0 21 0 15 0 23 0 16 0 27 0 19 0 29 0 21 0 32 0 23 0 CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 0 2 87 1 84 3 24 2 09 3 42 2 41 3 66 2 71 3 91 2 96 4 03 3 39 0 0 2 87 1 84 3 24 2 09 3 42 2 41 3 66 2 71 3 91 2 96 4 03 3 39 5 0 2 87 1 84 3 24 2 09 3 42 2 41 3 66 2 71 3 91 2 96 4 03 3 39 10 0 2 87 1 84 3 24 2 09 3 42 2 41 3 66 2 71 3 91 2 96 4 03 3 39 15 0 ...

Page 263: ...ure Indoor temperature CDB CWB 18 0 12 0 21 0 15 0 23 0 16 0 27 0 19 0 29 0 21 0 32 0 23 0 CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 0 2 87 1 94 3 24 2 21 3 42 2 54 3 66 2 85 3 91 3 12 4 03 3 58 0 0 2 87 1 94 3 24 2 21 3 42 2 54 3 66 2 85 3 91 3 12 4 03 3 58 5 0 2 87 1 94 3 24 2 21 3 42 2 54 3 66 2 85 3 91 3 12 4 03 3 58 10 0 2 87 1 94 3 24 2 21 3 42 2 54 3 66 2 85 3 91 3 12 4 03 3 58 15 0 ...

Page 264: ...0 1 44 0 46 1 63 0 53 1 72 0 61 1 84 0 69 1 96 0 75 2 02 0 86 Model ASYG12KGTB Outdoor temperature Indoor temperature CDB CWB 18 0 12 0 21 0 15 0 23 0 16 0 27 0 19 0 29 0 21 0 32 0 23 0 CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 0 2 87 1 61 3 24 1 84 3 42 2 12 3 66 2 38 3 91 2 60 4 03 2 98 0 0 2 87 1 61 3 24 1 84 3 42 2 12 3 66 2 38 3 91 2 60 4 03 2 98 5 0 2 87 1 61 3 24 1 84 3 42 2 12 3 66 ...

Page 265: ...6 1 63 0 53 1 72 0 61 1 84 0 69 1 96 0 75 2 02 0 86 Models ASYG12KMTB and ASYG12KMCC Outdoor temperature Indoor temperature CDB CWB 18 0 12 0 21 0 15 0 23 0 16 0 27 0 19 0 29 0 21 0 32 0 23 0 CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 0 2 87 1 61 3 24 1 84 3 42 2 12 3 66 2 38 3 91 2 60 4 03 2 98 0 0 2 87 1 61 3 24 1 84 3 42 2 12 3 66 2 38 3 91 2 60 4 03 2 98 5 0 2 87 1 61 3 24 1 84 3 42 2 12...

Page 266: ...erature Indoor temperature CDB CWB 18 0 12 0 21 0 15 0 23 0 16 0 27 0 19 0 29 0 21 0 32 0 23 0 CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 0 2 87 1 61 3 24 1 84 3 42 2 12 3 66 2 38 3 91 2 60 4 03 2 98 0 0 2 87 1 61 3 24 1 84 3 42 2 12 3 66 2 38 3 91 2 60 4 03 2 98 5 0 2 87 1 61 3 24 1 84 3 42 2 12 3 66 2 38 3 91 2 60 4 03 2 98 10 0 2 87 1 61 3 24 1 84 3 42 2 12 3 66 2 38 3 91 2 60 4 03 2 98 1...

