Release condition
The defrost operation is released when either one of the conditions below is satisfied.
Outdoor unit heat exchanger temperature
(after 1 minute or later since compressor start)
18/22/24 model
13°C or more
30/36/45 model
12°C or more
Compressor operation time
15 minutes
6-1. Defrost operation in heating operation stopped
If the outdoor unit is frosted when stopping the heating operation, it stops after performing the auto-
matic defrosting operation.
In this time, if the indoor unit operation lamp flashes slowly (6 sec on/2 sec off), the outdoor unit al-
low the heat exchanger to defrost, and then stop.
•
Triggering condition
When all of the following conditions are satisfied in heating operation
– Compressor operation integrating time: 30 minutes or more
– Compressor continuous operation time: 10 minutes or more
– Outdoor unit heat exchanger temperature: -4°C or less
•
Release condition
The defrost operation is released when either one of the conditions below is satisfied.
Outdoor unit heat exchanger temperature
(after 1 minute or later since compressor start)
18/22/24 model
13°C or more
30/36/45 model
12°C or more
Compressor operation time
15 minutes
6-1. Defrost operation in heating operation stopped
- (04-30) -
6. Defrost operation control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for ABYG18KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB004EF_03 ...
Page 24: ...2 2 Outdoor unit 01 18 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 25: ...2 TECHNICAL DATA AND PARTS LIST 2020 12 09 SR_CH02_AB004EF_05 ...
Page 71: ...3 TROUBLESHOOTING 2020 07 01 SR_CH03_AB004EF_01 ...
Page 74: ......
Page 138: ...5 2 Outdoor unit 03 64 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 139: ...4 CONTROL AND FUNCTIONS 2020 07 01 SR_CH04_AB004EF_01 ...
Page 141: ...8 8 High temperature and high pressure release control 04 42 CONTENTS continued ...
Page 142: ......
Page 187: ...5 FILED WORKING 2020 07 01 SR_CH05_AB004EF_01 ...