![FujiFilm PXG4 Operation Manuals Download Page 61](http://html1.mh-extra.com/html/fujifilm/pxg4/pxg4_operation-manuals_2342483061.webp)
– 60 –
6
Chapter
Guaranteed Soak
,
Guaranteed Soak Lower Limit
,
Guaranteed Soak Upper Limit
This function guarantees soak time. Soak time only
counts down when SV is in the proper temperature range.
In the diagram below, the total of the shaded regions
counts towards soak time. When this total matches the
specified soak time, the cycle proceeds to the next step.
The following settings are available.
•
Guaranty soak
: Yes/No
•
Guaranty soak upper limit : 0% to 50% FS
•
Guaranty soak lower limit : 0% to 50% FS
Setting Guaranty Soak
The following steps explain how to set guaranty soak by using
guaranty soak = "Yes" and a range of 5°C between the upper
and lower limits as an example.
1
Press and hold the
key to display the setup
mode channel menu ("
ooo
oPPPPEEEE CCCChhhh 1111
"), then use the
keys to display PrG ("
PPP
PrrrrGGGG CCCChhhh 4444
").
Refer to
See p. 56 in this chapter for information on how to display
the operation menu.
2
Press and hold the
key, the use the
keys to display GSok ("
GGG
GSSSSooookkkk
").
Select an activation pattern.
3
Press the
key, then use the
keys to
select "on" when the bottom part of the display
begins to blink.
Guaranty soak is set.
PV
t
set value
T1
T2
T3
soak time = T1+T2+T3
SV
guaranty soak band
upper limit
guaranty soak band
lower limit
4
Press the
key to confirm the setting.
5
Use the
keys to display GS-L ("
GGG
GSSSS----LLLL
").
Set the guaranty soak lower limit.
6
Press the
key, then use the
keys to
set 5.0 when the bottom part of the display begins
to blink.
The guaranty soak lower limit is set to 5.0°C.
7
Repeat steps 5 and 6 to set the guaranty soak
upper limit GS-H ("
GGG
GSSSS----HHHH
").
8
Press the
key to return to the operation mode
PV/SV display.
Summary of Contents for PXG4
Page 1: ...c...
Page 10: ...9 1 Chapter Chapter 1 Part Names and Functions Part Names and Functions 10...
Page 21: ...20 MEMO 2 Chapter...
Page 43: ...42 MEMO 4 Chapter...
Page 53: ...52 MEMO 5 Chapter...
Page 71: ...70 MEMO 7 Chapter...
Page 89: ...88 MEMO 8 Chapter...
Page 106: ...105 9 Chapter Behavior when control is lost Limit Cycle PV SV Time tuning MV control lost 100...
Page 119: ...118 MEMO 10 Chapter...
Page 125: ...124 MEMO 11 Chapter...
Page 131: ...130 MEMO 12 Chapter...
Page 141: ...140 MEMO 14 Chapter...
Page 151: ...150 MEMO 15 Chapter...
Page 152: ...151 16 Chapter Chapter 16 Troubleshooting Troubleshooting 152...
Page 157: ...156 MEMO 17 Chapter...