Page 267: ...24 2 09 3 42 2 41 3 66 2 71 3 91 2 96 4 03 3 39 20 0 2 87 1 84 3 24 2 09 3 42 2 41 3 66 2 71 3 91 2 96 4 03 3 39 25 0 2 87 1 84 3 24 2 09 3 42 2 41 3 66 2 71 3 91 2 96 4 03 3 39 30 0 2 87 1 84 3 24 2 09 3 42 2 41 3 66 2 71 3 91 2 96 4 03 3 39 35 0 2 87 1 84 3 24 2 09 3 42 2 41 3 66 2 71 3 91 2 96 4 03 3 39 40 0 2 72 1 64 3 07 1 87 3 23 2 16 3 46 2 42 3 70 2 65 3 82 3 04 46 0 2 56 1 46 2 89 1 67 3 ...

Page 268: ...0 1 67 5 50 1 70 5 40 1 73 5 20 1 77 10 0 8 0 5 80 1 32 5 60 1 34 5 50 1 37 5 40 1 40 5 20 1 43 15 0 10 0 5 80 1 20 5 60 1 23 5 50 1 25 5 40 1 28 5 20 1 30 20 0 15 0 5 80 0 94 5 60 0 96 5 50 0 98 5 40 1 00 5 20 1 02 24 0 18 0 5 80 0 84 5 60 0 86 5 50 0 88 5 40 0 89 5 20 0 91 16 15 0 16 0 3 30 1 34 3 30 1 37 3 20 1 40 3 10 1 43 3 00 1 46 10 0 11 0 3 80 1 39 3 70 1 42 3 60 1 45 3 50 1 48 3 40 1 51 5...

Page 269: ... 71 5 0 3 0 3 23 3 15 3 07 3 00 2 92 7 0 6 0 3 24 3 17 3 09 3 01 2 94 10 0 8 0 3 24 3 17 3 09 3 01 2 94 15 0 10 0 3 24 3 17 3 09 3 01 2 94 20 0 15 0 3 24 3 17 3 09 3 01 2 94 24 0 18 0 3 24 3 17 3 09 3 01 2 94 Model AUXG12KVLA Outdoor temperature Indoor temperature CDB 16 0 18 0 20 0 22 0 24 0 CDB CWB TC TC TC TC TC 15 0 16 0 2 11 2 06 2 01 1 95 1 90 10 0 11 0 2 38 2 32 2 26 2 21 2 15 5 0 7 0 2 65 ...

Page 270: ... 5 0 3 0 3 23 3 15 3 07 3 00 2 92 7 0 6 0 3 24 3 17 3 09 3 01 2 94 10 0 8 0 3 24 3 17 3 09 3 01 2 94 15 0 10 0 3 24 3 17 3 09 3 01 2 94 20 0 15 0 3 24 3 17 3 09 3 01 2 94 24 0 18 0 3 24 3 17 3 09 3 01 2 94 Model ARXG12KSLAP Outdoor temperature Indoor temperature CDB 16 0 18 0 20 0 22 0 24 0 CDB CWB TC TC TC TC TC 15 0 16 0 2 11 2 06 2 01 1 95 1 90 10 0 11 0 2 38 2 32 2 26 2 21 2 15 5 0 7 0 2 65 2 ...

Page 271: ... 5 0 3 0 3 23 3 15 3 07 3 00 2 92 7 0 6 0 3 24 3 17 3 09 3 01 2 94 10 0 8 0 3 24 3 17 3 09 3 01 2 94 15 0 10 0 3 24 3 17 3 09 3 01 2 94 20 0 15 0 3 24 3 17 3 09 3 01 2 94 24 0 18 0 3 24 3 17 3 09 3 01 2 94 Model ARXG12KLLAP Outdoor temperature Indoor temperature CDB 16 0 18 0 20 0 22 0 24 0 CDB CWB TC TC TC TC TC 15 0 16 0 2 11 2 06 2 01 1 95 1 90 10 0 11 0 2 38 2 32 2 26 2 21 2 15 5 0 7 0 2 65 2 ...

