2-13. E: 41. Room temperature sensor error (Indoor unit)
Indicator
→ired remote
controller
Error code
E: 41
Detective actuator Indoor unit main PCB
Room temperature thermistor is open or short is
detected always.
Room temperature thermistor
Forecast of cause
Connector failure
Thermistor failure
Main PCB failure
Check point 1. Check connection of connector
•
Check if connector is loose or removed.
•
Check erroneous connection.
•
Check if thermistor cable is open
-> Reset power when reinstalling due to removed connector or incorrect wiring.
Check point 2. Remove connector and check thermistor resistance value
•
For the room thermistor resistance value, refer to
"Thermistor resistance values"
•
If thermistor is either open or shorted, replace it and reset the power.
Check point 3. Check voltage of main PCB
Make sure circuit diagram of each indoor unit and check terminal voltage at thermis-
tor (DC 5.0 V).
NOTE:
For details of thermistor connector, refer to
TECHNICAL DATA AND PARTS LIST on page 02-22.
If the voltage does not appear, replace main PCB.
End
2-13. E: 41. Room temperature sensor error (Indoor unit)
- (03-17) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Summary of Contents for ACUH09LUAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 04 02 SR_CH01_AU021EF_01 ...
Page 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 04 02 SR_CH02_AU021EF_01 ...
Page 45: ...3 TROUBLESHOOTING 2021 04 26 SR_CH03_AU021EF_01 ...
Page 48: ......
Page 105: ...4 CONTROL AND FUNCTIONS 2021 04 26 SR_CH04_AU021EF_01 ...
Page 143: ...5 FILED WORKING 2021 04 26 SR_CH05_AU021EF_01 ...