- (02 - 03) -
O
U
TD
O
O
R U
N
IT
AO
A
45
-5
4LC
O
U
TD
O
O
R U
N
IT
AO
A
45
-5
4LC
INSTALLATION PLACE
3.
SINGLE OUTDOOR UNIT INSTALLATION
3-1.
WHEN THE UPWARD AREA IS OPEN
(Unit : mm)
Obstacles at rear
only
Obstacles at rear and
sides only
Obstacles at front
only
150
200
200
300
1000 or more
Obstacles at front and
rear only
1000 or more
150
WHEN AN OBSTRUCTION IS PRESENT ALSO IN THE UPWARD AREA
(Unit : mm)
Obstacles at rear and
above only
Obstacles at rear, sides, and above only
Max. 500
300
1000
Max. 500
500
250
250
1500