Page 272: ...2 02 1 96 1 91 5 0 7 0 2 36 2 30 2 24 2 19 2 13 0 0 2 0 2 99 2 92 2 85 2 78 2 71 5 0 3 0 3 23 3 15 3 07 3 00 2 92 7 0 6 0 3 24 3 17 3 09 3 01 2 94 10 0 8 0 3 24 3 17 3 09 3 01 2 94 15 0 10 0 3 24 3 17 3 09 3 01 2 94 20 0 15 0 3 24 3 17 3 09 3 01 2 94 24 0 18 0 3 24 3 17 3 09 3 01 2 94 Model ASYG12KGTB Outdoor temperature Indoor temperature CDB 16 0 18 0 20 0 22 0 24 0 CDB CWB TC TC TC TC TC 15 0 1...

Page 273: ... 02 1 96 1 91 5 0 7 0 2 36 2 30 2 24 2 19 2 13 0 0 2 0 2 99 2 92 2 85 2 78 2 71 5 0 3 0 3 23 3 15 3 07 3 00 2 92 7 0 6 0 3 24 3 17 3 09 3 01 2 94 10 0 8 0 3 24 3 17 3 09 3 01 2 94 15 0 10 0 3 24 3 17 3 09 3 01 2 94 20 0 15 0 3 24 3 17 3 09 3 01 2 94 24 0 18 0 3 24 3 17 3 09 3 01 2 94 Models ASYG12KMTB and ASYG12KMCC Outdoor temperature Indoor temperature CDB 16 0 18 0 20 0 22 0 24 0 CDB CWB TC TC ...

Page 274: ... 0 3 0 3 23 3 15 3 07 3 00 2 92 7 0 6 0 3 24 3 17 3 09 3 01 2 94 10 0 8 0 3 24 3 17 3 09 3 01 2 94 15 0 10 0 3 24 3 17 3 09 3 01 2 94 20 0 15 0 3 24 3 17 3 09 3 01 2 94 24 0 18 0 3 24 3 17 3 09 3 01 2 94 Model ASYG12KETA ASYG12KETA B Outdoor temperature Indoor temperature CDB 16 0 18 0 20 0 22 0 24 0 CDB CWB TC TC TC TC TC 15 0 16 0 2 11 2 06 2 01 1 95 1 90 10 0 11 0 2 38 2 32 2 26 2 21 2 15 5 0 7...

Page 275: ...oor temperature Indoor temperature CDB 16 0 18 0 20 0 22 0 24 0 CDB CWB TC TC TC TC TC 15 0 16 0 2 11 2 06 2 01 1 95 1 90 10 0 11 0 2 38 2 32 2 26 2 21 2 15 5 0 7 0 2 65 2 58 2 52 2 46 2 39 0 0 2 0 3 36 3 28 3 20 3 12 3 04 5 0 3 0 3 62 3 54 3 45 3 36 3 28 7 0 6 0 3 64 3 56 3 47 3 38 3 30 10 0 8 0 3 64 3 56 3 47 3 38 3 30 15 0 10 0 3 64 3 56 3 47 3 38 3 30 20 0 15 0 3 64 3 56 3 47 3 38 3 30 24 0 18...

Page 276: ...1 59 7 0 1 62 6 8 1 65 6 7 1 68 20 0 15 0 7 4 1 31 7 2 1 34 7 0 1 37 6 8 1 40 6 7 1 42 24 0 18 0 7 4 1 15 7 2 1 18 7 0 1 20 6 8 1 23 6 7 1 25 19 15 0 16 0 4 0 1 63 3 9 1 67 3 8 1 70 3 7 1 73 3 6 1 77 10 0 11 0 4 6 1 68 4 4 1 72 4 3 1 75 4 2 1 79 4 1 1 82 5 0 7 0 5 2 1 73 5 0 1 76 4 9 1 80 4 8 1 84 4 7 1 87 0 0 2 0 6 6 1 90 6 4 1 94 6 3 1 98 6 1 2 02 5 9 2 06 5 0 3 0 7 4 1 90 7 2 1 94 7 0 1 98 6 8 ...

