1. Compressor frequency control
1-1. Cooling operation
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference
or variation between a set temperature and present room temperature, and controls the operation
frequency of the compressor.
• If the room temperature is 6.0 °C higher than a set temperature, the compressor operation fre-
quency will attain to maximum performance.
• If the room temperature is 1.0 °C lower than a set temperature, the compressor will be stopped.
• When the room temperature is within the range of +6.0°C to -1.0°C of the setting temperature, the
compressor frequency is controlled within the range shown in the table below. However, the maxi-
mum frequency is limited in the range shown in the figure below based on the indoor fan mode
and the outdoor temperature.
•
Compressor frequency range
Model name
Minimum frequency
Maximum frequency
ABHG54KRTA
17 rps
95 rps
•
Limit of maximum speed based on outdoor temperature
36°C
A zone
34°C
32°C
B zone
30°C
21°C
C zone
19°C
D zone
E zone
F zone
10°C
0°C
12°C
2°C
Outdoor
temperature drops
Outdoor
temperature rises
Unit: rps
Model name
Outdoor
temperature
zone
Indoor unit fan mode
HIGH
MED
LOW
QUIET
ABHG54KRTA
A zone
95
66
51
33
B zone
95
66
51
33
C zone
80
51
41
33
D zone
56
41
35
27
E zone
56
41
35
27
F zone
56
41
35
27
1-1. Cooling operation
- (04-1) -
1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for ABHG54KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 04 16 SR_CH01_AB007EG_01 ...
Page 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB007EG_02 ...
Page 31: ...3 TROUBLESHOOTING 2020 07 29 SR_CH03_AB007EG_01 ...
Page 34: ......
Page 95: ...4 CONTROL AND FUNCTIONS 2020 07 29 SR_CH04_AB007EG_01 ...
Page 97: ...8 8 High temperature and high pressure release control 04 29 CONTENTS continued ...
Page 98: ......
Page 129: ...5 FILED WORKING 2020 07 29 SR_CH05_AB007EG_01 ...