MODEL :18/24/36/42RLX Systems

Duct Fan Control

SOLUTION

Fresh Air Intake w/ Compressor Operation Only

PROBLEM

SERVICE BULLETIN
Number: 0006
Date:  9/22/09 Rev2
Type: Field

FUJITSU GENERAL AMERICA, INC

353 Route West. Fairfield, NJ 07004
Ph: 973-575-0381 Fx: 973-836-0449

Em: [email protected]

1. Outline

The circuit shown below provides a cost effective solution for wiring a current switch 
that monitors the compressor operation ON/OFF status and energizes the coil of a 
relay which in turn close the contacts and provide line voltage to the duct fan. The 
duct fan is required to introduce fresh (outside) air for ventilation.

2. Application

A third party current sensor switch with a built-in relay was
used in this application. The current sensor may be
installed around one of the compressor line voltage wires (Red, 
Black or White).

3. Wiring diagram

Duct fan booster

Compressor

N.O.

24V DC

115V AC

IPM

Current Sensor

Built in Relay

N.O.

N.O.

+
_

Summary of Contents for 18RLX

Page 1: ...solution for wiring a current switch that monitors the compressor operation ON OFF status and energizes the coil of a relay which in turn close the contacts and provide line voltage to the duct fan The duct fan is required to introduce fresh outside air for ventilation 2 Application A third party current sensor switch with a built in relay was used in this application The current sensor may be ins...

Page 2: ...Current Status Sensor with Command Relay and Switching Power Supply FGAI Fresh Air Kit Part KHRS940 25 5 Recommended Fan size Duct and Fan are field supply A fan capable of generating 15 CFM at a static pressure of approximately 26 inches W C Wiring Recommended wire size 14 AWG 10A Fuse Field Supply ...

Page 3: ...ll the current sensor around one of the compressor line voltage wires Tuck sensor into the clearance behind the compressor wire molex plug Secure the current sensor with a zip tie Current Sensor Installation ...

Page 4: ...eeded for correct installation Secure the current sensor wires with all four zip ties according to the arrows Do not tie around any of the copper lines Cut the ends of the zip ties 1 2 3 4 1 2 3 4 Secure Current Sensor ...

Page 5: ...tte 24 in W C 25 ft 4 duct intake 45ft TEL x 04 100 018 in W C TOTAL 258 in W C Fan Selection Select fan to deliver 15 CFM approximately 26 in W C Static pressure requirements will vary with duct length and inlet conditions NOTE Filter for outside air required Add filter static pressure loss to static pressure requirements above CEILING CASSETTE OUTSIDE FRESH AIR INTAKE ...