Page 277: ... 5 m Height difference 0 m Outdoor unit Indoor unit 2 or more indoor units should be connected The total ability of connected a indoor unit is from 14 000 Btu h up to 26 000 Btu h Input in the table are calculated based on the maximum indoor unit input combinations 271 6 3 Heating capacity 6 Capacity table OUTDOOR UNIT AOYG14 18KBTA2 OUTDOOR UNIT AOYG14 18KBTA2 ...

Page 278: ...A Outdoor temperature Indoor temperature CDB 16 0 18 0 20 0 22 0 24 0 CDB CWB TC TC TC TC TC 15 0 16 0 2 50 2 44 2 38 2 32 2 26 10 0 11 0 2 88 2 81 2 74 2 67 2 60 5 0 7 0 3 25 3 18 3 10 3 02 2 94 0 0 2 0 4 15 4 05 3 95 3 85 3 75 5 0 3 0 4 64 4 53 4 42 4 31 4 20 7 0 6 0 4 64 4 53 4 42 4 31 4 20 10 0 8 0 4 64 4 53 4 42 4 31 4 20 15 0 10 0 4 64 4 53 4 42 4 31 4 20 20 0 15 0 4 64 4 53 4 42 4 31 4 20 2...

Page 279: ...utdoor temperature Indoor temperature CDB 16 0 18 0 20 0 22 0 24 0 CDB CWB TC TC TC TC TC 15 0 16 0 2 50 2 44 2 38 2 32 2 26 10 0 11 0 2 88 2 81 2 74 2 67 2 60 5 0 7 0 3 25 3 18 3 10 3 02 2 94 0 0 2 0 4 15 4 05 3 95 3 85 3 75 5 0 3 0 4 64 4 53 4 42 4 31 4 20 7 0 6 0 4 64 4 53 4 42 4 31 4 20 10 0 8 0 4 64 4 53 4 42 4 31 4 20 15 0 10 0 4 64 4 53 4 42 4 31 4 20 20 0 15 0 4 64 4 53 4 42 4 31 4 20 24 0...

Page 280: ...utdoor temperature Indoor temperature CDB 16 0 18 0 20 0 22 0 24 0 CDB CWB TC TC TC TC TC 15 0 16 0 2 50 2 44 2 38 2 32 2 26 10 0 11 0 2 88 2 81 2 74 2 67 2 60 5 0 7 0 3 25 3 18 3 10 3 02 2 94 0 0 2 0 4 15 4 05 3 95 3 85 3 75 5 0 3 0 4 64 4 53 4 42 4 31 4 20 7 0 6 0 4 64 4 53 4 42 4 31 4 20 10 0 8 0 4 64 4 53 4 42 4 31 4 20 15 0 10 0 4 64 4 53 4 42 4 31 4 20 20 0 15 0 4 64 4 53 4 42 4 31 4 20 24 0...

Page 281: ...0 3 78 3 69 3 60 3 51 3 42 24 0 18 0 3 78 3 69 3 60 3 51 3 42 Model ASYG12KGTB Outdoor temperature Indoor temperature CDB 16 0 18 0 20 0 22 0 24 0 CDB CWB TC TC TC TC TC 15 0 16 0 2 50 2 44 2 38 2 32 2 26 10 0 11 0 2 88 2 81 2 74 2 67 2 60 5 0 7 0 3 25 3 18 3 10 3 02 2 94 0 0 2 0 4 15 4 05 3 95 3 85 3 75 5 0 3 0 4 64 4 53 4 42 4 31 4 20 7 0 6 0 4 64 4 53 4 42 4 31 4 20 10 0 8 0 4 64 4 53 4 42 4 31...

