2-2. E: 11. Serial communication error (Serial forward transfer
error) (Indoor unit)
Indicator
→ired remote
controller
Error code
E: 11
Detective actuator Indoor unit
Main PCB
→hen the outdoor unit cannot properly receive the serial
signal from indoor unit for 10 seconds or more.
Fan motor
Outdoor unit
Main PCB
Forecast of cause
Connection failure
External cause
Main PCB failure
Check point 1. Reset the power and operate
Does error indication show again?
Check point 2. Check connection
Check any loose or removed connection line of indoor unit and outdoor unit.
If there is an abnormal condition, correct it by referring to the installation manual or the “DESIGN
& TECHNICAL MANUAL”.
Check connection condition is control unit. (If there is loose connector, open cable or mis-wiring.)
Check point 3. Check the voltage of power supply
Check the voltage of power supply
Check if AC 198 V (AC 220 V -10%) to AC 264 V (AC 240 V +10%) appears at
outdoor unit terminal L — N.
+
-
2-2. E: 11. Serial communication error (Serial forward transfer error) (Indoor unit)
- (03-5) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Summary of Contents for ACUH09LUAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 04 02 SR_CH01_AU021EF_01 ...
Page 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 04 02 SR_CH02_AU021EF_01 ...
Page 45: ...3 TROUBLESHOOTING 2021 04 26 SR_CH03_AU021EF_01 ...
Page 48: ......
Page 105: ...4 CONTROL AND FUNCTIONS 2021 04 26 SR_CH04_AU021EF_01 ...
Page 143: ...5 FILED WORKING 2021 04 26 SR_CH05_AU021EF_01 ...