Page 282: ...9 3 60 3 51 3 42 24 0 18 0 3 78 3 69 3 60 3 51 3 42 Models ASYG12KMTB and ASYG12KMCC Outdoor temperature Indoor temperature CDB 16 0 18 0 20 0 22 0 24 0 CDB CWB TC TC TC TC TC 15 0 16 0 2 50 2 44 2 38 2 32 2 26 10 0 11 0 2 88 2 81 2 74 2 67 2 60 5 0 7 0 3 25 3 18 3 10 3 02 2 94 0 0 2 0 4 15 4 05 3 95 3 85 3 75 5 0 3 0 4 64 4 53 4 42 4 31 4 20 7 0 6 0 4 64 4 53 4 42 4 31 4 20 10 0 8 0 4 64 4 53 4 4...

Page 283: ... B Outdoor temperature Indoor temperature CDB 16 0 18 0 20 0 22 0 24 0 CDB CWB TC TC TC TC TC 15 0 16 0 2 50 2 44 2 38 2 32 2 26 10 0 11 0 2 88 2 81 2 74 2 67 2 60 5 0 7 0 3 25 3 18 3 10 3 02 2 94 0 0 2 0 4 15 4 05 3 95 3 85 3 75 5 0 3 0 4 64 4 53 4 42 4 31 4 20 7 0 6 0 4 64 4 53 4 42 4 31 4 20 10 0 8 0 4 64 4 53 4 42 4 31 4 20 15 0 10 0 4 64 4 53 4 42 4 31 4 20 20 0 15 0 4 64 4 53 4 42 4 31 4 20 ...

Page 284: ... 0 3 0 4 64 4 53 4 42 4 31 4 20 7 0 6 0 4 64 4 53 4 42 4 31 4 20 10 0 8 0 4 64 4 53 4 42 4 31 4 20 15 0 10 0 4 64 4 53 4 42 4 31 4 20 20 0 15 0 4 64 4 53 4 42 4 31 4 20 24 0 18 0 4 64 4 53 4 42 4 31 4 20 Model AGYG14KVCA Outdoor temperature Indoor temperature CDB 16 0 18 0 20 0 22 0 24 0 CDB CWB TC TC TC TC TC 15 0 16 0 2 64 2 58 2 51 2 45 2 39 10 0 11 0 3 04 2 97 2 89 2 82 2 75 5 0 7 0 3 44 3 36 ...

Page 285: ...76 0 950 0 921 2 5 0 993 0 993 0 978 0 952 0 923 0 1 000 1 000 0 985 0 959 0 930 Indoor unit is lower than outdoor unit 2 2 5 1 000 1 000 0 985 0 959 0 930 5 1 000 0 985 0 959 0 930 10 0 985 0 959 0 930 15 0 959 0 930 Heating Pipe length m 2 5 5 10 15 20 Height difference H m Indoor unit is higher than outdoor unit 1 15 0 937 0 915 10 0 956 0 937 0 915 5 1 000 0 956 0 937 0 915 2 5 0 990 1 000 0 9...

Page 286: ...0 927 0 905 15 0 923 0 900 Indoor unit 12 000 Btu h Cooling Pipe length m 2 5 5 10 15 20 Height difference H m Indoor unit is higher than outdoor unit 1 15 0 914 0 877 10 0 959 0 921 0 884 5 0 991 0 965 0 928 0 890 2 5 0 993 0 993 0 967 0 930 0 893 0 1 000 1 000 0 974 0 936 0 899 Indoor unit is lower than outdoor unit 2 2 5 1 000 1 000 0 974 0 936 0 899 5 1 000 0 974 0 936 0 899 10 0 974 0 936 0 8...

Page 287: ...955 0 938 0 921 5 0 994 0 953 0 936 0 919 10 0 949 0 933 0 916 15 0 928 0 911 Indoor unit 9 000 Btu h Cooling Pipe length m 2 5 5 10 15 20 Height difference H m Indoor unit is higher than outdoor unit 1 15 0 928 0 898 10 0 966 0 936 0 905 5 0 991 0 972 0 942 0 911 2 5 0 993 0 993 0 974 0 944 0 913 0 1 000 1 000 0 981 0 951 0 920 Indoor unit is lower than outdoor unit 2 2 5 1 000 1 000 0 981 0 951 ...

Page 288: ...0 932 0 915 15 0 927 0 910 Indoor unit 14 000 Btu h Cooing Pipe length m 2 5 5 10 15 20 Height difference H m Indoor unit is higher than outdoor unit 1 15 0 913 0 873 10 0 959 0 919 0 882 5 0 991 0 967 0 927 0 888 2 5 0 993 0 993 0 969 0 929 0 890 0 1 000 1 000 0 976 0 934 0 895 Indoor unit is lower than outdoor unit 2 2 5 1 000 1 000 0 976 0 934 0 895 5 1 000 0 976 0 934 0 895 10 0 976 0 934 0 89...

Page 289: ...ength m 20 or less 30 Max 20 g m Additional charge g 0 200 8 2 Model AOYG18KBTA2 Refrigerant type R32 Refrigerant amount g 1 020 Refrigerant charge Total pipe length m 20 or less 30 Max 20 g m Additional charge g 0 200 283 8 1 Model AOYG14KBTA2 8 Additional charge calculation OUTDOOR UNIT AOYG14 18KBTA2 OUTDOOR UNIT AOYG14 18KBTA2 ...

Page 290: ... 1 670 l s 464 CFM 983 Heating m3 h 1 670 l s 464 CFM 983 9 2 Model AOYG18KBTA2 Cooling m3 h 1 960 l s 544 CFM 1 154 Heating m3 h 2 020 l s 561 CFM 1 189 284 9 1 Model AOYG14KBTA2 9 Airflow OUTDOOR UNIT AOYG14 18KBTA2 OUTDOOR UNIT AOYG14 18KBTA2 ...

Page 291: ... 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Model AOYG18KBTA2 Cooling Octave band sound pressure level dB 0 dB 0 0002 µbar 80 70 60 50 40 30 20 10 0 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Octave band center frequency Hz 63 125 250 500 1 000 8 000 2 000 4 000 Heating Octave band sound pressure level dB 0 dB 0 0002 µbar 80 70 60 50 40 30 20 10 0 ...

Page 292: ...ar Airflow Rear view Side view NOTE Detailed shape of the actual outdoor unit might be slightly different from the one illustrated above 286 10 2 Sound level check point 10 Operation noise sound pressure OUTDOOR UNIT AOYG14 18KBTA2 OUTDOOR UNIT AOYG14 18KBTA2 ...

Page 293: ...current is the total current of the indoor unit and the outdoor unit 2 Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005 As the regulations of wire size and circuit breaker differ in each country or region select appropriate de vices complied to the regional standard 3 This is the wiring length in case voltage descent is less than 2 When the wiring length be comes...

Page 294: ... motor restart 120 10 C Fan motor restart Compressor protection Temperature thermistor Discharge temp Activate 110 C Compressor stop Reset After 7 minutes Compressor restart Temperature thermistor Compressor bottom temp Activate 108 C Compressor stop Reset After 3 minutes and 80 C or less Compressor restart Thermal protection program Outdoor temp Only in COOL or DRY mode Activate 20 C Compressor s...

Page 295: ...s AOYG14KBTA2 and AOYG18KBTA2 Part name Exterior Q ty Part name Exterior Q ty Installation manual 1 Drain pipe 1 289 13 1 Models AOYG14KBTA2 and AOYG18KBTA2 13 Accessories OUTDOOR UNIT AOYG14 18KBTA2 OUTDOOR UNIT AOYG14 18KBTA2 ...

Page 296: ...sures Reference When installed near adjacent houses Perform installation work so that operating sound does not disturb the neighbors 1 Install a soundproof barrier 2 Change the installation site When there is the possibility of strong wind If the outdoor unit is exposed to strong wind capacity may drop frost may form during heating and operation may be stopped by high pressure rise In addition whe...